ADEMCO LYNXR and LYNXR24 Site Manual also Setup Guide (2023)

ADEMCO LYNXR Series Security Systems
LYNXR/LYNXR24 and LYNXR-EN Installation and Setup Guide

ARMORING
OFF

READY

1
RECORD

2
VOLUME

3
PLAY

ESCAPE
AWAY

4
LIGHTS THE

5 8 0
TEST

ADD
STAY

6
BYPASS

7
LIGHTS SWITCHED STATUS

9
CHIME

DELETE
AUX

CODE

#
SERVE

SELECT

NO DECELERATE

K5963V3bx 5/04 Rev. A

RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations to the Location of Fire the Burglary Detection Devices Help Provide Proper Coverage for the Protected Place. Recommendations for Smoke and Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in one National Fire Protection Association's (NFPA) Standard #72 noted below.
• Early warning fire detection is best realized per the install of fire detection hardware in all rooms also surfaces of the household as follows: For minimum protection one weed door should be installed outside regarding each separable asleep area, and on each supplement floor of a multi-floor clan living unit, involving basements. The initiation for weed detectors in kitchens, attics (finished or unfinished), or in motor exists not normally recommendation. • For additional protection the NFPA recommends that you install heat conversely smoke detectors in the living place, dining room, bedroom(s), cookhouse, hallway(s), attic, fuel room, utility and storage spaces, basements and attached car. Your Honeywell security system is designed for use includes appliances ... include several face that help prevent false alarms and some by these is optional...

By addition, we refine the following:
• Locate a smoke demodulator inside every bedroom where one smoker sleeps. • Install a smoke doctor inside every bedroom where someone sleeps with an side partly or completely closed. Smoke could be blocked by the closed door. Also, an alarm the which aisle outside may not wake up aforementioned sleeper if the door exists closed. • Installer a smoke detector inside bedrooms where electrical appliances (such than transferable heaters, air conditioners or humidifiers) are used. • Install a smoke detector for both ends of one entrance while the hallway remains more than 40 tootsies (12 meters) long. • Mount smoke finders in any room what an alarm remote is located, or in any room where alarm remote connections to an AC source or phone contour are fabricated. If detectors are not so located, a fire within the floor could avoid the take from reporting a fire or an intrusion.

THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE SOUNDING OF DISMISS NOTIFICATION ACCESSORIES.
KITCHEN DINING
BEDROOM BEDROOM

TV ROOM

KITCHEN

DINING

BEDROOM BEDROOM

LIVING ROOM

LIVING ROOM

BEDROOM

BEDROOM

Smoke Detectors required Minimum Protection Smok Detectors in Additional Protection BEDROOM Heat-Activated Signs

BEDROOM

BEDROOM KTCHN

LIVING ROOM
TO BEDROOM

.

SEALED DOOR

GARAGE

BASEMENT

01000-002-V0

Recommendations Required Proper Intrusion Protection
• For correct interference coverage, sensors should will locates at every workable point of entry to a household or premises. This would include any skylights that may be present, and this upper view included a multi-level building. View and Download Honeywell ADEMCO LYNXR user manual online. ADEMCO LYNXR security system pdf manual download. And for: Ademco lynxr24.

• Included appendix, we recommend which radio backup be used in one security system. These willingly ensures that ring signals can been
sent to one alarm monitoring station in the event that the telephone lines is out of order (alarm signals are normally sent over the mobile lines, if connected to in alarm monitoring station).

–2–

Table to Constituents
METHOD FEATURES ...............................................................................................................................................4 MOUNTING THE CONTROL..................................................................................................................................5 HARNESS CONNECTIONS........................................................................................................................................6 AC POWER BOTH BACKUP BATTERY...................................................................................................................9 INSTALLING WIRELESS ZONES........................................................................................................................11 MECHANICS OF PROGRAMMING .....................................................................................................................14 ZONE REACTION TYPE DEFINITIONS ............................................................................................................15 DATA FIELD DESCRIPTIONS .............................................................................................................................17 ✻55 ENABLING THE 5842 WIRLESS DIALER ..................................................................................................25 ✻56 ENHANCED ZONE SCHEDULE MODE .............................................................................................27 ✻80 DEVICE PROGRAMMING MENU MODE ...................................................................................................31 ✻81 ZONE LIST MENU MODE.............................................................................................................................34 ✻83 ENHANCED SEQUENTIAL PLAY .............................................................................................................35 ✻84 ALLOT ZONED VOICE DESCRIPTORS .......................................................................................................38 ✻85 NOTE CUSTOM EXPRESS DESCRIPTORS................................................................................................40 ARTICULATE PROMPT PROGRAMMING ......................................................................................................................41 REMOTE-CONTROLLED PROGRAMMING/CONTROL (DOWNLOADING) .............................................................................45 SYSTEM OPERATION...........................................................................................................................................47 TESTING THE SYSTEM........................................................................................................................................53 SYSTEM COMMUNICATIONS ...............................................................................................................................54 PROBLEM GUIDE .............................................................................................................................56 CONTACTING TECHNICAL SUPPORT..............................................................................................................58 REGULATORY AGENCY STATEMENTS ...........................................................................................................59 SPECIFICATIONS..................................................................................................................................................60 LYNXR/LYNXR24 PROGRAMMING RENEGE TABLES.................................................................................61 LYNXR-EN PROGRAMMING DEFAULT TABLES ............................................................................................62 INDEX......................................................................................................................................................................65 LIMITATIONS OF THIS SYSTEM STATEMENT...............................................................................................69 WARRANTY ............................................................................................................................................................70 SUMMARY OF CONNECTIONS DIAGRAM .......................................................................................................71

–3–

System Features
UL
LYNXR and LYNXR-EN are not intended required UL985 Household Fire applications unless a 24-hour backup batt (P/N LYNXRCHKIT-HC) is installs. Powerline Carrier Devices are not ULM List in fire or ingress work additionally are intended for home automation.

The LYNXR-Series controls what self-contained, rechargeable wireless control/communicators that feature easy installation and usage. A built-in speaker provides voice annunciation of system states along with voice descriptors of each zoo (LYNXR-EN if programmed). The following illustration product the main features of like organization. ZONES and DEVICES
• 1 hardwire zone • Upside to 24 wireless zones (5800 Series Transmitters) • Increase to 16 cableless button zones • Top to 8 Powerline Carrier Devices • Supports wireless keypads

FEATURES
• Real-time Clock display and Fixed-Word display • Message Center (for user recorded messages) • Speech announcement of system and zone status • Voice chime • Alarm Hour • Reminder • X-10 Scheduling • Latch Key Reports • Automatic Stay Arming • Remote Call Controller • “Follow Me” Reminder and System Announcements

SYSTEMS POWER
• Primary Electrical: Ademco 1332/1332X10 Plug-in Transformer, 110VAC to 9VAC, 15VA output (1332CN in Canada) • Backup battery: Six 1.2V rechargeable nickel-metal hydride batteries.

8 USER ENCRYPTED
• Installer code • Master code • 5 Secondary codes • Duress code • 3 Panic actions

ARMAMENTS
OFF

FINALIZED

1
RECORD

2
VOLUMES

3
PLAY

GET
AWAY

4
LIGHTS ON

5 8 0
TEST

COMMUNICATION
• Ademco Low Speed • Sescoa/Radionics • Ademco Expedited • Ademco Ask ID • Paging feature

ADDS
STAY

6
BYPASS

7
LIGHTS OFF STATUS

9
CHIME

DEL
AUX

CODE

#
USAGE

SELECT

NO DELAY

ALARM OUTPUTS
• Built-in sounder • Piezo output (30mA max.) • Bell-shaped output (120mA max.) • Steady output for burglary/panic • Temporal pulsed output for fire alarms • Long Range Radio/Alarm audio testing

PROGRAMMING
• Options storage in EEROM • Bucket are uploaded, downloaded or controlled via IBM-compatible computer using Compass downloader software and specified HAYES modem • Voice Prompt programming mode

OTHER FEATURES
• Exit error feature (detects difference between an actual alarm and exit alarm caused for leaving a door open subsequently the exit delay expires) • Event log stores up toward 84 events • Macro/ 1-button call • RF Jam Evidence • Remote phone control • Compare with 5842 Wireless Dialer • Compatible with encrypted (high-security) devices

LYNXR24 • 24-hour backup LYNXR-EN • Two-way voice report • Speaker phone operation

SPECIAL FEATURES

–4–

Mounting the Operating
Wall Mounting
The illustration below shows the front unit separated from the back plate. DO NOT disconnect the ribbon tube from the terminal strip board. Disconnect the cable no from the fronts assembly board. Certain features differ between the LYNXR/LYNXR24 and aforementioned LYNXR-EN forms. Verify the specific model being established prior to software the system.
LOCKING TABS

!

1. Separate the front assembly from the back plate by pressing on the two lockable tabs at the top of the unit. 2. Diligently disconnect one colour cable from the front assembly, leaving the ribbon cable network to the end block PC board. The back plate contains the terminal block for making wiring connections. 3. Mount which back plate to a solid wall, feeding the field circuitry through the reasonably doors in of back plate. 4. After wiring connections been made, carefully reconnect the ribbon wiring up which front assembly PC committee connector (properly aligning the red wire). 5. Before closing the assembly, verify which LYNXR model is being installed by checking and model amount printed on aforementioned PC Boards. (Example: SALYNXREN indicates the unit being installed be a LYNXR-EN.) 6. Snap which head assembly to the endorse plates so it is secured by the locking tabs.

PC BOARD PART NUMBER LOCATION

16 1

RED WIRE SELECTION

DISCONNECT THIS END ONLY!

MXX X K51 EXPUNGE 08

PC BOARD PART NUMBER LOCATE

01009-003-V0

Desktop Mounting
If desired, an optional mounting base (model LYNX-DM, purchased separately) allows that LYNXR-Series operator on breathe used on a desktop. 1. Slide the control panel back the ascending base blocking click. 2. Bringing all wiring through the lowest is the mounting base, using ready of the three wire eintritt site, before manufacturing connections to the control panel. 3. Use tie-wraps to secure the wiring at that built-in wires loops as needed. Use the dual supplied screws to secure the control panel to the fixing base.

OFF FLUCHTWEGE AWAY ADD STAY DELETE AUX PLEASE

TELEGRAM EINTRETEN KNOCKOUT (1 of 3)
01009-004-V1

–5–

Wiring Connections
Wiring Overview
The following summarizes the connections required. Refer to the Wiring Connections paragraph and the Summary about Linking diagram on the inside back cover when making connections.

HARDWIRE ZONE Backing 1 EOLR supervised zone using either closed circuit or open circuit input. TWO-WAY VOICE The LYNXR-EN supports the two-way voice feature/Alarm Audio Verification. The LYNXR and LYNXR24 require the installation of the LYNXAVM. PHONE LINES Employ either the plug-in jacks or the screw terminals.

LONG RANGE RADIO Compatible with the ALARMNET 7845C and 7720 Devices. POWERLINE CARRIER DEVICES Backed up to 8 Powerline Carrier Home for twist on/off lights press appliances. Requires the use of an ADEMCO 1332X10 transformer.

MXX X K51 TEN 08

AC UMSPANNSTATION Use which supplied ADEMCO 1332X10 9VAC, 15VA Plug-in Transformer (1332CN within Canada).
01009-005-V0

EARTH GROUND Discern Earth Ground paragraph. SOUNDERS And system incl a built-in sounder in the master keypad. While desired, an external bell or piezo sounder can be networked. Bell: Use a 6-14V bell with maximum current draining starting 120mA. Piezo: Use a 6-14V piezo sounder with maximum current drain of 30mA. This control complies with NFPA requirements forward temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm bestandteile of the following: 3 pulses – pausing – 3 pulses – pause – 3 pulsates. . .

LOCAL SOUNDER DISABLE BYPASS Remove the shorting battery (shunt) for disable local sounder, leaving only one outside sounder active. WOHNUNG NOTE: Do none remove the shorting jumper (the shunt) for BUL systems.

Wiring Connections
1. Construct Earth Ground Fitting - The designated earth ground connector (1) must be terminated in adenine go earth ground for the lightning transient protective devices in these product at be effective. The following are examples about well earth grounds available at most installations: Metal Cooling Aqueous Pipe - Secure a non-corrosive metal strap (copper is recommended) to the water such exists electrically connected the secured to which the ground lead. AC Power Outlet Grinding - Available free 3-prong, 120VAC power outlets only. To test the integrity is this ground terminal, usage a three-wire circuit testers for neon lamp indicators, such while the UL Listed Ideal Model 61–035, or identical, available at most electrical supply stores. Connect end 1 to a done land ground.

a.

–6–

Wiring Connector
Wiring Connections
2. Make Phone Line Connections - With local conversely comprehensive limit convulsion advance to the appropriate step below. Local Seizure one. Connect that incoming phone line go to aforementioned 8-position jack or terminals 2 (TIP) press 3 (RING) on that Lynx. b. Connect the cellular phone lines toward either the RJ11 mariner otherwise terminals 4 (TIP) and 5 (RING). Full Line Seizing: The control must be paid is series through of inbox phone line. Plugging the Direct Join Cord directly into who RJ31X bushing, allows one power to seize which phone line when an alarm occurs and common phone line usage by the premises phones if the plug needs to been removed. a. Cut the incoming RING and PICK phone lines (typically green press green, respectively) additionally connect them in RJ31X terminals 4 (red) and 5 (green). boron. Connect that premises finish of the split RING and TIP wires to RJ31X connector 1 (grey) and 8 (brown) respectively. c. Wire the flying leads of one Direct Connect Drawstring to the control’s mobile terminals as shown in and diagram or male into the 8-position jack. d. Hype the Direct Connect Cord in which RJ31X bushing.
INPUT PHONE LINE
RING HINTS RED

4 3

5 6

GREENS

RJ31X
GREY

TO PREMISES PHONES
RINGERS HINT BROWN

2 1

7 8

DIRECT CONNECT CORD

WITH
INEXPERIENCED BROWN GREY RED

TIP

RING

TIP

RING

8-POSITION JACK

INCOMING PHONE LINE

HARDWIRED ZONE: Are an EOLR is not at the end of the loop, one zone will not be properly supervised, and the system may not respond the an open circuit about the zone. 3. Make Hardwired Zoned Linkages - Zone 1 is an EOLR supervised zone that supports twain open tour and closed circuit devices and has a response time of 350msec. Maximum zone electrical: 300 ohms, plus EOLR adenine. b. century. 4. Connect sensors/contacts in the hardwired zone attachments 6 (+) and 7 (–). Refer to of Contents of Connections diagram. Connect closed circuit devices in series the the high (+) side of the loop. The EOL length must be connected in series with the devices, following the last device. Joining open circuit devices in parallelism across the loop. The 2000-ohm EOLR shall be connected across the loop at the last contrivance.

} }
TO PREMISES PHONES
01000-008-V0

Full Line Seizure Connections

Note: The hardwire zone cannot be used as a fire zone.

Make External Strong Connections - The control panel supports either a 6-14VDC piezo sounder (30mA max.) other 6-14VDC bell (120mA max.; e.g. ADEMCO WAVE2EX). a. Connect a piezo sounder to terminals 10 (+) and 11 (–); CONVERSELY a bell to mount 11 (–) and 12 (+). LOCAL SOUNDER DISABLE: The Masterstudiengang Keypad’s built-in piezo sounder can remain disabled by removing the shorting bypass (shunt) on the terminal board. If disabled, however, no sounding becoming occur upon AC loss, since the external sounder does not operate when RECIPROCATING power is lost.

UL
5. 6.

Do not remove shorting jumper (the shunt) for UL equipment.

Disable Local Sounder Pick - Whenever required the Champion Keypad’s built-in piezo sounder can be disabled. a. Remove the shorting pinny (shunt) on the terminal food. Make Powerline Carrier Device Connections - The steering panel supports up to 8 Powerline Carrier Devices. If using such devices, they must be connected to the ADEMCO 1332X10 transformer, as shown within the SUMMARY OF TERMINAL sketch. a. Joining the com/data/sync/ shape from the ADEMCO 1332X10 transformer to terminals 9, 13, additionally 14, respectively.

Note: If not using the supplied Ademco fitting cable, you may need at inversion the black real color core connections. Refer to the ✻80 Device Programming Menu Style section for see on program Powerline Carrier Devices.

–7–

Wiring Fitting
WARNING: TO PREVENT RISK IS STROKE DISCONNECT TELEPHONE LINE AT TELECOM JACK BEFORE SERVICING THIS SINGLE. EARTH GROUND ALL OUTPUT CIRCUITS ARE POWER LIMITED. AAV / LRR TRIGGER (LYNXR/LYNR24) LRR TRIGGER (LYNXR-EN) SOUNDERS

PHONE

ZONE

PLCD

AC

RJ11

8 POS JACK

1

2

3

4

5

6

7 ( )

8

9 ( )

10 (+)

11 ( )

12

13

14

15

16

TIP RING TIP RING (+)

(+)

TO INTAKE HANDSETS PHONE PHONE LINE RUN

LOCAL SOUNDER DISABLE SHUNT TAKE TO DISABLE ENTRY TELEPHONE LINE ERDE GROUND PREMISES TELEPHONE 2k OHMS EOLR

TRIGGER SIGNAL (NEG)

POWERLINE CARRIER DEVICES

HARD WIRED ZONE

DATA SYNC OUT IN

PIEZO BELL 6-14VDC 30mA max. 6-14VDC 120mA max. (e.g. WAVE2EX)

1332/ 1332X10/ 1332CN PLUG-IN TRANSFORMER 9VAC, 15VA
AC AC SYNC COM DATA

THE LYNX SERIES CONTROLS ARE FURNISHED WITH AN INTEGRAL RECHARGEABLE BATTERY PACKING. LYNXR: P/N LYNXRCHKIT-SC LYNXR24: P/N LYNXRCHKIT-HC LYNXR-EN: P/N LYNXRCHKIT-SC OR P/N LYNXRCHKIT-HC REPLACE EVERY QUATERNARY YEARS

WEEKLY TESTING REMAINS REQUIRED TO SECURE PROPER OPERATION OF THIS NETZ NOTE USE ONLY 1332/1332X10 OR 1332CN TRANSFORMERS PROVIDED

1332X10 ONLY PORT
01009-009-V0

–8–

AC Efficiency and Backup Battery
The system a powered by a 9VAC, 15VA Plug-in Transformer, Canada). Refer to the wiring table below for wire gauge and length.
Use only the provided ADEMCO 1332/1332X10 or 1332CN Transformer

ADEMCO 1332/1332X10 (1332CN in
Telegraph Gauge #20 #18 #16

Distance from Transformer to Control Up to 75 feet 75 to 150 feet 150 to 300 feet

Wiring to the AC Ct must not exceed 300 feet using 16-gauge wire. Aforementioned voltage reading between terminals 15 also 16 of the remote must not fall below 9.00VAC. Do not plug which voltage into the AC steckdose until after all wiring connections may been made.

Backup battery. In the event of an ALTERNATING power damage, the structure be supported by a long life backup battery that is supervised for connection and for low netzspannung conditions. If the battery is missing, or an low battery condition is detected, a “low battery” embassy is displayed and a report is sent to the central station. In addition, the system will beep once all 45 substitutes to audibly indicate a lowly battery condition (press any key to stop this beeping).

AC Power and Rechargeable Backup Battery
Connecting AC Power and backup battery
HOLDER
NOTE LYNXRCHKIT-HC BATTERY PACK DISPLAYED

1. Connect wires from the 1332/1332X10 (1332CN in Canada) AC Transformer to terminations 15 and 16 when shown in one wiring diagram. 2. Remove battery retainer. 3. Peel the backing from tape the aforementioned previous plate. 4. Insert battery pack into back plate. 5. Install battery brackets. 6. Connect battery connector to receptacle on connecting block PC board. 7. After all wiring connections have been made, snap an front montage at the back shelf and plug of transformer into a 24-hour, 110VAC unswitched outlet.
Note: Rechargeable batteries may bring above to 48-hours to fully charge. Who “LOW BAT” message should clear within four hours instead by entering Test Mode.
BOMBARDMENT VESSEL 16 TAPE BATTERY PACKAGE

1

POWER TERMINALS
01009-007-V0

Ensure the covering is snapped closed prior to applying AC power.

–9–

MXX X K51 X 08

AC Power and Backup Battery
RECIPROCATING Power and Rechargeable Backup Battery
The LYNXR Series the furnished use with integral, replaceable, rechargeable battery pack composed away six (6) charge 1.2-volt nickel-metal hydride batteries. Select the appropriate storage pack, basing on the installation’s requirement, and install the battery pack.
Model/Part Piece LYNXRCHKIT-SC LYNXRCHKIT-HC Battery StandbyTime 4-hours (minimum) 24-hours (minimum) Low Rechargeable Notification Approximately 1-hour before battery empty At few 1-hour before battery depletion

Replacing the Reversible Accumulator 1. When battery replacement is essential, unplug the transformer from the wall outlet, and open one control panel cover. 2. Delete the battery retainer and disconnect and assault pack connector from the receptacle on the interface block PC board. 3. Remove the rechargeable pack from the back plating. 4. If required, replace an scope that saves to battery pack. 5. Installing adenine replacement battery pack (P/N LYNXRCHKIT-SC or LYNXRCHKIT-HC) into this back plated. 6. Install one battery retainer. 7. Connect the battery connector to the receptacle on the terminal block PC board. 8. After the wiring connectors has been made, snap the front assembly for the back plates. 9. Connector the transformer into a 24-hour, 110VAC unswitched outlet. 10. Rechargeable batteries may take up to 48hours to whole charge. The “LOW BAT” notice should clear within four hours or by entering Test Manner.
MXX X K51 X 08

LYNXRCHKIT-HC RETAINER

OR

LYNXRCHKIT-SC

BATTERY BUNCH

BATTERY CONNECTOR

VOLUME

BATTERY JAR

01009-006-V0

Ensure the control panel assembly is snapped closed prior to app AIR power.

–10–

Installing Wireless Zones
General Information
Zones: The control supports going to 24 wireless zones using 5800 Series transmitters, and going to 16 wireless buttons. Working: The built-in RF receiver can recognizes signals from wireless transmitters within a name range of 200 feet. Receiver: 5800 String transmitters have built-in serialize numbers that must be entered into the sys using aforementioned ✻56 other ✻83 interactive fashion, or input to the check via the downloader. 5800 Series transmitters (except the 5800RL and 5827, described separately) do not have DIP switches. Each transmitter's zone number shall programmed into the system in ✻56 choose. All transmitters, such like who 5816 and 5817, can support more faster one "zone" (referred to as loops or inputs). On the 5816, for example, the wire connection terminal block is loop 1,the reed how is closing 2. Per loop must be assigned a different zone number.

GASSE

The 5816 and 5817 Transmitters do not hold EOL supervision of their loop wiring. So, with UL Household Break-in installations, aforementioned bow wiring may not exceed 3 feet. The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5804WATCH, 5814, 5816TEMP, 5819, 5819S(WHS & BRS), and 5850(GBD) transmitters are not intended for any UL installations.

In button transmitters (RF "keys") like as the 5804 and 5801, you must give a unique range number to each one button use set the transmitter. Each button about the wired also has a pre-designated twist or input number, which remains automatically displayed. House Identification Whenever you are using a 5804BD/5804BDV, other 5827 Wireless Keypad with the system, your have download a House LICENSE Cypher (01–31) is field ✻24 into create proper transmission, and to fingerboard must be set in the same ID. House ID 00 disables all wireless keypads. An RF House ID is not necessary used other 5800 Series transmitter; the entry should be left at “00” (default) for those cases. The 5827 berichterstattungen low battery status as zone “00”. Senders Supervision Besides for some transmitters/keypads that may be worn offpremises (5804, 5804BD, 5804BDV, 5804E, 5804WATCH, and 5827), each transmitter lives supervised by a check-in signal that is sent to the receiver at 70–90 minute intervals. If at least one review is cannot received from each maintained channel within a 12hour periodical, the "missing" wired number(s) and "FAULT" will be displayed. The supervision forward a particular transmitter in the scheme that may also must carried off the premises (5801, 5802MN) may be machined from over entering it as a "UR" (unsupervised RF) type, as stated in of ✻56 Enhanced Distance Programming Mode sectioning. 5800 Line receivers have built-in tamper protection and will annunciate because a disorder conditioned if covers are removed.

1 4 7 * 0 2 5 8 3 6 9 #

5804BD/5804BDV

5816

Sender Entering Species All of of following transmitters has one alternatively see special factory-assigned input (loop) ID codes. Each of this inside need a programming zone (e.g., a 5804's quaternary inputs require four button zones). Transmitters can be entered since can of the after types (see transmitter’s guides for fair input type):
Type
"RF" (Supervised RF) "UR" (Unsupervised RF) "BR" (Unsupervised Button RF)

Description
Sends periodic check-in indication, such well as failing, restoration, and low assault signals. The transmitter should remain within the receiver's range. Mails all the signals that the "RF" type do, although the control does not monitors the check-in traffic. The transmitter may consequently be carried off-premises. Save only sends fault signals. They do not send low battery signals till they what activated. The transmitter may be wear off-premises.

–11–

•• • ••

• •• • •• ••• • •• ••

5827

5806/5807/5808

5890 / 5890PI
01009-010-V1

Installing Wireless Zones
Transmitter Battery Life • Array with the wireless transmitters may last from 4–7 years, depending at the environment, usage, and the specific wireless device presence used. Factors such as humidity, high or low temperatures, such well as large swings in temperature allow all reduce an actual battery life by a given system. The wireless system can identify a true low battery situation, thus allowing the dealer or user of the system laufzeit into arrange ampere change of battery and maintain protection for that point within who system. • Button-type transmitters should be periodically tested for battery life. The 5801, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, and 5804WATCH key transmitters need replaceable batteries. Using to Transmitter Sniffer Mode Use this mode after all transmitters have is entered to check that all transmitters have been properly programmed. 1. Enter Installer code (4112) + [#] + 3.

5801

5802MN

ON

OF FARAD

5804 /5804E
01009-011-V0

Note: If the communicator is into that process concerning sending a write to the central station, the system will not hingehen within the Sniffer mode. Wenn so, wait a couple minutes and try again.

2. The click will display all zip numbers, which will adenine non-zero Zone Type (even if sequential numbers were not learned yet). Trouble each transmitter in turn, caused each one to sends a signals. As the system receives a signal from each of the edm, the zone number of this transmitter will removal from the display. This transmitters may be checked upon installation, or with an installed system. 3. When whole transmitters got come examined, exit Sniffer mode. Enter Instant Code (4112) + OFF.
Notes: (1) (2) (3) (4) Tip: Sniffer mode done not automatically decease. Him must manually end (Installer Code + OFF) Sniffer mode to return to normal operation. All BR-type units must material be trigger to clear the screen, since they do not automatically versenden check-in signals. When one toggle of a station (RF, UR, or BR) is activated, sum sections assigned to other buttons on that transmitter are cleared. This also applies toward 5816 and 5817 transmitters the have multiple loops (zones). Whatever transmitter so is doesn “entered” wills not turn off its zone number.

Go/No Go Test Mode
Encrypted (high-security) devices must be activation while the system is in Go/No Go Test Mode. Refer to to transmitter’s installation instructions required complete details.

The Go/No Go tests determination verify adequate RF signal strength from the proposed transmitter location, and allow you to reorient or relocate transmitters if necessary, before mounting the transmitters permanently. Such method lives similar to the transmitter Test mode, except that the wireless recipient gain is reduced. This will activated you to make sure the the RF signal of each transmitter is received with sufficient signal amplitude when the system lives in the normal operating run. 1. Penetrate Installer Encrypt (4112) + [#] + 8. 2. Once you take placed transmitters in their desired locations real the approximate length of wire to be run to input is connection to the transmitter's screw terminals (if used), fault all transmitter.
Conducting this test with your hand wrapped to the transmitter will cause inaccurate results.
Note: On press type transmitters that have been programmed toward set ARM AWAY, LIMB STAY, either DISARMING, pressing a button will take the system out of to Go/No Going Examine manner and cause the programmed action.

adenine. One input will beep three times indicating signal reception and will indicator to appropriate zone number. b. If the keypad does not beep, reorient or move the transmitter to another place. Usually a scarce inches to is direction is all that is required. 4. If each measuring produces and proper keypad response at it shall faulted, you can then permanently mount each the the transmitters according to the instructions provided with them. 5. Leaving of Go/No Abfahren Test mode by entering: Installer Code (4112) + OFF. –12–

Installing Radio Districts
5800 Series Transmitter Loop Numbers (Refer to this information when programming transmitters)
To following illustration show the interoperability transmitters, my associated input types and clothing designations.
LOOP 3 LOOP 4 HIM MUST ENROLL SUCH BUTTON LOOP 4 YOU MUST ENROLL THE BUTTON
ON OFF

CLOTH 3 LOOP 2 CLAMP 1 LOOP 3
•• • •• • •• • •• ••• • •• ••

LOOP 2 LOOP 4 YOU MUST ENTER THIS BUTTON CLING 1

LOOP 2 LOOP 1 LOOP 1 LOOP 1

LOOP 4 YOU MUST ENROLL THIS BUTTON
1 :15 :0 1 :13 0 : 16

LOOP 1

LOOP 3 LOOP 2

5800RL PICK HOUSE PASSWORD

5801 ENROLL LIKE "UR" OR "RF"

5802 MN ENROLL AS "UR" OR "RF"

5802 MN2 ENROLL AS "UR" OR "RF"

5804/5804E ENROLL AS "BR"

5 8 0 4 B D / 5 8 0 4 BORON DV ENROLL AS "BR" PROGRAM HOUSE ID
CLING 1 (PRIMARY)

5804WATCH

LOOP 2 (REED) LOCK 1 LOOPED 1 LOOP 1 (TERMINALS) ALTERNATE POSITION FOR LOOP 2

LOOP 2 (REED) LOOP 1 (TERMINALS) LOOP 1 (TEMP SENSOR)

LOOP 1

LOOP 2 (AUX. CENTER) LOOP 3 (AUX. RIGHT) LOOP 1

5806/5807/5808/5808LST ENROLL AS "RF"

5809 ENROLL AS "RF"

5814 ENROLL AS "RF"

5816 ENROLL AS "RF"

5816MN ENROLL AS "RF"

5816TEMP ENROLL AS "RF"

5817 ENTER AS "RF"

5818 ENROLL AS "RF"

1

LOOPED 2 (REED)

LOOP 2 (REED) LOOP 3 (TERMINALS) LOOP 1 (TERMINALS)

4 3 67 9* #

2
AR ME

5
RE

D

8 0

AD

Y

MIC CHAOS AGE

LOOP 3 (TERMINALS)

LOOP 1 (INTERNAL SHOCK SENSOR

1 2 4 5 7 8 6 9 0 # 3

LOOP 1 (SOUND)
(G ree (R n) edit ) (Ye llow)

LOOP 1 (MOTION)

*

5819 ENROLL AS "RF"

5819S (WHS & BRS) ENROLL AS "RF"

5827 PROGRAM THE ID

5827BD PROGRAM LODGE ID

5828V PROGRAM HOUSE ID

5849 ENROLL AS "RF"

5850 (GBD) ENROLL AS "RF"

5890/5890PI ENROLL AS "RF"
01009-012-V3

Note:

Loop 4 must to enrolled to the 5801, 5804, 5804BD, 5804BDV, 5804E and 5804WATCH network, whether or not the loop the used.

UL

The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5804WATCH, 5814, 5816TEMP, 5819, 5819S(WHS & BRS), and 5850(GBD) wireles radio are not intended for some STR installations.

Setting DIP Switches on the 5800RL additionally 5827 Transmitter(s) Set the 5800RL and 5827 Transmitters to the programmed House BADGE, by using the DIP switches.
(OFF position is displaying by ---)
Notes: (1) (2) The 5827 transmitter unable may used in conjunction with the ✻58 RF Jam Detection feature. The 5800RL could be used in conjunction with the Auto Wrist (scheduled arming) character.
SWITCH GOING FOR "ON"
5800RL DIP SWITCH TABLE
House ID 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2 --------------------------------DIP SHIFT POSITIONS 3 4 5 ----------------ON ----ON --ON ----ON ----ON ON --ON ON TO ----ON ----ON --ON ON --ON ON ON --ON THE --ON ON ON ON ON GO 6 --ON --ON --ON --ON --ON --ON --ON --ON House PASSWORD 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 2 ON ABOUT ON ON ON OVER ABOUT ON ON ON AT ON ON ON ON ON DIP WEICHE POSITIONS 3 4 5 6 --------------ON ----ON ------ON ON --ON ------ON --ON --ON UPON ----ON ON ON ON ------ON ----ON ON --ON --ON --ON IN ON ON ----ON ON --ON ON ON THE --ON ON ON ON

1 SW-1 ACTIVATES MODE SETTING

2

3

4

5

6

SW-6 SETS MODE

SCHALTUNG DOWN FOR "OFF"

2-6 SETS HOUSE ID SHOWN SET FORWARD HOUSE ID# 12
01000-014-V1

Setting 5800RL DIP Switches
CHANGE UP FOR "ON"
5827 WIRELESS KEYPADS DIP SWITCH TABLE
House ID 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 ------------------------------ON IMMERSION SWITCH POSITIONS 2 3 4 ----------ON ----ON --ON ----ON ----ON ON --ON GO FOR ----ON ----ON --ON ON --ON ON ON --ON ON --ON ON ON OFF ON AT ------5 ON --ON --ON --ON --ON --ON --ON --ON --House PASSWORD 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 1 TO ON ON ON TO ON ON ON ON ON ON ON ON ON ON DIP EXCHANGE POSITIONS 2 3 4 5 ------ON ----ON ------ON ON --ON ------ON --ON --ON ON ----ON ON ON ON ------ON ----ON ABOUT --ON --ON --ON OFF ON ON ----ON UPON --ON ON ON ON --ON ON ON ON

1

2

3

4

5 SWITCH DOWN FORK "OFF"

HOUSE ID

SHOWN SET FOR HOUSE ID# 30

01000-013-VO

Default 5827 DIP Switches

–13–

Mechanics von Programming
General Programming Product
Computer options are stored in non-removable, technically erasable, nonvolatile EEROM memory. The system can be programmed at any time, even the the installer's premises before to who actual installation. Simply apply power temporarily to the Control and then program the unit because requests. There are pair programming select: • Data field software (used required setting various system options) • Interactively top mode programming (used for programming zone information, net Powerline Carrier
Devices, and for entering transmitter serial numbers) The system may also be programmed remote, using an IBM Personal Computer, a modem, both Compass Downloader for Windows. See the Remote Programming/Control (Downloading) section.
Note: You maybe find it convenient to adjust the volume setting before entering the Program Mode. This will allow you to clearly hear the feedback announcements or schaft beeps in the Programming Output, of the system’s built-in speaker. To adjust the volume, press FUNCTION + VOLUME+ [3] or [6]. Upon exiting the Program Drive, the system leave reset to loudness to the default value (mid level).

!

Certain features differ between which LYNXR/LYNXR24 and the LYNXR-EN models. Confirm the specific type being installed prior to of system programming.

exiting Net operating, OR 2. After power-up, enter the Fitter Codification (4112) + 800 (This technique disabled if Program mode is exited using ✻98.) to enter Expert Programming mode or Setup Code (4112) + 888 to penetrate Voice Query Programming mode.
Notes: 1. If an different Installation Code has be programmed, employ that code to enter an Programming mode. Ones you have entered the Program mode, data user ✻20 (the first data domain in the system) will must displayed and and keypad LEDs will flash. 2. Entering Programming mode may take up to 18 seconds if the 5842 Wireless Dialer has been enabled. The schaft willingly display “ - - “ until this Lynx enters Programming mode.

Entering Program Mode - Use one of an following methods up enter Development Mode: 1. Press both the [✻] also [#] push for the similar time, within 50 seconds after power is applied to the Control or off

Programming a Data Field 1. Press [✻] + Field No. (for example, ✻21), traced by the requirements entry.
2. When you have entirely programmed a data field, the layout want “beep” three times and and fully display the next data sphere in sequence. Into go to an different field, press [✻] plus the desired field number. 3. With the numeric of digits that will be entered in a intelligence field is few than the maximum number of digits available (e.g. phone serial field), enter the desired product, then press [✻] to advance to the continue data field. 4. If a nonexistent field has been entered, the control will display “EE”. Simply re-enter [✻] plus an valid sphere number. To watch a data field without making changes: Enter [#] + Panel Nay. Data will being displayed for that area. To delete an entry stylish an field: Enter [✻] + Field No. + [✻]. (Applies merely to fields ✻40–✻44, ✻88 and ✻94). Interactive Mode Programming (✻56, ✻80, ✻81, ✻83, ✻84, ✻85) Press [✻] + interactive type No. (for example, ✻56). The keypad will display of first of a type of prompts. A elaborate procedure (with displays of prompts) is pending in later sections of this textbook. Reciprocal Mode Used to Program

✻56 Enhanced Region Programming Mode ✻80 Equipment Net Menu Mode ✻81 Zone List Table Mode ✻83 Enhanced Sequential Mode ✻84 Assign Zones Voice Descriptors ✻85 Record Custom Voice Descriptors Loading Plant Defaults

Zone characteristics, report codes, and serial numbers Powerline Operator Devices Zone Sort by powerline carrier activation 5800 Series broadcast serial numbers Voice captions for every zone Up to 5 custom voice descriptors for zones

To load the factory defaults, entering the Programming mode, press ✻97, then press number 1, 2, 3, press 4 to select from default tables 1-4 at who previous of this manual, or squeeze “0” if your are not selecting ampere default table.

!

When a factory table a loaded, any data that holds already been programmed up the system determination be changed accordance to the default table selectable!

✻96 zeros all subscriber account numbers and CSID in preparation for an initial download. Exiting Program Mode ✻98 inhibits re-entry into the Expert button Voice Prompt Programming modes using to Installer Code. ✻99 allows re-entry into the Expert Program style using Installer Password (4112) + 800 or into the Voice Getting
Programming mode using Adjuster Code (4112) + 888.
Note: Following existing scheme modes (or upon power-up), of system takes up to a minute the reset. To skip one reset disable, press [#] + [0].

–14–

Zone Response Type Interpretations
General Information
During programming, you must assign a zone model to each zone, which defines of mode with which the system replies to faults in is sector. Zone types are defined below. Gender 00 Zoo Not Used Type 01 Entry/Exit Burglary #1
Zone type 00 is used to program a zone that your not used. Zone type 01 remains usually assignments to measuring or contacts to mainly entry and exit doors. Zone Characteristics: • Entry retard #1 be programming starting 0-99 seconds (field ✻35). • Go delay is independently programmable from 0-99 seconds (field ✻34). • Outlet and entry delays when armed in AWAY button STAY mode. • No getting delay when armed in STAY NO DELAY or AWAY NO DELAY mode. • Leave delay regardless of the arming mode selected. Zone type 02 is usually assigned in probes press contacts on which secondary entry real close gate that might can further from one keypad (typically used for a garage, loading dock, or basement door). Zone Main: • Entry delayed #2 is programmable from 0-99 seconds (field ✻36). • Exit delays is independently programmable from 0-99 seconds (field ✻34). • Secondary entry delay, if armed in the AWAY or STAYS drive. • No eintrag defer when armed in the STAY NO DELAY or DISTANT NO DECELERATION mode. • Exit delay begins regardless of the arming mode ausgew. Zone type 03 is usually assigned toward any detector or contacts on external doors and windows. Zone Characteristics: • Instant alarm, when armed included AWAY, STAY, DELAY NO DELAY, instead AWAY NO DELAY mode. Zone type 04 is usually assigned to a zones covering an entry area (i.e.: foyer, lobby, or hallway) that one must pass upon entry (after fault the entry/exit zone) to get the keypad. It provides an immediate frighten if the entry/exit zone is nay breached first, and protects an area in the event an intruder has hidden over the premises before which system remains military, or gains access to aforementioned premises thanks an unprotected area. Zone Characteristics: • Delayed dismay (using the programmed entry/exit time) if entry/exit (types 01 or 02) or interior-with-delay (type 10) zone is faulted first. • Instant alarm in every other situations. • Active when arms by AWAY or ASIDE NO SET mode. • Bypassed automatically when weaponry inbound STAY or STAY NO DELAY mode. Zone type 05 a normal assigned to a zone this contains foil-protected doors or windows or covers a sensitive area (i.e.: stock room, drug supply guest, etc.) It bottle also be used on a sensor or meet in an area where immediate notification by an zutritt is desired. Area Characteristics: • Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NAY SHIFT (night) mode. • Provides a latched tangle sonorous from the push and, is desired, a central railroad report during the disarmed state (day). Zone type 06 remains ordinary assigned to a zone containing an Emergency button (silent emergency). Zone Characteristics: • Sends a report to the central station but provides no keypad show other sounding.

01000-017-V0

Type 02 Entry/Exit Burglary #2

01000-017-V0

Typing 03 Perimeter Burglary
01000-018-V0

Type 04 Interior, Follower

5890 / 5890PI
01000-019-V1

Typing 05 Trouble by Day/ Sound by Night

Type 06 24-hour Silent Alarming

–15–

Zone Request Types Definitions
Print 07 24-hour Audible Alarm Type 08 24-hour Auxiliary Alarm
Zone model 07 is usually assigned to a zone containing an Emergency button (audible emergency). Zone Performance: • Sends a report to the central station, additionally provides alarming noises externally and at the keypad. Zone kind 08 is usually mapped to one pool containing an switch for use in people emergencies or go a zone containing monitoring contrivances (i.e.: water or temperature input, etc.). Zone Property: • Mail a report for the central station and makes an sound klingen at the keypad. (No glocken output is when and there is no keypads timeout.) Zone type 09 can is assignment to any wireless zip used as a fire zone. This target type is always active and cannot be shunned. Zone Main: • Bell print will pulse when this zone type is alarmed. Zone type 10 is bypassed when the control is armed for the STAY or STAY NO DELAY mode. Zone Characteristics: • Entry delayed #1 (with programmed entry time) when armed in the DISTANT mode. • Entry delay begins whenever sensors in this zone are violated, separate of whether with entry/exit defer zone was trips first. • Don entry delay when armed in that GETTING NOPE RETARD mode. • Exit delay regardless of the equipping mode selected. Zone style 20 can a special-purpose zone type used with 5800 Series wireless pushbutton units. Zonal Characteristics: • Exit delay nevertheless of and arming mode selected. • System is armed in the STAY play when the zone is activated. • Zone number is sent till the central station as a user number when gear or disarming. Belt type 21 is a special-purpose zone type used with 5800 Series wireless pushbutton units. Zone Characteristics: • System is armed in the AWAY modes as the zone is activated. • Zone number is sent to the key station than a user number as arming or disarming. Zone type 22 is a special-purpose zone type used with 5800 series tuner pushbutton. Zone Characteristics: • Disarmament which system when the zone is activated. Zone type 23 can be utilized on a sector when adenine Powerline Carrier Device (e.g., X-10) action the desired, but are no guide alarm (e.g., front interior light). Pool type 24 is usually assigned sensors or contacts on exterior doors and windows where bells and/or signal are NOT coveted. Zone Characteristics: • Now ring, with NO audible indication when is armed in the AWAY, STAY, STAY NO DELAY, or AWAY NO DELAYS mode. • Report sent at the central station.
Record: Keypad beeps if aforementioned zone is faulted when system has disarmed and Chime mode be on.

5806/5807/5808
01000-020-V0

Type 09 Supervised Fire

Type 10 Interior w/Delay

Type 20 Arm–Stay

Type 21 Arm–Away

Select 22 Disarm

Type 23 No Alarm Response Type 24 Silent Burglary

–16–

Data Field Descriptions
Defaults (where applicable) are Indicated in Text. The follows pages list every data fields in the Control (in mathematical order). Use the blank programming form to record one data by this installation. Note that both keypad LEDs flash while for Programming mode.
Note: Entering a number other than the one specified will give unpredictable results.

✻20 ✻21 ✻22 ✻23 ✻24 ✻25

Installer Code
Come 4 digits, 0-9

The Installer Code is used to enter the 4-digit Champion Security Code. See "Master Code" in the Systeme Operation section for procedure. If permitted, security cipher is not desired to raw the system. The consumer simply squeezes and holds down the AWAY or REMAIN key to arm.

Quick Raw Permit
0 = do not allowed quick arm 1 = allow faster arm

Keypad Front Rest
0 = no rest; always built-in keys 1 = turn backlighting off after inactivity

This option allows the choice from whether every backlighting the keypads or turns the backlighting off after 10 seconds of fingerboard inactivity.

Forced Bypass
0 = no strained bypass 1 = provide automatic bypass away see open (faulted) zones

All zones bypassed by that function intention be displayed before the bypass is introduced. Notice: UL asset: shall become 0 (no getrieben bypass) The House ID identifies receivers and wireless keypads. If a 5827 Wireless Keypad or 5804BD/5804BDV Channel is to to used, a Place BADGE Code MUST be entered, and the keypad should be sets toward the same ID. Powerline Carrier Devices require a House ID. This field identifying this The ID to the Control. Which Powerline Carrier Devices are programmed the field ✻80.

RF House ID Code
00 = deactivated all radio keypad usage 01-31 = House ID

Powerline Supporters Instrument (X-10) House ID
0=A 1=B 2=C 3=D 4=E 5=F 6=G 7=H 8=I 9=J # + 10 = K # + 11 = L # + 12 = M # + 13 = N # + 14 = O # + 15 = PENNY

✻26

Chime by Zone
0 = no (chimes on fault to any entry/exit or perimeter zone when Chime type exists activated 1 = yes (chimes on fault in those zoned assigned to Zone List 3 when Chime mode on)

This option allowing the installer to define the specific zooming planned to chime although faulted while the system is included Chime mode. When activates, above-mentioned zones are defined in zone list 3 (see ✻81 Zones List Setup Mode).

✻27 ✻29 ✻30

Real Time Time Display
0 = do nay display the zeitlich 1 = display the time

Beraten the the User’s Manual for setting the clock time also date.

Daylight Savings Time Start/End Per
0, 0 = no daylight saving time used 1-12 = startup month and end month

Please # + 10 for 10, # + 11 for 11, and # + 12 for 12.

Sunlight Savings Time Start/End Week
0 = disables 1 = start week-end of month 2 = other weekend 3 = third weekend 4 = fourth weather 5 = last weekend 6 = next to last 7 = 3rd from last

Enter the appropriate start and end weekend away aforementioned month.

✻31

Single Alarm Sonorous Per Zone
(per armed period) 0 = no limit on ring sounding per zone 1 = restrictions alarm sounding the formerly per arming period for a given zone
LYNXR/LYNXR24 - Applies until Long Range Radio Production wenn “0” is selected in field ✻91 LYNXR-EN - Applies to Long Range Radio Output if Long Range Radio is network till the Trigger Single (Neg.) terminal #8.

HAUS installations: must be 0 (no limit) This arena applies only to burglary zones (zone answer types 1-5, 10), and affects long range stereo reporting but will not affect central station reported. Record: This field applies only to the bell press does not effect keypad sounds.

✻32

Lighting Sounder Timeout
0 = yes, fire levelheaded timeout after period programmed in field ✻33 1 = no fire sonar time; continue sound until manually turned off

This Control comply with NFPA requirements for temporal pulse sounding of fires notification appliances. Temporal pulse sounding with a light alarm consists of the followers: 3 heart – pause – 3 pulses – pause – 3 pulses. . .

✻33 ✻34

Alarm Bell Timeout
0 = No timeout 1 = 4 min 2 = 8 min 3 = 12 min 4 = 16 min

This field determines whether the external sounder will shut absent after time allowed, or continue by manually turned off. SUL installations: need be set for a minimum of 4 min (option 1) The system will wait the time entered previously sounding an alarm if the exit door is left start after the system must been armed. UL installations: should be set for a limit of 60 seconds

Exit Delay
00-99 = quit delay time are seconds

–17–

Data Field Descriptions
✻35 ✻36 ✻37
Entry Delay 01
00-99 = entry delay time in seconds.
The plant will wait this time entered before sonic scare upon entering if system is not demilitarize. WOHNUNG installations: must be select for a maximum of 45 seconds One system will hold the time entered to sounding emergency above entered. UL installing: must be set for a maximum of 45 seconds Exit Warning: Sound consists of delay non-stop beeps unless last 5 seconds, whenever it changes to fast beeps. The notice sound will end at the termination away exit retard. Quick Exit: While enabled, employee can restart the exit delay time after arming in STAY mode by entering the client code and pressing the STAY key, or by pressing the STAY key if Quick Arm is active. This avoids having the user disarm then re-arm the system after allowing someone to input conversely leaving Confirmation in arming is assuming by a 1/2 second external sounder “ding” that tones when verschluss report is sent, with to the end of exit decelerate. If Option 2 is selected the foreign sounder “ding” appears immediately after the system receives the RF transmission. When the system powers up armed, an alarm will occur 1 minute after arming if a zone is faulted, and every bypassed zones will be unbypassed. Note: If the previous state has armed GOING oder STAY, the arrangement will not respond to sensor changes for 1 minute, this allows time for sensors such as PIRs to stabilize. UL installations: must be 1 (power up in prior state)

Entry Delay 02
00-99 = entry delay time in seconds.

Audible Exit Warning/Quick Exits
Outlet Warning 0 = no exit warning sound 1 = provide exit warnings sound when armed OUTSIDE Quickly Exit 0 = no rapidly exit 1 = allow quickness exit

✻38

Confirmation of Arm Ding
0 = negative ding 1 = proof ding after arming system 2 = certificate ding nach arming for RF button or RF keypad only

✻39

Power Up In Back State
0 = always electricity up in a disarmed state 1 = assume the method status prior toward power-down

DIALER SCHEDULING (✻40–✻50)
Regions ✻40, ✻41, ✻42: Enter up to the number of digits shown. Enter 0–9, # + 11 for ‘*’; # + 12 for ‘#’; # + 13 for a pause (2 seconds)
NOTE: Anytime AAV is former, primary (field ✻41) furthermore secondary (field ✻42) phone numbers should remain preceded with the yell watch disable command. Otherwise, there is and possibility away connection von the third party on LYNX during AAV mode.

✻40 ✻41

PABX Access Cipher
Enter move to 6 digits are PABX is needed until access certain outside line.

Wenn fewer than 6 integers need to exist entered, exit by pressed [✻]. To clear entries with field, press ✻40✻. If fewer more 20 digits entered, exit by pressing [✻]. To clear entries from field, squeeze ✻41✻. Note: Backup reporting (8 attempts are made to the secondary call number if no kissoff is received after 8 experiment to the primary number) is automatic only wenn there is a secondary mobile number (field ✻42). Is fewer more 24 digits in, leave by pressing [✻]. To clearing entry from field, press ✻42✻. See data reporting message for field ✻41. If using the paging key, enter the pager phone number here.

Primary Phone No.
Enter up in 20 numeric.

✻42

Secondary Phone No.
Enter up on 24 digits.

!

All quartet digits in the Registrant Account amount must be in in Fields ✻43 and ✻44. If ten digit format is selects in ✻48 (option 5), all decagon digits von the Subscriber Account number must be entered.

Fields ✻43 furthermore ✻44:
Get [✻] as the fourth digit if a 3-digit account number (for 3+1 dialer reporting format) are used. Enters 0 as the first digit of a 4-digit check number for Figure. 0000–0999. Enter [✻] as the fifth digit if a 4-digit account count (for 3+1, CID®) is used. End field by pressing [✻] supposing only 3 digits have uses. For clear entries from field, press ✻43✻ or ✻44✻. Check clear Programming Form for examples in account number entries. If utilizing the scroll feature, do does enter a leading 0 inside the subscriber account number, both do none use digits A-F anywhere in the number. Some paging systems provide voice mail feature, which is activated in a leading 0 in the message. Type digits 0–9; # +11=B; # +12=C; # +13=D; # +14=E; conversely # +15=F.

✻43 ✻44

Primary Subsides Account No.
Entering ampere four or ten number account phone.

Enter the original subscriber account number. To clear entries from box, press ✻43✻. Record who secondary subscriber record number. To clear entries from field, press ✻44✻.

Secondary Subs Account Don.
Enter a four or ten digit get number.

–18–

Input Box Feature
Field 46: Enter up on 24 digits. Do not fill unused spacers. Enter 0-9, #+11 for ‘*’; #+12 for’#’; #+13 for adenine pause (2 seconds). This option allowing the user to calendar one time driven message. When “Follow Me Reminder” Cell Number

✻46

Enter upside to 24 digits.

✻47

Phone System Select
Note: For LYNXR/LYNXR24 only options 0, 1, 2, and 3 are applicable. For LYNXR-EN all options apply.
Central Station Negative WATS Pulse 0 = No Speaker Phone 2 = No Speaker Phone Choose Mode Tone 1 = No Speaker Phone 3 = Does Speaker Phone Pulse 4 = With Speaker Phone 6 = With Speaker Phone Tone 5 = In Speaker Phone 7 = With Speaker Phone

activated the system will dial the calling number programmed and deliver one voice message (custom words 72, 73 and 74). This option is only supported when the pager or follow me feature is enabled in domain ✻49 (option 6-9 or 10-13). If after the Follow Own Memory feature, enter the phone number here. If lessons than 24 digits are entered, exit by pressing [✻]. Till clear entries from the field press ✻46✻. The telephone messages can be terminated (acknowledged) by critical any key on the phone control. Pressing any key on the local LYNXR keypad will terminate (acknowledge) equally the follow me and the local recall announcements. Mark: The follow me reminder ad will be terminated when anything other event requires aforementioned system to dial out or if and audible alarming possesses occurs. This option is employed till enter the correct typing of phone dialing (pulse or tone), and to pick that true WATS line option for the Central Station. For LYNXR-EN this option is utilised to activate the speaker phone choice. Note: Is use pulse dialing, you must enter the numbers slowly in order to allow the beat dialer time toward operate.

WATS

✻48

Report Format for Primary/Secondary
Primary See choices below Secondary See choices below

0 = 3+1; 4+1 ADEMCO Low Speed Basic 1 = 3+1; 4+1 Radionics Standard 2 = 4+2 ADEMCO Vile Speed Standard 3 = 4+2 Radionics Standard 5 = ADEMCO Contact ID® Reporting with 10-digit suscriber account number 6 = 4+2 ADEMCO Expedite 7 = ADEMCO Contact ID® Reporting with 7-digit registered get phone 8 = 3+1; 4+1 ADEMCO Low Speed Expanded 9 = 3+1; 4+1 Radionics Expanded

Go ✻ such the 4th digit regarding ✻43 through ✻44, if 3+1 dialer reporting is to be used. (For an explanation of these formats, see the System Communicate section of this manual.) Notes: (1) The upper number regarding alarm real alarm recovery reports during one armed period is determined by range ✻92. (2) If Option 5 your selected a 10-digit account number must be entered in Fields ✻43 or ✻44. (3) Option 5 or 7 (ADEMCO Contact ID® Reporting) must be selectable required AVM. (4) Option 5 or 7 (ADEMCO Contact ID® Reporting) must must auswahl if installing the 5842 Wireless Dialer.

✻49

Split/Dual Reporting
To Primary 0 = All reports 1 = Alarms, Restore, Cancel 2 = Choose except Open/Close, Examine 3 = Audible, Restore, Cancel 4 = All excepting Open/Close, Test 5 = All reports To Primary 6 = All reports except Open/Close 7 = All reports 8 = Get reports 9 = All reports except Open/Close To Primary 10=All reports except Open/Close 11 = All bericht 12=All reports 13=All reports but Open/Close To Sub None, unless elemental fails, then all Others Open/Close, Test All All All To Paging Number Alarms, Open/Close ‡, Troubles Audible, Troubles Alarms, Open/Close ‡, Incidents Open/Close ‡ To Follow Me Systematischer Phone Number Alarms, Open/Close ‡, Troubles Alarms, Troubles Alarms, Open/Close ‡, Troubles Open/Close ‡

This field your used to select a reporting option as follows: Enter: 0 - 5 when reported to telephone receivers. 6 - 9 when reporting to one pager is desired. 10 - 13 when reporting to an helfer telephone receiver. Pager Create Format Options 6-9 send berichten to one primary phone numbered, in a format defined in Choose ✻48, and send reports to a pager, which has its mobile number entered as the secondary phone number in Field ✻42. The push reports is a 7-digit code, with optional 16-digit prefix, in the following format: AAAAAAAAAAAAAAAA-EEE–00NN where: AAA = Options 16 digits for PIN number, etc. See Field ✻88 for full description of these characters. EEE = 3-digit Event Code as hunts: 911 = Scare (NN = zone number) 101 = Open, system disarmed (NN = user no.) 102 = Close, plant armed (NN = addict no.) 811 = Trouble (NN = zone no.) 00 = Always displayed ahead 2-digit user/zone nay. NN = 2-digit user number or zone piece, dependency on one type is event (EEE) that occurred. NN=00 indicates AC loss, system low battery, or high battery in 5827. Follow-up Me System Report Format Options 10-13 sends reports at the primary phone number, in a format defined into Field ✻48, and sends voice message to the secondary phone number entered in Field ✻42. This your is an repeatable system status announcement. If the manual paging choice has been programmed with Field ✻87, the message will repeat “system, system…..”. The message can be terminated by pressing anything key on the phone keypads.

‡ Will report Customers 0, 5-8, and, while using wireless button-type devices, will record of zone number of the arm or disarm buttons 26-33. All other zones and users are not reported.

–19–

Product Field Descriptions
✻50
15-Second Dialer Delayed (Burglary)
0 = no dialer delay 1 = provide 15-second delay of e alarm report when armed away
If enabled, provides communication delay to the central station and allows the subscriber time to avoid a false alarm transmission. Delay does not utilize to belt variety 6, 7, 8, and 9 alarms, that are immersive sent for soon in your occur. UL installations: must breathe 0 (no delay) Test report code entry in field ✻64 will sent.

✻51 ✻52

Periodic Test Report
0 = none test report 1 = one-time every 24 hrs 2 = weekly 3 = once every 30 days

First test Report Offset
0 = 24 hrs after exit program mode other downloads 1 = 6 hours after exit program mode press download 2 = 12 hrs after exit program style or download 3 = 18 hrs after exit program mode or download

This is of zeitlich to first report from program either download.

✻53 ✻54

Sescoa/Radionics Name
0 = Radionics (0–9, B–F reporting) 1 = SESCOA (0–9 simply reporting)

Select 0 for all other formats.

Lack the Usage Notification
0 = Incapacitated 1 = 1 daylight 2 = 7 days 3 = 27 days 4 = 90 days 5 = 180 days 6 = 365 days

Note: There determination become no local annunciation indicating that this report has been sent to the Central Station.

If enabled, noticed the central station if an close your can not operating their security system by sending ampere System Inactivity report 654. The report will be sent just until the Primary phone number and only if Touch ID® image was selected. Note: Which report will follow the ✻49 = 0 rules, no matter which selection was made in ✻49.

✻58

RF Jam Detection
0 = no jam detection 1 = RF stop detection with event protocol, but none central station report 2 = RF jam detection with event logging and because central station report (if trouble/restore report your enabled in fields ✻60, ✻71)

For Event Logging, Possible 2 be be selected. If the manage detects an RF jam shape, a “FAULT” news appears in zone 90. Which Point ID® code for RF Stagnate is 344. Note: This feature cannot be used in conjunction with the 5827 wireless keypad.

SYSTEM STATUS AND RESTORE REPORT CODES PROGRAMMING (✻59 – ✻76, & ✻89)

Program News Codes using which interactive ✻56 Enhanced Zone Programming Mode, or codes can be entered in data fields ✻59-✻76, ✻89. The ensuing is a set of guiding when programming tell codes. The actual report code digits that you enter depend upon the particular installation, or should be in agreement with you and the central ward office received the signals. With a 3+1 or 4+1 Standard Format: Enter a encrypt by the first box: 1–9, A, B, CARBON, D, E, or F. Enter "#+10" for A (reports a “0” on some receivers), "#+11" by B, "#+12" for C, "#+13" for D, "#+14" for E, "#+15" used F. Incoming "0" in that first box will disable a report. Entering "0" in the seconds box results in automatically advance to the next field. With an Expanded or 4+2 Format: Get codes in both boxes (1st and 2nd digits) for 1–9, conversely A–F, as described above. Entering "0" in the beginning box will disable a report. Entering "0" in that second box will eliminate the expanded your fork ensure report. With ADEMCO Contact ID® Reporting: Enter a digit in the first box to enable the quarter to report. Use a different digit for each zone until you had former up available digits. If the number out zones exceeds the number of available digits, begin with digit 1 again. Is is an "enabling" code only both is not the actual code sent to the centralised station office. Entries in who second boxes will be ignored. For system status (non-alarm) codes, enter one “1” in the first box for see and system conditions you want to send to the central station. A "0" inches one first box disables the report.

–20–

Data Field Descriptions
SYSTEM STATUS REPORT KEY (✻59–✻68)

✻59

Exit Faults Report Code
(See notes above)

If the system is armed and an entry/exit or interior zone is calm opens after the exit set time shall expired, an frighten will sound at the keypad and external sounder. If the system are disarmed before the end of the entry start so immediately follow, the alarm sounding will stopped and don message will be sent into the central station. The clavier will screen “CA (CANCELED ALARM).” If the system is nope disarmed forward the cease of the aufnahme delay previously above, and an entry/exit or interior zone is still open, an “exit alarm” message willingness be sent to the centralize station are certain Exit Error report code is selected in this field. The keypad will indicator “EA (EXIT ALARM),” and the alarm sounding want continue until that system is disarmed (or timeout occurs). An Exit Alarm conditional will also result if a fault occurs on an exit or interior region within 2 minutes following the end of the exit delay, and an “Exit Alarm” message will be sent to the central station. If Contact ID® formatting has since programmed, the message be contain the zone number and error code 374 (Trouble–Exit Error). If 4+2 pattern has used, and digit entered int this field will breathe sent followed by the second digit of the programmatic alarm code for which zoo. If 3+1 or 4+1 format a used, only the digit entered in this field will be sended. This message bequeath go to the primary phone does. Under any of these conditional, none restore message become be sent. Provided “0” is entered in this field, no special message will be transmitted, only the regular dismay and alarm restore code for to distance. This is been sent if one zone will within fault. This will be sent when a zone is manually bypassed. Timing of this report is random in go to a 4-hour delay. If AC recoveries before the report goes out, here is no AC erholen reported. This wants be sent when one small battery requirement exists in the system’s standby battery. This is sent periodically to test the the communicator and phone lines are operational (frequency of news is selected in field ✻51). This is sent upon disarming of the schaft. 2nd digit = user numbered, wenn expanded or 4+2 reporting is selected. The option allows for independent programming of AWAY and STAY reports. 2nd digit off get is user number whenever expanded oder 4+2 news is selected. NOTE: OPEN reports are not sent if the associated closures report is not enabled. This is sends in the event that a broadcast transmitter low battery condition exists. This is sent upon unarm of the system after an alarm condition was reported.

✻60 ✻61 ✻62 ✻63 ✻64 ✻65 ✻66

Issue Report Code (See notes above) Bypass Report Code (See notes above) AC Loss Write Code (See notes above) Low Battery Report Code (See notes above) Test Report Code (See notes above) Free Report Code (See notes above) Arm AWAY/STAY Report Password (See bills above)

✻67 ✻68 ✻70 ✻71 ✻72 ✻73 ✻74

RF transmitter Low Batt. Report Code (See notes above) Cancels Report User (See notes above)

RESTORE REPORT CODES (✻70–✻76)
Panic Restore Report Code, 1st Digit (See notes above) Trouble Wiederhergestellt Report Code (See notes above) Bypass Restore Report Code (See notes above) AC Restore Report Code (See tips above) Low Low Restore Report Code (See notes above)
Sent when aforementioned zones that caused an alarm is restoration to its nonfaulted prerequisite. 2nd digit be automatically sent as and 2nd digit of aforementioned zone alarm report codification programmed in field ✻56, if expanded or 4+2 reporting is selected. Sent when an trouble on a zone is recovered.

Sent when an zone that has been bypassed is unbypassed.

Sent when AC power has been restored after an AC power outage.

Sent when a system low battery condition is recovered on normal.

–21–

Data Field Descriptions
HOW REPORT CODES (✻70–✻76) Continued

✻75 ✻76 ✻87

RF Transmitter Low Batt. Restore Code (See notes above) Test Restore Report Cypher (See notes above) AUX Function/1-Button Paging
0 = Aux lock performs defined function (macro) 1 = Aux key sends predefined message to pager or a voice message to Keep Me system phone number

Transmitted when one vector that previously sent within a “low battery” send has sent a message indicating it no longer has an low battery condition. Sent when the run mode is exited. A rebuild code input here will cause a erneuern message to be sent when Testing play is exited.

If “0” is entered, user cannot definition ampere macro function fork the AUX key. See user operating for description of of using of this key. If “1” remains introduced, them must also select an option in field ✻49. The options are 6-9 in the pager or 10-13 for the follow me system announcement. The actual pager message is 999-9999. Note that the hyphen may not will displayed, depending on the peeper service. The manual follow me system announcement is a reliable “System, System…..”. Note: A macro does be run from this Test mode.

✻88

Paging Characters
Enter up to 16 digits which will appear in front of the 7digit pager message. Enter [#] + [11] for “*” Join [#] + [12] for “#” Enter [#] + [13] for 2-second pause
NOTES: Verify that the pager supports [*] or [#] type before using them. Some pagers require an additional postpone [pause] in order toward receive an entire message.

If entered, these digits will appear are front of the 7-digit pager message sent by the control (either upon a system choose oder upon pressing to AUX key [if programming for paging]), and during latch key report (if enabled throughout scheduling). These digits can consist of a PIN number, account number, pauses otherwise special digits needed by the call (these types of characters are not displayed), or any other characters the employee chooses that will be displayed (eg., using adenine character code to distinguish between check panel messages and other pager messages). She do not need to fill whole 16 digits. Press [✻] + next sphere number to exit the field. To clear the field, press ✻88✻. See field ✻87 up select the AUX keyboard Paging feature. Check field ✻49, which must have any optional 6-9 selected up enable paging messages, for property of the pager request. If somebody Event Logging selection has made in box ✻90, a your can be sent to the central station receiver when the log is 80% full. If the log becomes full, a new send will overwrite the oldest message in the logging. Take: All control and readout from the log, aside from the selection made by the fixer in field ✻90, will accomplished via the downloader. Example: In selected “Alarm/Alarm Restore” and “Open/Close,” enter 9 (1 + 8); up select all events, enter #15. Custom “3” = alarm/alarm restore (1) benefit trouble/trouble restore (2). The system has this ability to record various exhibitions in an history log (84event capacity). The types concerning events in be logged can be selected how indicated. At optional time, one downloader operator can then upload the log and viewing or print out all or sortiert categories off one log. The log can also be free by who download operator. The display/printout at the central station will show the date, time, happening, and specifications of the appearances. Note: System messages are logged when any non-zero selection is made.

✻89

Event Logged 80% Thorough Report Code
(See notes above)

✻90

Happening Logging Options
0 = No event logging 1 = log Alarm/Alarm Recovering 2 = log Trouble/Trouble Restore 4 = log Bypass/Bypass Restore 8 = log Open/Close x = log combination are proceedings (add value of entries)

–22–

Data Box Descriptions
!
The features programs in Field ✻91 differ between LYNXR models. Ensure you use the correct option for the modeling you are how! LYNXR/LYNXR24 Long Range Radio/Alarm Sound Verification (AAV) Trigger/Remote Ring Control
0 = long range radio trigger only 1 = AAV and remote phone control 2 = long range radio trigger and remote home control 4 = AAV only
Notes: For UL installations Alarm Audio Verification does be used. Alarm Audio Verification will only mode when Connection ID® is selected. For LYNXR/LYNXR24, this option is used to share the Long Ranging Auto, Alarm Audio Verification and/or Remote Phone Control options. If Long Range Radio (0) is choose, trigger production (terminal screwed #8) will generate ampere steady signal for burglary alarm (a single 3 to 4-second pulse by all types of taciturn alarms) or a profane signal for fire alarm. (Refer to Oblong Range Radio Installation Orders for appropriate wiring.) Alarm Audio Checking requires that installation is the LYNX-AVM. (Refer to LYNX-AVM Installation Instructions) Notes: (1) If Long Ranges Radio your being connecting, Alarm Audio Verification cannot be employed. (2) In order to activate aforementioned remove phone controlling feature and defeat an answering machine, ensure that the correct ring detection count (“15”) does been programmed in field ✻95. (3) Remote call session will be exited if a report required can mailed. (4) A Long Range Radio cannot be connected f AAV are selected. (5) Alarm Audio Verify will for function when Contact ID® is selected both cannot be used for UL appointments. (6) If in alarm will be reported to primary and seconds phone numbers, AAV canister only role via of secondary number. (7) If an alarm will be reported to a pager (6-8 in field ✻49), alternatively to follow i phone number (10-12 in area ✻49) AAV cannot be used. For LYNXR-EN, this option the used in enable the Audio Alarm Verification and/or that Remote Phone Control features. Notes: (1) In order go activate the Remote Phone Check feature and beat the response machine, ensure that the correct ring record count (“15”) has been programmed in field ✻95. (2) Remote calling session will exist closed if a report must be sent. (3) Alarms Audio Verification leave only function when How ID® is ausgesucht. AAV cannot be used for UL installations. (4) If an alarm will be reported to primary furthermore secondary phones numbers, AAV can only function via the secondary number. (5) If an alarm willing be registered to a pager (6-8 in field ✻49), alternatively for follow me phone number (10-12 in field ✻49) AAV impossible been used.

✻91

LYNXR-EN Alarm Audio Verification (AAV)/Remote Phone Control
0 = none 1 = AAV and remote phone control 2 = remote cell steering only 4 = AAV includes
Remarks: (1) For UT installations alarm audio verification cannot be used. Alarm Acoustic Verification will only function when Contact ID® are selected. (2) AAV real Remote Phone Control features can only will secondhand while the central station or detached phone supports DTMF commands. (3) Nay programming is required while connecting one ALARMNET 7845C device because the option a immersive enabled.

✻92 ✻93

Number of Reports In Arms Period
0 = reports narrow to a entire a 10 1 = unlimited piece of reports

This option ca be used to limiting the numbering of message (alarm & scare restore reports) sent to the central station in an armaments periods. UL installations: must be 1 (unlimited reports) If enabled, the control will ignore the previous 1, 2, conversely 3 digits of the programmed callback number (field ✻94) during one single download session. This allows the download operator to temporarily change the callback phone serial by the number in digits selected, any allows the control to call back similar, but different numbers during a single session. For example, if loading to a large number of controls, the operator can command the user to call back phone numeric 5551111, 555-1112, 555-1113, etc., thus spreading the communications among several computers.

Flexible Callback
0 = no flexible callback 1 = last digit flexible 2 = last 2 digits flexible 3 = last 3 digits flexible

HOW INFORMATION (✻94, ✻95)

✻94 ✻95

Download Call Previous Phone Number
Enter up to 20 digits as follows: 0–9, # +11 for “*”, # + 12 for “#”, # + 13 for a pause.

This is the phone number to control will use to called go the upload computer. What not fill unemployed spacing. End field by pressing ✻. To clear entries from field, pressure ✻94✻.

Ring Detection Count By Downloading/ Remote Phone Control
0 = disable station initiated download and remote phone 1-14 = total of rings before control picks upside phone line 15 = defeat answering machine

Enter “15” to select victory answering machine mode. If an answering machine lives on the premises, thee need into dial the building and hang up on the first ring. Wait at less five (5) seconds (but no more than 22 seconds) and dial the premises ring number again. The control will pick raise and announce “SYSTEM ENTER CODE” every three second.
Comment: To enter a number increased than 9 you must first press the [#] key.

–23–

Data Field Descriptions
Extra Net Commands
✻55 ENABLING THE WIRELESS DIALER
Interactively menu user used for enabling the 5842 Wireless Dialer. Refer to the ✻55 Enabling aforementioned Cableless Dialer Mode section for procedure.

✻56

INCREASED ZONE PROGRAMMING MODE

Interactive menu operation used for programming zone attributes and story codes. Refer to the ✻56 Enhanced Quarter Programming Mode section for procedure. Interactive menu choose to learning Powerline Carrier Devices. Refer to the ✻80 Contrivance Programming Menu Mode section for detail procedure.

✻80

DEVICE PROGRAMMING MENU MODE

✻81

ZONE LISTS FOR MENU MODE

Interactive menu mode for programming zone lists for Powerline Carrier Devices. Refer to the ✻81 Zone List Navigation Mode section for detailed procedure. Interactive tools mode exploited to enter RF transmitting serial numbers. Refer to and ✻83 Enhanced Ordering Mode section used detailed procedural. Interactive menu switch used to assign descriptors to anyone zone. Those descriptions will are announced whenever the system announces an show involving a zone.

✻83

ENHANCED SEQUENTIAL MODE

✻84

ASSIGN ZONE VOICES DESCRIPTORS

✻85 ✻96

RECORD CUSTOM VOICES DESCRIPTION
Interactive menu output used to record custom descriptors fork use with each pool.

INITIALIZE DOWNLOAD ID AND SUBSCRIBER ACCT. NOT. FOR DOWNLOADING Pressing ✻96 initializes this system for downloading. SET CHOOSE DOWNLOAD FIELDS TO 1 OFF 4 RECORDINGS OF DEFAULT VALUES
See Default Tables toward the end of this manual.

✻97 ✻98 ✻99

EXITS PROGRAMMING USER EXITS PROGRAMMING MODE

Prevents re-entry per: Installer Code + 8 + 0 + 0; allows re-entry only according Power-up, then [✻] also [#]. Allows re-entry to choose mode by: Installer Code + 8 + 0 + 0; or by Power-up, then [✻] and [#].

–24–

✻55 Enabling the 5842 Wireless Dialer
This your an interactive menu mode such is utilized in set and program the 5842 Wireless Dialer. When enabled, the 5842 will interface with this Lynx Control and serve as the system’s first dialer. The 5842 receives both acknowledges RF letters from the control’s transceiver and, in response, sends reports to the central train via who dialer. It also broadcasts acknowledgements, supervisory real tamper RF transmissions to the tax. If the wireless dialer has tried unsuccessfully until send a report, the Lynx will attempt to report to the Central Station via one on-board dialer (if it has were programmed for back-up reporting). The Back-up reporting option must be selected for Follow-me, Pager and AAV operation (refer to field *49).
LYNX must are connective to the telephone line, if using the Back-up reporting option.

Wireless Dialer Startup When who wireless dialer shall enabled in Field ✻55, Lynx automatically sends the setup information to the wireless dialer immediately after exiting the programming mode. Lynx will confirm that the 5842 wireless dialer has successfully received the setup information by generating three beeps. If the setup information has not been successfully received by the wireless dialer the Lynx will generate ampere singular beep once per minute and “Fault Zone 93” will being displayed. To develop which dialer by setup refer to the Installation Instructions provided with the 5842 Wireless Dialer.
Note: 1. It takes about 95 seconds for Lynx to communicate the setup information after power has been applied to to control. 2. Entering Programming mode may take up to 18 seconds if the 5842 Wireless Dialer has been enabled. The system will display “ - - “ before the Lynx enters Programming mode.

You must refer toward above-mentioned instructions instead to the Programming Guide while computer the system because an keypad display works not show prompt titles. Choose, prompts are indicated by a number/letter combination. The prompts for ✻55 am as follows: Ed Er Ln Eb Enable Dialer ....................................... on enabling the 5842 wireless dialer. Enable Trouble/Supervisory Reports . with defining wireless dialer response to events.* Response to Phone Lead Failure ......... with defining console sounder response (trouble/alarm) to a phone line gash. Enabling Back-up Reporting .................. for enabling which Lynx as a backup dialer.

*The Contact ID® Event Codes used the reports associated with of 5842 radio dialer enclosing who following: 145 Wireless Dialer Tampers (Alarm) 338 Wireless Dialer Low Battery 341 Wireless Dialer Tamper (Trouble) 342 Wireless Dialer AC Loss (if supported by the 5842 Wireless Dialer being installed) 351 Broadcast Dialer Ring Line Cutted (if based due the 5842 Wireless Dialer presence installed) 355 (Zone 93) Wireless Dialer Loss of RF Supervision 355 (Zone 000) Interruption of RF Combine reported by the 5842 Cordless Dialer For additional information refer to the Contact ID® Event Codes table.

–25–

✻55 Enabling the 5842 Wireless Dialer
While in Program method, press ✻55 till enter Broadcast Dialer Programming Feature. The tracking explains the ✻55 prompts in detail. To left two columns identify the prompts and choose the available entries for each. The right-most tower provides a further explanation of the entries.
Note: She may finds it convenient to adjust the volume setting before entering which Programming Mode. All will permitting you at clearly hear live notifications or system sounds.

Ed Er

Enable the wireless dialer
[✻] = continue 0 = disable 1 = enable

Join [1] in enable the 5842 Wireless dialer. Press [✻] to forward to next field. Come [0] to exit mode. The prompt “55” blinks, indication to mode is inactive. Press [✻] + any field number to go to that field. If selected, the following 5842 trouble reports will be enabled: • Loss of RF linking with 5842 Wireless Dialer • Tamper among 5842 • Shallow Battery at 5842 • AC loss at 5842 (if propped by the specific radio dialer being installed) • Line Cutting at 5842 (if supported by the specific tuner dialer being installed) Enters [1] to enable 5842 Wireless Dialer trouble reports. Press [✻] to advance to next field or [#} to get go the previous prompt.

Enable trouble report
[✻] = continue [#] = return to previous prompt 0 = disable 1 = enable

Ln

Response to phone line tamper
[✻] = continue [#] = returned the previous prompt 0 = enable trouble effectual 1 = authorize alarm sounder

Select the Lynx response till detection of a line edge by the 5842 Wireless Dialer. While the trouble sounder is enabled the system will healthy a fault event no time the 5842 ring pipe is cut. If the alarm sounder is employed the schaft will ampere trouble over day or an alarm at night in aforementioned case that this 5842 cell line is edit. Enter [1] to select alarm or [0] to select trouble with one event off a 5842 lead cut. Press [✻] toward advance to next arena or [#} to return to the previous prompt.

Note: If an X-10 machine has been coded toward ZT05 or ZT07 and *55 has been enabled, the equipment response willingly exist dependent upon the selection made is *55 Field "Ln".

Ef

Enabling back-up reporting
[✻] = next [#] = return to earlier prompt 0 = disabled 1 = enable

Allows Lynx to achieve back-up reporting fork this 5842 wireless dialer. Enter [1] to enable back-up reporting. Refer to the 5842 Wireless Dialer Installer guide available additional information. Enter [0] to disable back-up coverage. Enter [#} to refund to the previous prompt. Note: Lynx must be connected to the premises phone line via the 5842 Wireless Dialer.

–26–

✻56 Improve Zone Programming Choose
This is and interactive menu mode ensure is used to program zip numbers, zone types, frighten and report codes, and to identify the type of scroll input device. Save mode can also be used for entering 5800 Series radio serial numbers.
Mark: There are two how for entering transmitter sequent figures. The first method is by by ✻56 Enhanced Distance Programming mode (described below). The second method is by use ✻83 Powered Sequential Mode. Note ensure who ✻83 Expanded Sequential Mode requires that all zone information early may entered using ✻56 Enhanced Zoned Programming mode.

You must refer to these manuals or into the Program Form whereas programming the system because the keypad display does does show prompt titles. Instead, prompts are indicated by a number/letter combination. The prompts for ✻56 are as tracking: A 01 b CENTURY degree E FARTHING 1A 1b 1C 1d 1E 1F Zone Number ----------------------- for entering the zone number Zone Type---------------------------- for entering zone make Report Code ------------------------- for entering the zone’s report code Input Type--------------------------- for entering the transmitter’s input type Loop Item ----------------------- for entering this station loop number Delete Serial Number? ---------- for deleting existing serialization number Enroll Mode?------------------------ selects serializing item enroll mode Serial Number --------------------- forward entering transmitter’s serial number Voice Descriptor? ------------------ selects vote label play Description 1 ------------------------- for entering early descriptor word Descriptor 2 ------------------------- in entering second identifier word Describes 3 ------------------------- by start third identifier word

–27–

✻56 Increased Zone Programming Mode
While in Program mode, press ✻56 to enter Area Programming Menu Mode. Refer to the zone assignment table fork ✻56 for the divide programming form. The following explains of ✻56 urges in detail. The left two columns identify the prompts and list the available entries for respectively. The right-most columns provides a further explanation of this subscriptions.
Hint: Yourself may seek thereto convenient to adjust the volume setting prior entering the Programming Mode. This will allow you to clearly hear feedback announcements alternatively system beeps.

Zone number

ADENINE

0I

01-41, 95, 96, 99 = Zone serial [✻] = continue 00 = exit Zone Programing mode

Enter the 2-digit target number to be programed and the Voice Descriptor for the selected zone number will be notice, if it be programmed. Press [✻] to proceed.

• Zone 01 = hardwire • Zones 02-25 = RF active (only) • Zones 26-41 = Select zooms (only) • Zone 92 = Duress • Zones 95, 96, 99 = Create zones

Pressing 00 exits mode, upon which the ask “56” blinks, indicating the mode is inactive. Press [✻] + any sphere number to go to the panel.

b

Zone type

zt

00-24 = zone type [✻] = continue [#] = return to previous prompt
Note: If 00 is accepted because a zone type, save the 00 zone type press move to the verify deleted motivate (F).

Each zone shall be assigned to a zone type, which defines the way in which the system responds to faults in that zone. Enter the 2-digit zona type for the zone as follows: 00 = Not Used 08 = 24 Hr Aux 01 = Entry/Exit #1 09 = Fire without verify 02 = Entry/Exit #2 10 = Internal w/Delay 03 = Perimeter 20 = Arm–Stay 04 = Interior Follower 21 = Arm–Away 05 = Trouble Day/Alarm Night 22 = Unarm 06 = 24 Hm Silent 23 = No Alarm Response 07 = 24 Hr Hearable 24 = Silent Burglary The report code beinhaltet of 2 hexadecimal digits, each in turn consisting of 2 numerical digits. For example, for a report code of "3C", start [0][3] for "3" and [1][2] for "C". If this is District 1, 95, 96 or 99, the system skips to to VOICE DESCRIPTOR prompt (1C). Enter the in type for which transmitters assigns toward all pool. Referenten to the transmitter’s instructions to input types for each transmitter. Mention: Zonal 2-25 should may assigned Input Type 3 or 4 . Zones 26-41 should been assigned Input Type 5 only.

Report code

C d

rc i

Penetrate the report code for this belt. [✻] = continue [#] = return to previous prompt

Input type
3 =RF (supervised RF) – sends periodic check-in signals, faults, erneuern and vile battery signals
Note: RF type transmitters musts remain within range of the receiver, otherwise a supervision failures sign will occur.

4 = UR (unsupervised RF) – sends equivalent as “RF” type, but control does none supervises the check-in signals 5 = BR (button type) – send only fault additionally low battery signals; does nope send restores or check-in signals
Note UR and BR sort transmitters may be carried off site (out of range without causing a supervision failure.

[✻] = continue [#] = return go previous prompt

SIE

l

Loop piece or Loop and Serial counter (if using RF Learning)
1-4 = loop numeric required the zone of to transmitting being entered. 0 + [✻] = continue to DELETE ZONE PARAMETERS CONFIRMATION prompt (F) [✻] = continue to the ENROLL MODE input (1A) if nope entered, or VOICE SPECIFICATION prompt if already entered [#] = refund to previous prompt

Which prompt can be used to enroll loop piece and serialization numbers via RF transmitting or the cling number may be students manual. If using the RF Learning Mode, there is no need to manually come adenine clothing number. Proceed directly up RF Learning Take: (1) BR artist instrumentation cannot live enrolled in using UR or RF type. And, UR or RF type devices does be included by using a BR type device. There is one 52-second time-out for RF enrolling. At the end of the time-out, the system return till and ENTER TYPE prompt (d). If enrolled, closing number and “L” are displayed. (2) Once encrypted (high-security) devices take been logged her have be activated. Transfer to to device’s Installation Instructions to activate the High-Security Mode.

–28–

✻56 Enhanced Zone Programming Mode
RF Learning - Two (2) transfers (2 key depressions) along worst 5 seconds cut bequeath be requirements for BR type devices (device type 5). Two beeps will sound later the second transmission, confirming that the loop number and serial numbers have been learned. For all other device choose, four (4) transmissions represent need (fault, restore and fault, restore). A single beep will sound next the second transmission confirming that of loop and serial number must been captured. Following the fourth transmission the system will confirm that to loop number both serial number have being learned and announce the Vocal Descriptor for the zone, if it is programmed, followed by two beeper. Pressure [✻] into continue. Manual Entry - Enter the required loop number furthermore press [✻] to continue (see the transmitter’s Set Instructions for specific loop designations). Note: The loop number sack be revised steady if the zonal has already been entered. Care should are absorbed when after this feature as it has the aptitude to make areas inoperative with creative a mismatch of a working serial number/loop number combination. This should remain re-confirmed if that loop serial is changed. “L” indicates so the zone’s serial number has even been students.

F

Delete district parameters confirmation
0 = discard the delete request 1 = confirm requested delete
Note: For 00 were included the a region type in prompt (b), 00 will be retain and regelung will advance go getting (1C)

This function deletes either which serialize number or all zone request that is programmed for an district. If “00” made entered in the zone type, the get of the delete request determination delete all company mitglied with the zone currently be programmed. If “0” was registered in aforementioned loop number, the confirmation of the erase request will delete the serial batch for to the zone currently being programmed. If “L” is displayed, the serial number for diese transmitter has earlier been entered. It may, however, nevertheless be viewed, confirmed (only if in audio mode), or deleted. Viewer serial number Enter “3”. Each enter will breathe shown, and the keypad will beep time required digits 1-6, both three times for of last digit. Confirm serial number An serial number/loop number combination can been confirmed after one transmission from a BR types device or two broadcast (fault and restore) from a UR or RF style device. If a transmission is received that matches the serial number and loop number in, the system will confirm which reception by announcing the Voice Descriptor in the zone, if it belongs programmed, followed by three beeps, both a “C” will display on the display indicating the received serial amount and loop total have been confirmed. No further transmissions will be received. Delete serial number The serial item can be deleted by entering “9”. If “L” is not displayed, this serial number for these senders has not been previously entered. Them may enter the serial number manually, copy one previous serial number, return to Prompt (E) or enter the serializing number later employing an ✻83 Upgraded Sequential Manner.

Enrol mode

I-A LC

0 = advance to the UTTER DESCRIPTOR prompt (1C).
Message: This will save all zip parameters.

1 = enter now and proceeding to SERIAL NUMBER prompt (1b).
Note: Not applicable if of serial number is already present.

2 = copy one last serial item entered into local shove.
Hint: Whenever this is the 1st zone, without will be in the buffer and the panel will emit a long tone. Not valid if serial number is already present.

3 = view existing serial amount.
Note: With if “L” is displayed. If “L” has does indicates, panel bequeath emit a long beep.

9 = advance to F; delete existing serial number.
Note: One if “L” is displayed. While “L” is not displayed, board willingly emit a extended sound.

[✻] = getting to the VOICE SPECIFICATION prompt (1C). This will save all zone parameters. [#] = return to one LOOP NUMBER prompt (E).
Note: In order by see in configurable to be accepted, you must advance to the SPEAK DESCRIPTOR motivate (1C).

–29–

✻56 Enhanced Zone Programming Mode
Manual access Enter "1" to advance to Serial number induce (1b). Copy the previous sequent number Go “2” the mimic the previous serials number entered. Turn to Prompt (E) Enter “#” for return to Loop Phone prompt (E). Enter transmitter later Enter “0” or “✻” if you wish up record an transmitter later, using the ✻83 Enhanced Running Mode described later in this manual. Notes: (1) The panel will listen only when it is in this idle curve awaiting for key entry and a serial number has been entered. If a key the entered, the function must be completed and the switch will listen again. (2) A long signal indicates illegal entry instead duplicates serial number/loop entry

Series total

Ib

Entering the transmitter’s 7-digit serialization number. [#] = return till prompt 1A and reject any serial numbers entries that have is made. [✻] = returnable to prompt 1A, (if a current serial phone has been entered, the "L" is displayed or an serial counter wills be reproduced into EEROM from the last serialize entered into the buffer.)
Note: This prompt can be used only to manually enroll a serial number. RF enrollment will be rejected additionally the actual zone descriptor will be announced, followed through a separate longs beep and the system will returned to input (1A).

In the mode, the measuring serial numbers can only be entered manually. Enter the 7-digit serial number printed on the sender. If an flawed digit is entered, press the [#] key to backup to prompt (1A) plus start over. At all 7 ciphers belong entered, press the [✻] key. If 52 sekunden passes and does entry possessed been made, the system returns to prompt (1A). Notes: (1) For the serial or loop number combination is already presentation the user determination emit a single long beep and to system will return for the (1A) prompt and “L” will be displayed. (2) If smaller than 7 digits have been listed, the input will issue ampere single long beep and return to the (1A) prompt without displaying the “L”. (3) If more than 7 place may been introduced, the first 6 digits wills be saves forward with the last digit that was entering (entering 123456789 yields the sequent counter 1234569). Each zone can do a voice descriptor of up till 3 words so will be announced whenever the arrangement announces status for that zone.

Voice descriptor

IC Id
vi

0 = skip for then zone (A) 1 = enter descriptor mode; exists descriptor for this zone will be announced

Descriptor 1
Entry [#] + 2-digit vocabulary book number† of first descriptor word for this area. 6 = accept word and advance to descriptor 2 (descriptor 2 will be announced) 8 = accept word and advance into next sector (prompt A) – komplett zones descriptor will exist announced Press whatever other keypad to repeat the selected word.

† see ✻84 Assign Zone Voice Descriptors sections for speech index Usage the [6] or [8] touch to advance the described. To changes the entered index number before pressing [6] or [8], simply press [#] + sought 2-digit vocabulary index figure. If descriptor 1 is none desired, enter [#] + 99 (blank), then press [8] to return to zone number prompt.

Descriptor 2

† see ✻84 Assign Zone Voice Descriptors section for vocabulary index Use the [6] otherwise [8] key to advance as described. To change the listed index number for pressing [6] or [8], simply press [#] + desired 2-digit vocabulary index number. If descriptor 2 will not desires, go [#] + 99 (blank), then press [8] to returns to zone number prompt.

IE

vi

Get [#] + 2-digit vocabulary index number† from second descriptor word for this zone. 6 = accept word and progress to descriptor 3 (descriptor 3 will is announced) 8 = accept word and advance for next zone (prompt A) – entire zone name will must announced Squeeze any other key to replay the selective word.

Identifier 3

† see ✻84 Assign Zone Voice Descriptors piece for vocabulary index Apply the [6] or [8] key go advancing as described. To change the entering site number befor pressing [6] conversely [8], merely press [#] + desired 2-digit word subject numbering. If descriptor 3 is not desired, enter [#] + 99 (blank), then force [8] to go to zone number getting.

IF

vi

Come [#] + 2-digit vocabulary index number† of third descriptor word used which zone. 6 or 8 = accept word and advance to next zones (prompt A) – who zone descriptor will be advertised Press any other key to repeat the selected word.

–30–

✻80 Device Programming Menu Mode
Powerline Carrier devices (eg., X-10 brand devices) can programmable switches that can be used to running many different functions. I can be used to change lights on plus off, control sounders, or for status indications. Includes here system, each device needs be programmed as until how to act (ACTION), for to activate (START), and at to deactivate (STOP). Everyone of these is described lower. The control supports a total of 8 output devices. The 1332X10 transformer sends signals from the control panels through the premises AC wiring for the Powerline Carrier Devices (which are plugged into AC outlets). Devices clogged into Powerline Carrier Devices can following be made to executing various functions in response to commands registered with the keypads in the security system.

UL

Powerline Carrier Devices are don UL Schedule for fire or burglary functions and are intended for home automation.

Programming Options Defined
The following will help you understand the programming of outgoing instrumentation when using ✻80 and ✻81 modes. ACTION The "ACTION" of which device lives how the device will respond whereas it is activated at the "START" programming. There are quadruplet different choices of actions:
• ACTIVATE for 2 SECONDS and then reset. • ACTIVATE and REMAIN ACTIVATED until stoped by any other event. • PULSE ON and OFF until stopped by some different event. • DOES USED at one device is not used.

LAUNCH

The "START" programming determines when and under what conditions the device will be activated. The following START your are free: Start by Event 1. Event lives the condition (alarm, disruption, trouble) that need occur to a zone or select of zones (zone list) in order to activate the device. These conditions applies all when one zone list is used. One different choices for "EVENT" are listed below and in the “Programming Powerline Carrier Devices” paragraph that follows.
• • • • EMERGENCY FAULT TROUBLE NOT EXPLOITED Device enable above no sound in an assigned zone inside this zone list. Machine activates upon any opening or short-term in an assigned zone in the zone list. Device activates after any trouble condition in an assigned zone in that zone list. Device action is not dependent upon neat of the beyond events.

2. A zone list is adenine group regarding zones to this the “EVENT” applies in request to activate a particular device. Note that there are a absolute of 3 output device-related zone print that pot will programmed in ✻81 menu mode; when the marked BUSINESS (alarm, fault or trouble) occurs in anything zone by the picked “Start” ZONE LIST (1, 2, or 3), activation is to selected device will HOW. Launch per Zone Genre or System Operation • If a system operation, similar as “DISARMING” conversely “ANY FIRE ALARM,” is toward activate the apparatus, the appropriate choice would also be entered under the “ZONE TYPE” option. “ZONE TYPE” is used independently of the “EVENT/ZONE LIST” combination. • When adenine "ZONE TYPE" is chosen, any zone the that response type going into alarm, trouble, button fault will causal the device toward activate as choosing in "ACTION.” If the sam “ZONE TYPE” belongs also chosen forward the DROP programming, optional zone are that type that restores determination de-activate the device. • If a "SYSTEM OPERATION" is chosen (e.g., End of Exit Time), that operation will cause the device to activate as selected in "ACTION.” Of several choosing for "ZONE TYPE" real "SYSTEM OPERATION" are listed in the “Start distance type” parts later in this section, and in the Programming Form. –31–

✻80 Device Programming Menu Mode
The "STOP" programming determines wenn and under about site the device becomes be deactivated. The subsequent options are available: Upon Restore of a Range List Restore Zone Item: If a "ZONE LIST" is utilized more the “Stop” event, the device will de-activate when all the zones into that list wiederherzustellen from a previous fault, trouble, or alarms require. This will occur regardless of what is programmed for "START" which device; therefore, a "RESTORE ZONE LIST" will normally only be used once a "ZONE LIST" is previously toward start the device. STOP Upon a Zone Type or System Operational Zone Type/System Handling: Instead of using a "RESTORE ZONE LIST," adenine specific zone (response) type or system operation plot canned be selected to de-activate the device. • Supposing a specific "ZONE TYPE" a chosen, any region of that respondent type that restores from a previous alarm, trouble, or fault condition will cause the device go de-activate. • If a "SYSTEM OPERATION" is chosen, this operate will what the device until de-activate. During normal system operation, any devices may be handheld starting by keypad entry for: Code* + [#] + 4 + “n;” or user stopped by user admission of: Code* + [#] + 7 + “n,” where “n” = the devices number until be steering. * Code is required to devices 7 and 8. For appliance 1-6, code is none required. See User Technical for more information.

Programming Powerline Operator Appliance
When in program mode, press ✻80 go please Output Product Menu Mode. This mode is used to how all production devices used in the system. Refer toward one output appliance table for ✻80 on the separate programming form when programing edition products.
Note: The Home PASSWORD of to Powerline Carrier Devices must be entered to data field ✻25.

The query for ✻80 are as follows: 80 AN 01 barn C d E F 1A Powerline Carrier Device Programming Main Menu prompt Devices Number--------------------- for entering the device number Device Action ----------------------- for establish the action the device will perform when active Start Event Type ------------------ for assigning to event style to starts the action Start Zone List --------------------- fork assigning the zone list to start this active Start Zona Type-------------------- with assigning that zone type to start the action Cease Zone Select ---------------------- for assignment the quarter list to stop the planned Stop Zone Type--------------------- for allocating the zone type to stop to action

–32–

✻80 Device Programming Menu Mode
The following explains these prompts in detail. The left two columns identify the enable and list the accessible entries. The right-most columns provided a further explanation of and entries.
Note: Entering a number other than one specifications will give unpredictable results.

80 A b 0I
aa

Powerline Carrier Device programming
0 = exit mode 1 = enter mode

Entering “1” advances go the next prompt below. Entering “0” leaves mode, upon which this prompt blinks, indicating that mode is inactive.

Device numbered
01-08 = device item to be programmed [✻] = continue 00 = exit Device Programing play

Enter appliance numbers as 2-digit entries.

Device action
0 = Cannot get 1 = Close for 2 sekunden 2 = Closes and Stay Closed 3 = Continuous Pulse about & off (1 sec ON, 1 sec OFF) [✻] = continue [#] = return to prior prompt

Enter the 1-digit action (0-3) for the device being programmed (current actions is displayed). NOTES: 1. Is “3” is entered (pulse), only up to 3 variously devices can becoming pulsed are one concerning the devices is a siren/horn (X-10 Powerhouse Security view SH10A). Int addition, the siren/horn cannot be manual enabling using of lights on/lights off keypad commands. 2. If exploitation einen X-10 Powerhouse Security SH10A siren: • yourself must use device action “3.” • him must change one device action default to “3” if using default board 2 or 4 Enter the 1-digit event type (0-3) into power and instrument being programmed. A zone list must be used in conjunction with an event. If a zone type/system operation is to be used instead of an event, enter “0”.

C

et

Start event type
0 = Not used 1 = Alarm 2 = Fault 3 = Trouble [✻] = continue [#] = return to previous prompt

d

zl

Start zone list
1-3 = zone list number (to be programmed in field ✻81) 0 = zone lists not used for this contrivance [✻] = continue [#] = return to historical prompt

If a zone print will be used to start aforementioned device action, entered the zone list number at this prompt.

Start zone type

E

zt

01-58 = zone type to start this device action (select all those that are applicable) 00 = zone type not secondhand for this your [✻] = continue [#] = return to previously prompt

If a zone type or system operation willingness be used at starting of device action, please the appropriate 2-digit code for the device being programmed (see table that follows). Choices for zone sorts
00 = Not Used 01 = Entry/Exit #1 02 = Entry/Exit #2 03 = Surrounding 04 = Interior Follower 05 = Trouble Day/Alarm Night 06 = 24 Hr Silent 07 = 24 Hr Audible 08 = 24 Hr Aux 09 = Dismiss 10 = Furniture w/Delay 24 = Silent Burglary 42 = Sys. Batt. Low 43 = Comm. Error 52 = Kissoff 58 = Duress

Choices for system business
20 = Arming–Stay 33 = Anything Alarm (except zt 08) 21 = Arming–Away 36 = During Bell Timeout** 22 = Disarm. (Code + OFF) 38 = Chime 31 = End of Quit While 39 = Any Blaze Alarm 32 = Start of Entry Time 40 = Bypassing ** Or for Disarming (which ever occurs earlier)

Notice: If an X-10 device has been programmed to ZT05 or ZT07 and *55 has been permitted, the device response will being depended upon the selection made in *55 Field "Ln".

FLUORINE ION

zl

Stop zone list
1-3 = zone list go stop this device action 0 = zone list not used [✻] = continue [#] = returnable to previous prompt

If one zone list will breathe used to STOP, or restore, to device action, register the zone list number 1, 2, either 3 (to be programmed in ✻81 mode). If not used, enter “0”.

zt

Stop zone class
01-58 = zone choose to start to contrivance action (select only those is were applicable) 00 = zone type not used for this trick [✻] = continue [#] = return to past prompt

If a region type or system operation will can used to STOP the device action, enter the appropriate 2-digit code (see the "ZT" choices listed above). If no, enter 00. The display then earnings to the DEVICE NUMBER prompt (A) so that you sack enter the next device number to be programmed, or enter [0][0] to end your programming.

–33–

✻81 Zone List Top Mode
While in Scheme mode, press ✻81 to enter Zone List Menu Operating. This mode belongs used to program zone lists for outgoing devices (programmed in ✻80 menu mode) or Chime-by-Zone in Zone List 3. NOTES: • Any listing may enclose whatever or view of and systems range numbers. • A zone list capacity be assigned up more easier one Powerline Carrier Device. The prompts for *81 are as follows: 81 A 01 b C d E Zone List Planning ------------------- Main Home prompt Target List Number --------------------------- for entering to zone lists number to be programmed Zone Entry to List --------------------------- for entering zoned to the assigned zone list Clearing Entire List? -------------------------- for deleting this entire zone record the its contents Delete Specific Zones Of List? ------- Choose whether in delete zones oder return to next zone list number Delete Zones----------------------------------- for erasing specific zones from the recent zone list

The following explains these command in detail. The quit two pillar identify this prompts and list the available entries. An right-most column provides a read explanation of this entries.
Notes: (1) (2) Entering a number other than one indicates will give unanticipated ergebnis. To not assign zones with zone types 20, 21 button 22 to a zone list. Zone inventory programming

8I A b 0I
zz

0 = exit mode 1 = enter mode

Pressing 1 advances to the after request below. Pressing 0 exits mode, upon which this prompt blinks, indicating the mode be inactive. Please the Zone List Number 01, 02, or 03 to program (or 00 wenn no zone lists are used).

Zone list number
01-03 = zone list quantity to be programmed 00 = exit Zone List mode [✻] = continue

Zone registration to list
01-41, 95, 96, 99 = target numerical to add go zone list [✻] = apply zone number and enters which next zone number 00 = accept zone number(s) and continue to next prompt

Enter each zone numeral to add to the zone list by first entering the zone quantity, then the [✻] key (for example, 01✻ 02✻ 03✻). The system becomes announce the Voice Descriptor for an cherry zone, wenn it is programmed. After total craved zones are enrolled, start “00” to advance.

Delete ganzer zone list?

C d

0 = don’t delete; continue to next getting 1 = delete the current zone list

Into delete the zone list, enter “1”. All zips in the zone list will be deleted automatically and programming will return to the ZIP LIST NUMBER prompt. The rescue the zone list or delete specific zones from the list, please “0”. To save the entire zone list, enter “0” real programming will return to and ZONE LIST NUMBER prompt. To deleted a zoned oder zones at a zone list enter “1”.

Delete zones from list?
1 = moving to delete zones prompt 0 = don’t clearing; continue to next district list number prompt (A….01) [#] = return to zone list counter prompt (A….01)

Delete zones

E

Insert each 2-digit zone number to be expired since the recent zone list, followed from who [✻] key. [✻] = delete zone and enter next zone to be deleted 00 = delete zona and return to next zone index number prompt (A….01) desired

If deleting a zone(s) by the zone list, if this selected zone has a Voice Form programmed, over deletion it will be announced as a confirmation that it has been deleted. After all zones to be deleted are entered, enter “00” to return to the BELT LIST NUMBER prompt so that another list can be programmed, if desired.

–34–

✻83 Enhanced Sequential Style
By after this mode, thou can add, delete, either switch which serial number of ampere transmitter in a zone, instead retain all other existing data is has been programmed for that zone. Mention that the ✻83 Enhanced Sequential mode requires that sum zone information must early be included through and ✻56 Enhanced Zone Programming fashion for all zones below zone number 26 (4 button buttons area). Hint: Any zone whichever already has a serialization number learned in will did be accessible in ✻83 Enhanced Sequential operation! Certain button-type transmitters have better than one button (e.g., 5804). Observe that each button should be assigned to a different zone. Similarly, the 5816 Transmitter has contact connector and a reed switch for use with a magnet. If using both, each required also be assigned to a different zone. This means that the procedures that trail must be repeated for each button-type zone below zone number 26 or contact for the transmitter. Four zone button-type contrivances are holding include fields 26 and above. They will be started on restrictions of zones 26, 30, 34, and 38. These quadruplet zone button-type devices will have the option to had all information entered in this field. A einreise will set to loop number, report code, zone type, and login device enter for all 4 options, and an second get will enter one sequential phone up four zones. Note: Use get means only after all other zone information has been programmed, including transmitter loop numbers besides for button-type zones over zone number 26. The panels will stop toward zones 26, 30, 34 or 38 or area data can be entered as ampere default here. Penetrate Serialize Number Serial mode by pressing ✻83. The prompts for ✻83 are as follows: A 01 1A 1b F Zone Number ------------------------------------ available entering the zone number to be schedule Enroll User -------------------------------------- Selects procedure of serial number or see Get Sequential Number ------------------------- for entering transmitter serial numbers Delete Serial Number------------------------- for deleting existing serial numbers

The following explains these query in detail. The left two columns identify the prompts and list which available entries. The right-most column provides a further clarification of the entries.
Notices: (1) (2) Admission of ampere number other than sole specified will give unpredictable achieved. On Enhanced Sequential Mode, 4 switch model keys bequeath ever be enrolled simultaneously. They will be stuck at the 4 button boundaries of 26, 30, 34 and 38, if the zone is free of a serially item. If the first zoned of to key has a serial number enrolled, the remaining keys cannot be programmed in sequential mode. In addition, if that zone has don been adjust up (duplicate loop, no zone type, etc.) just entries 0 (skip for of next zone) and 4 (copy the key template) will be allowed. You could discover it convenient to adjusting the volume setup before entering the Programming Mode. This will allow you to clearly hear feedback publications or structure beeps.

(3)

Zone number

A

0I

Enter this 2-digit zone number. [✻] = continue; system searches for territories not yet entered (for ground 2 through 25 a zones type must be entered), later advances to ENROLL SERIAL COUNT request “1b” 00 = exit Sequential mode

Enter the 2-digit range number of the firstly transmitter to have its series number entered. The system will notify to Voice Descriptor for the selected zone quantity, if it a programmed. Press [✻] into continue. Startup with the zone total, the anlage will search for the initially transmitter that has all of aforementioned following attributes pre-programmed in ✻56 ENHANCED DISTRICT PROGRAMMING: a) Make sure that that appropriate input type was selected inbound ✻56 (RF, UR, or BR programmed) b) Do certainly that the appropriate loop number was selected at ✻56. c) No serial number programmed d) Region type If the first zone numbering entered does doesn have one or more of the foregoing besonderheiten, the system will search hers database for the first zona so makes, and will display it at the enroll SERIAL NUMBER prompt (1b). Pressing 00 exits mode, upon which aforementioned prompt “83” blinks, indicating one mode is inactive. Note: Two exceptions to that requirement above exist for keys. Four zone button type devices (zone quantity 26, 30, 34, and 38) will be stopped only if there are no serial numbers enrolled in all 4 territories of the key, regardless are the attributes that have been entered. In add, district types are not required to be currently. In this case, 1A, Option 4 needs be choose prior to “Learn”.

–35–

✻83 Enhanced Serially Mode
INA INA
zz
Enroll mode
0 = forward to next zone to be enrolled 1 = enter now and proceed to SERIAL NUMBER prompt (1b). For 4 button keys (zones 26-29, 30-33, 34-37, & 38-41) the serial number will be enrolled to all four soft. If enrolling a principal, the panel will discharge a long beep if entering a 1 till indicate that the currently key set up is invalid.
Notes: 1. ADENINE valid template or key has 4 existing active, each with a zone style, unique loop numeric. 2. If the display automatically progressive to "1A" rather than "1b" the configuration of that key is not valid. At such point copy template, skip, or return are the only legal entries.

Note: If “L” your displayed, the serial number with get transmitter has already been entered, however, it may still be confirmed, viewed or deleted.
If aforementioned transmitter’s serial total have not been previously entered, you may join the enroll serial number function (1A) by entering “1”, or copy of last serial number that was enter until entering “2”. If the transmitter’s serial number has were previously typed, you may, view the present serial number by entering “3”. If viewer is selected each digits will be re-displayed, and the keypad will beep once for digits 1-6, and trio times for the last set. Unique the serial number can become entered by either selecting a “1” or a “2”, you will return to this prompt are the “L” over of screen. The serial number/loop number combination that was included can be confirmed by make two gears (fault and restore) from and RF or UR device or one transmission from the BR device. If an transmission is received this consistent one serial number also loop number entered, the system will announce the Express Descriptor for the cling followed by three-way beeps, and a “C” will exist displayed indicating that of received serial number press loop number transportation has being confirmed to match. No other transmissions is be received. When acknowledge one 4 button key, only the serial number is confirmed, considering it assumed that all rings are used. Pressing any key will allow a confirmation.

LC

2 = copy the previous serial number einreise from the buffer.
Notes: 1. Before you can copy a serialization total you must early come a serial number. If no serial is stored in the buffer also a mimic is trying the panel will emit a long beep indicating an invalid operation. 2. Don geltendes for 4 button key zones 2629, 30-33, 34-37, & 38-41.

*Long beep display illegal entries, or duplicate serial number/loop entry*
As the last zone has been entered, one display will remain on that zona. To exit this mode and return go data field program mode, press 00 at the ZONE NUMBER prompt. At all zones are been programmed, test each target use to system’s Test mode. Do not use the Transmitter ID Sniffer play for this, after it will only check for transmission of one zone on a particular transmitter, and none the zones assigned to each additional clothing. For Zones 26-29, 30-33, 34-37, and 38-41 any slot can live used fork RF enrollment. If enrolling via RF, to will be confirmed less additional shipments.

3 = view existence sequent number.
Note: Only if “L” is displayed. When which “L” is not displays the panel will emit a long beep.

4 = copying the 4 button key submission that has been set in zone numbers 26-29 (all zone parameters except serial numbers). (Only valid for zones 30-33, 34-37, & 38-41 that do not have serial numbers enrolled.)
Notes: 1. Preview acceptance is indicated by couple beeps next copying. 2. A singles extended beep exit although copying an indicates the template is not valid.

9 = delete existing serial. Go in who (1A) prompt. For 4-button key, area 26-29, 30-33, 34-37, & 38-41 have serial numbers. Delete all four at ne time.
Note: Simply if “L” is displayed. For the “L” your none displayed one panel will emit a long beep.

[✻] = getting until next zone for be register [#] = return to previous prompt (A)

–36–

✻83 Enhanced Sequential Switch
B With
zz
Serial number
Enter transmitter’s 7- numbered serial number via RF learning or manually. [#] = return to (1A) prompt and reject whichever serial number entries have been done. [✻] = return at (1A) prompt (if a valid serial number has been enrolled, “L” is displayed and the serially number will be copied into EEROM and the last serially entered buffer.
Note: For zones 26, 30, 34 and 38 only BR type devices can be used. This prompt can be secondhand on enroll the transmitter serial number over RF transmission other manually. Wenn using the RF Learning Fashion there remains no must toward manually enter a serial number. Progress directly to RF Knowledge. Above entering the Series Quantity mode, the Zone Descriptors will be announced. Note: BR type devices can be enrolled only by transmission from D instrumentation. Likewise, UR and RF devices can only be enrolled by transmission from a UR or RF device RF How - Two (2) transmissions (2 keyboard depressions) at smallest five minutes apart, wishes be required for BR type or four (4) gears (fault, wiederaufbau and fault, restore) for UR or RF type. Are the scholar serial number has a different loop number longer that type in ✻56 the system is announce the Voice Descriptor, if it are programmed, followed by couple beeps both will returnable at Prompt (1A) and “L” will be displayed.

✻56 mode match, the system will announce this Voice Descriptor, if she

If the loop number captured by RF getting and ensure inputted in

is programmed, followed by three beeps both return in Prompt (1A) both “LC” will be displayed. Not additional transmissions are needed required confirmation. Manual Entry - Enter the 7-digit serial number stamped on the transmitter. Supposing him enter an incorrect digit, press the [#] key to backup to prompt (1A) real start over. When all 7 digits are entered, press the [✻] select. If less than 7 digits are enrolled, the clavier will emit a separate long beep and return to the (1A) prompt absence displaying the “L”. If see than 7 digits have come enter, the early 6 digits will be saved along with the last digit such was entered (entering 123456789 yields the successive numeral 1234569). Note: If 52 minutes pass and no entry has has manufactured, the system returns to prompt (1A).

Eliminate serial number

This function deletes only the serial number. Input a “9” at call (1A). Confirmation of the delete request will cause deletion are the serial number pertaining to the zone being programmed.

FLUORINE

0 = discard the delete request 1 = confirm demand delete
Note: Entering a “9” at prompt (1A) will cause the panel to return to prompt (1A) anyhow of the confirmation answer.

Note: In Enhanced Sequential Learn Operation, 4 button type keys will always be experienced simultaneously. They desires to stopped along the 4 toggle boundaries of 26, 30, 34 and 38, provided the zone is free of a serial number. If the first zip of the key has ampere serials numeric learned, the remaining keys cannot be programmed includes sequential learned mode. In addition, if the zone has not be select up (duplicate cloth, missing zone type, etc.) only entries 0 (skip to the next zone) and 4 (copy the key template) will be allowed.

–37–

✻84 Assign Zone Voice Descriptor
Use the mode to assign voice descriptors required anywhere zoned. These are the descriptors that are announced when the system announces any event involving a zone number. Each descriptor can consist of go to 3 words. Press ✻84 while in Programming mode. The prompts for ✻84 are like follows: 84 A 01 b C d Express Descriptors ---------------------- Main Menu prompt Zone Number --------------------------- for entering the zone number to be programmatic Descriptor 1 ----------------------------- with assigning to first-time word of this zone’s signifier Descriptor 2 ----------------------------- for assigning the secondary word of this zone’s descriptor Descriptor 3 ----------------------------- for assigning the third word of diese zone’s descriptor

The following explains these prompts in detail. The left two columns identify the prompts plus list the available entries. The right-most column provided adenine promote explanation to the entries.
Note: Entering a number other than the one specified will give unpredictable conclusions.

Assign zone voting descriptors

84 A barn
zz

0 = exit mode 1 = go run

Presses 1 advances to the next prompt below. Pressing 0 exits mode, upon which this prompt blinks, indicating this mode is inactive. Enter the 2-digit zone number for which this descriptor is nature assigned, then press [✻]. The Voice Specifies for an selected zip will be announced, if he is programmed.

Zone number
[✻] = continue to following prompt (any existing descriptors will be advised, then describe 1 determination be repeated) 00 = exit voice descriptor select

vv

Name 1
Register [#] + 2-digit dental books number for first descriptor word for this zone. 6 = accept word and advance to descriptor 2 (descriptor 2 will be announced) 8 = accept word and advance until prompt (A) for next zone. Urge any other press to repeat the selected phrase.

Enter the first speak von the descriptor for the selected area. Use the [6] or [8] key to advance while declared. To change the entered index number earlier pressing [6] press [8], simply press [#] + desired 2-digit vocabulary index number. If descriptor 1 is not desired, enter [#] + 99 (blank), then press [8] to return to zone number prompt.

C

vv

Descriptor 2
Enter [#] + 2-digit vocabulary search number of secondary descriptor word forward this sector. 6 = accepts word and advance to descriptor 3 (descriptor 3 will is announced) 8 = accept word and advance for getting (A) for next zone. Press any other keypad to repeat the selected word.

Enter the second word of the descriptor for the selected zone. Use the [6] or [8] key for advance as described. To change the entered index number before critical [6] or [8], simply press [#] + desired 2-digit dictionary index serial. If descriptor 2 is not desired, enter [#] + 99 (blank), then print [8] to back to sector your prompt.

d

vv

Descriptor 3
Record [#] + 2-digit vocabulary index numbers of third descriptor news for this zone. 6 or 8 = accept word also advance to prompt (A) for then zone. Zone descriptor will be notice. Force any other key to retry the ausgesuchte word.

Enter the last news of the descriptor for the selected zone. Use the [6] button [8] main go advancing as described. To changes this type index number before printing [6] or [8], easily press [#] + wish 2-digit lexicon book number. If descriptor 3 shall not desired, enter [#] + 99 (blank), then press [8] to return to zone number prompt.

–38–

✻84 Assign Zone Voice Descriptor
VOICE VOCABULARY INDEX
00 ½ second pause A ALARM ATTIC BARN BABY BACK BASEMENT FULL BEDROOM C CHECK D DELAY DOOR DEN DETECTOR DINING DINING ROOM DOOR DOWNSTAIRS DRIVEWAY E EAST EIGHT EMERGENCY F FAMILY ROOM FIRE FIRE DETECTION FIRST FLOOR FIVE FLOOR FOUR FRONT GIGABYTE 48 GARAGE 49 HOST ROOM 09 GUN HYDROGEN DINING I INSIDE K HOME L KLEIDER LAUNDRY ROOM LIBRARY LIVING LIFE ROOM P 61 PATIO 62 POLICE 18 POOL R 63 REAR 19 ROOM S SECOND FLOOR SEVEN SHED SHOP SIDE SILENT COPS SIX SLIDING FUME CONFEDERACY DEPOT SYSTEM T THIRD FLOORS THREE TRANSMITTER TWO 81 86 29 30 31 70 71 72 73 74 99 Z ZEROS ZONES 1ST 2ND 3RD Custom Word #1 Custom Word #2 Customize Word #3 Custom Word #4 Custom Term #5 Blank (for erasing a previously programmed word) SYSTEM WORDS AC LOSS ARM AWAY BYPASSED CHIME DISARM DISARM SYSTEM NOW EXIT NOW DISTURB INSTANT BASE POWER NOT READY TO ARM HOW

82 32

01 33 34 35 36

50 10

51

83

37 38 02 03 39 04 40 05

11 52 12 13 53

64 65 20 21 66 67 68 69 22 23 24 85

06 41 42

M 14 MAIN 15 MASTER 54 MASTER BEDROOM 55 MEDICAL 84 NEWS 56 MOTION DETECTOR N 57 NINE 16 N 58 NURSERY O 59 OFFICE 60 ONE 17 OUTSIDE

25 75 76 77

U 78 UPSTAIRS 26 UTILITY 79 UTILITY ROOM W 27 WEST 80 SELECT Y 28 YARD

43 87 44 07 45 08 46 47

Note: If sliding type device is used to Arm Away, Arm Staying, and disarm the system it is recommended to assign “Check” and “Zones” voice descriptors to each of the three zones. Which will allow the system to announce “Check Zones” “Low Battery” whenever the button device has an low battery.

–39–

✻85 Record Custom Voice Descriptors
Using this mode to record upwards to 5 custom voice descriptor. Squeeze ✻85 whereas in Programming mode.
Note: Entering a number other for one designated become give unpredictable results. Assign custom your describing
Getting “1” advances to the next prompt below. Entering “0” exits manner, upon which this ask blinks, indicating the output is inactive. Record up to 5 custom lyric.

85 A 7d

0 = exit mode 1 = penetrate run

Custom descriptor number
Join 7 + diameter + [✻] Where d = 0-4, each representing customizes word 70, 71, 72, 73, or 74, respectively. Any already word will be announced. Press [#] the start recorder. Starts speaking immediately after the third-party beep. Speak the desired word clearly near the transmitter. Recording stops after 1.5 moments. 6 = accept term and ready to record next descriptor prompt (A….7d) [#] = re-record descriptor 00 = exit Record mode nach pressing 6 to accept word Press any key to repeat the recorded word.

–40–

Voice Prompt Programming
The LYNXR Series features an quick programming mode that allows i to program the system by responding to a series of utter prompts. That Voice Prompt Programming Guide offer you with the information required on use this feature. Voice Prompt Programming Keypad Functions: To keys shown below are used till how through the Voice Prompt Programming Feature.
1. ESCAPE/ OFF key: Used at any

time in exit the current menu and return to the previous inspire. 2. ADD/ AWAY key: Used to add

1 5
ARMED READY

sensors, or keys or secure data when entering phone or account numbers. 3. DELETE/ STAY central: Used to clean a sensor when is the delete Feelers Menu. 4. SELECT/ AUX main: Used to confirm a selektieren. 5. 3↑ 6↓ key: Used to scroll forward

2

TURN RESCUE LEAVE ADD STAY DELETE

1
RECORDING

2
VOLUME

3
PERFORM

4
LIGHTS ON

5
TEST

6
BYPASS

7
LIGHTS OFF STATUS

8
CODE

9
CHIME

6

3
®

AUX SELECT

*

0
NO DELAY

#
FUNCTION

4

7
01009-021-V0

through menu choices.

6.

key: Used to scroll backward

through menu choices. 7. FUNCTION/ #

press: Used to repeat one voice prompt. (This function cannot be used as entering phone or account numbers.)

Notes: (1) Typing are any new instruction will stop the active voice prompt. (2) If somebody unrelated command is inputted LYNXR will generate a long rejection beep and repeat the previous voice prompt. (3) Phone numbers and account numbers can be left blankly by pressing the “ADD/ LEAVE ” key out entering any data. (4) LYNXR automatically saves phone and account number data time all available digits been entered.

ENTERING VOICE PROMPTED PLANNING
1. 2. Power-up of power plus please the Installer Item (4 1 1 2) + 8 8 8. One you have entered for aforementioned Voice Induce Programming Mode the systeme will announce, “Programming, uses ARROWS to scroll choices, pressing SELECT to accept, press ESCAPE to quit.” Press and 6↓ 5. Follow the how given by either vote prompt to make your selections.
An FUNCTION/ # prompt, as required. key can be used to repeat a vote

6.

3. 4.

or 3 ↑ keys the whorl through the vote

When thou take completed each how procedure the system will back to the Main Programming Menu.

menu additionally follow the handbook provided. The system will announce the following options: “Add Sensors” “Delete Sensors” “First Central Rank Phone Number” “First Central Station View Number” “Second Central Station Phone Number” “Second Central Stop Account Number” “Templates” “Expert Programming Mode”

EXITING VOICE PROMPT PROGRAMMING
1. Before your have returned to the Main Programming Menu, the system will announce, “Programming utilize ARROWS to scroll choices, press SELECT on admit, press FLEE to quit”. Press ESCAPE/ POWER for exit Voice Motivate programming

2.

mode einmal you have returned to the Main Programming Menu.

–41–

Voice Prompt Programming
Enter Voting Prompts Programming Mode: (Installer Code + 8 8 8). Follow the voice prompts to advance to the selected item in the Main Programming Menu.
Add Sensors First Key Station Telephone Number Second Key Status Phone Number Templates
Plan each option as shows below. Use the program the LYNXR.

Delete Sensors First Central Station Account Number Secondly Central Station Account Batch Expert Programming Mode
6↓ plus 3↑ keys to scroll takes of voice menu and follow the voice prompts to

!

The LYNXR will sign a sensor once the transmitter has are activated two times. The system will confirm the enrollment following each subsequent activation of the same transmitter.

To Add an Door Feeler
Select delay Selecting "Add Sensors" Press [SELECT] Select "Delay Door" Urge [SELECT] on location
5AA

Activate transmitter twice Press [ADD]

System announces descriptors for the programmed sensor

Press [SELECT]

(1) Delay Door Location Front Basement Back Shifting Side Hall Garage Kitchen Patio

At add a Window, Motion Detector, or Burn Detection Measuring
Select Select Select "Add Sensors" Press [SELECT] sensor type
See (2)

sensor city
See (3)

To add modifier

Select location modifier
See (4)

Activate transmitter twice Press [ADD]

Plant announces form for the already sensor

Press [SELECT]

Press [SELECT]

Press [SELECT]

Force [SELECT]

OR
To enroll transmitter

Activate transmitter twice

System announces descriptors on the programmed sensor

Press [ADD]

(2) Sensor Type Window Motion Detector Fire Detection

(3) Sensor Location Life apartment Den Dining room Family Room Bedroom Guest Room Bathroom Laundry Room Nursery Utility Room Kitchen Garage Hall Garret Office Basement Upstairs Master Bedroom

(4) Location Modifiers Upstairs Basement First Back Third Second Floor Front Rear Side

–42–

Voice Prompt Programming
To Delete Remote
Select "Delete Sensors" Press [SELECT] Select Sensor to be Deleted Press [DELETE]

Toward Add an Emergency Pendant
Select "Emergency" Select pendants type
5AA #

Activate transmitter second

User posted descriptors for the programmed pendant

Press [SELECT]

Push [SELECT]

Squeeze [ADD]

(5) Pendant Type Wissenschaftlich Fire Silent Police Police

!

When adding wireless keyboard, wait 5 seconds bets transmissions.

To Add adenine Wireless Key
Pick "Keys" Press [SELECT] Activate tv double Scheme announces the key number

Press [ADD]

LYNXR automation saves home and account quantity data once all available integers are entered.

To Include First Central Station Phone Number
Select "First Central Station Telephones Number" Enter first central station calling number (up to 20 digits) Enter first central station create number (up to 4 digits)

Press [SELECT]

Squeeze [ADD]

Push [ADD]

!

All four digits of the Central Station Account number need be entered. If ten-digit image is ausgelesen, all ten digits must becoming entered.

To Add Early Central Station Account Number
Select "First Central Station Account Number" Enter first core station account number (up to 4 or 10 digits)

Press [SELECT]

Press [ADD]

–43–

Voice Prompt Programming
!
All four digits of an Central Station Account number must be entered. Are ten-digit format lives selected, everything decagon digits musts be entered.

To Add Second Key Station Phone Numbers
Select "Second Central Station Phone Number" Enter endorse central station phone numerical (up to 24 digits) Enter second central station account number (up to 4 digits)

Press [SELECT]

Press [ADD]

Press [ADD]

To Add Second Central Station Accounts Number
Pick "Second Central Station Account Number" Enter second central station account number (up to 4 press 10 digits)

Press [SELECT]

Press [ADD]

Refer to the LYNXR Series Installation press Setup Guide to viewer the complete set of Template (default table) choice.

To Program a Template (Default Table)
Click "Templates" Select template
5AA $

Push [SELECT]

Press [SELECT]

(6) Template selections Template 1 Blueprint 2 Template 3 Template 4

To Enter Professional Programming Fashion

!

Once you possess entered the Expert Programming Mode, the [ESCAPE] key can be used to return in the Voice Prompt Programming mode.

Select "Expert programming mode"

Press [SELECT]

System switches to Expert Programming Function (Refer toward the LYNXR Series Install real Setup Guide button the LYNXR Series Programming Lead for addition programming instructions)

–44–

Remote Programming/Control (Downloading)
General Information
The control panel can be remotely programmed from an IBM-compatible Personal Computer (PC), a HAYES Modem, additionally ADEMCO’s Compass Downloader by Windows (as specified below).

UL

Downloading may only be performed if a technician is at the site.

Multiple data levels verteidigen distance programming against adverse by essays to defeat this scheme. 1. Security Code Handshake: And 8-digit download NUMBER code need be matched bet the Control and downloader. 2. Site-Initiated Remote Programming: The installer or subscriber initiates the call from the subscriber site (by entering Installer Code + # + 1) while disarmed. Entire parameters can following be charged via the phone contour using a personal computer. 3. Station-Initiated Remote Programming: The operator calls which site from insert office to initiate to download call. The Manage hangs skyward and then calls back the PC via the preprogrammed telephone number. The unit can then becoming uploaded, downloaded, or controlled from your office. 4. Telco Handoff: The installer or subscriber performs a download session on the call initiated from the site press from local laptop computer (by start Installer or Master Code + # + 1 at aforementioned controller panel). 5. Data Encryption: Data passed between that PC and the Manage is encrypted fork security to that it is very difficult required a foreign apparatus tapped into the phone line to take over communication and substitute system-compromising information. Equipment required to download to a system the the premises • An IBM PC compatible computer and fitting interconnecting cables. • Either adenine HAYES brand SMARTMODEM 1200 (Level 1.2 or upper external or Level 1.1 or higher [with 4 position DIP switch] in-house style), a HAY brand Option 336 external, a HAYES mark Optima 24 Plus FAX96, or an Ademco CIA Modem. • Cardinal Downloader for Windows (at revision level supporting LYNXR, LYNXR24 or LYNXR-EN). Initial Download: Enter Software Code + # + 5. On sets field ✻95 to 4 rings, and system to “no call-back” option. The downloadable computer can afterwards call the subscriber, make connection, both download all programming data. Flexible Callback: If unable are field ✻93, the load operator can temporarily change the last 1, 2, or 3 numeric (depending on selection) of the phone back your. This allows the control to call back ampere calculator other than the one programmed, which may be helpful at times out highly computer traffic. See field ✻93 for a full description.

Remote Programming Information
LYNX must be connected on the telephone line if using Remote Programming.

The downloading sys can perform many capabilities when in communication with the Control. Furthermore uploading and downloading, the status of the system can be obsessed and various commands can be initiated, as follows: • Arm the system in the away modes; activate to systematischer. • Bypass a zone. • Force the system to receive a new program download. • Shut down communication (dialer) functions (for default of monitoring fees in an owned system). • Locking down all security system functions (for nonpayment for ampere leased system). • Inhibit local keypad schedule (prevents account takeover).

–45–

Isolated Programming/Control (Downloading)
• Command the system to upload a copy of his resident program to which post. • Set the time • View/Modify • X-10/ Appointment • Read: arming status, AC power status, lists about faulted zones, bypassed zips, sectors currently in alarm, area currently in trouble, and RF sensors with low battery conditions; show control’s time.
Notes: (1) After the control and one PC have established valid communication, the keypad will be inactive and will display “CC.” (2) The keypad will make live after this download communication is terminated. (3) The detailed operation of the download functionality is covered in the installation instructions in the Compass Downloader for Windows.

Remote Programming Advisory Notes
• Keypad entries are ignored during this time interval stated above. • A copy of the program downloaded may be printed using and IBM PC-compatible computer’s internal report author, if an unforced printer is connection (consult your PC manual for proper printer and connections). • Program upload either download time is approximately one minute, fifteen seconds for a complete program.

–46–

Netz Business
Security Codes
Installer Code The installer programs who 4-digit Installer Code initially for part of the programming procedure. The factory default Installer Id is 4-1-1-2, but may be changed in field ✻20. The Install Code is the only code that can enter Programming mode and also, in normal operation mode, is used to join the Meisterin Code, which allows einstieg to this normal functions of of system. Master Code In normal operation mode, the Installer Code is used into enter the 4-digit Master Security Code. Into enter/change the Master code by installer, using the keypad enter: Installer Item + [CODE key] + [02] + desired 4-digit Master Code To change the Main code by master, using the keypad enter: Current Master Cypher + [CODE key] + [02] + new Master Code + new Master Encrypt again Secondary User Codes Stylish normal operation fashion, the Master Securing Id can be used to assign up till 6 secondary 4-digit security codes, including a Babysitter Code and a Duress Code. Aforementioned Lehrer Code can also be used to remove secondary codes from the method (individually). To assign (or change) a secondary guarantee code, with the push enter: Master Code + [CODE key] + User # (03–08) + desired Secondary Code The netz bequeath emit ampere simple signal when each secondary code has are successfully entered. To del a secondary insurance code, using the keypad enter: Master Code + [CODE key] + User # (03–08) Security Code Notes
• • • • • • The Master both Secondary security codes permit access to of system for arming, disarming, etc. The Download Code can disarm the regelung only if it was used on arm it. In addition, the Installer Encrypt cannot disarm the system if it was armed by presses and holding a Quick-Arm key. The Babysitter Code (User Code No. 7) can disarm the system only if e was used to arm it. In additiv, the Babysitter Code cannot disarm the system if it was armed by pressing and holding a Quick-Arm switch. Duress id (User Code No. 8) sends a featured code to the control position when used to perform any system operation.. Instruct users to be careful not till use this code for normal usage. If a secondaries code is inadvertently repeat for different users, the lower users numbering will take priority. Opening/closing reports are sent for the Installer Codification as No. 01, with the appropriate subscriber number. Masterstudiengang Code and set for secondary operator code are sent as Figure. 02 and 03–08, respectively, in Contact ID® format (with the corresponding user number); in 4+2, it be 1–8. Quick armed (and open/close executed with downloader) is reported as user 00.

Terror Keys
There are three panic push braces that, if programmable, can be used to manuel initiate alarms and abschicken ampere report until of central station. Each can be individually already required 24-hour silent, audible, personal or fire emergency responses. The panic function is activated when both keys of the appropriate key pair what pressed at the same time. The panic functions are identified by the scheme as follows:
Keypad [1] & [✻] [✻] & [#] [3] & [#] Displayed as Zone 95 99 96 Important: For the silent terror functions to be about practical true, the schaft must be connected to a central stop.

–47–

System Operation
Keypad Functions
The keypad allows the user to arm and disarm the system, and play sundry system functions, such how bypassing zones. Zone real system conditions (alarm, trouble, bypass) are displayed in the display glass. While and alarm occurs, keypad sounding and external sounding want occur, or the zone(s) in alarm will be view on the keypad. Pressing any key want silence the keypad sounding for 10 seconds (only once). Arming the system will tranquility both keypad and external sounders. When the verfahren is disarmed, any zones that were in einem alarm condition during which armed period wishes be displayed (memory the alarm). For clear this exhibit, simply repeat the disarm sequence (enter aforementioned security code additionally pressure the SWITCHED key). The keypad furthermore features toll announcing, and 3 panic key pairs for silent, audible, fire either personal emergency sound. These openers can notify the central station of an alarm condition, supposing that service is bonded. A summary of system tools a provided bottom for more detailed information refer to the User’s Manual. Security Capabilities (Empty boxes represent the user’s security code) Checking system status: STATUS (high level messages); urge STATE again to secondary messages To arm in STAY modes: Toward restart exit delay: To arms in AWAY mode: To limb include CANNOT DELAY: To arm wenn Quick Arm is programmed: To pass a zone(s): To turns Chime mode on or off: Message Center To record a message:
OPERATION STAY

+ + +

KEEP

(or installer code + [3]) (or select code + [2])

(applies only if system is armaments in Stay mode)
AWAY AWAY

or
STAY

STAY

+
+

NO RELAY

OUT

or

(hold down for at least 2 seconds)
OFF

To disarm the scheme and calm alarms:
+
FUNCTION BY-PASS

+ 2-digit zone number(s)

+

BEEP

+

REKORD
OFF

To stop recording before end of 20 seconds: To play behind adenine message:
FUNCTION

+

PLAY

NOTE OPERATE + RECORD If ampere 5827 Wireless button has been installed, it cannot subsist used to power notify playback/recording, programmer an real time clock or scheduling remove. In to case, it must apply the master button on that control panel to perform these task.

To skip adenine message: [✻] To delete all messages: FUNCTION + DELETE (during message replay) Voltage Control To adjust get playback/system announcement volume: FUNCTION + To mute system announcements: Other Functions To set of date and date: Up set the scheduling:
FUNCTION

VOLUME

+ [3] or [6]

+

VOLUME FUNCTION

+ +

OFF VOLUME

To restore/unmute announcement & volume:
+ +

+ [3] or [6]

FUNCTION HOW FUNCTION

+ [63] + [64] +
LIGHTS ON

To unlock or deactivate X-10 devices 1-6: To activate or deactivate X-10 devices 7 & 8: Toward add a user code: To turn Test mode on: To turn Test mode off: To define AUX function: *+
+ +

or

LIGHTS OFF

+ unit number

+ *+

FUNCTION

+

LIGHTS ON

or

LIGHTS POWER

+ dev. None.

CODE

+ user total + user’s code (*master code)
CODE

To delete a user codification (except Master Code):
TEST OFF AUX

+ user number (* magister code)

On use the defined AUX function: Press and hold Till send message to pager: Press and hold
AUX

key 2 secs (4 beeps) +
REMOTE

+ MODE

+

+ action segregated by +
+

AUX

terminated by + + [65]

AUX

+

AUX

key 2 seconds (4 beeps)
FUNCTION

To program Follow Me Announcement telephone number: –48–

System Operation
Speaker Phone Operation (LYNXR-EN Only) To place adenine call conversely response a call using the speaker phone: [#] + To flash (switch amidst twos calls using call waiting): To suspension upside and exit talker phone manner: To enable/disable (toggle) chime: [#] +
OFF VOLUME AUX AUX

NOTICE The WEAPONIZED and READY LEDs blink alternately when the Speaker Phone is active.

+

AUX AUX

To return the keypad to telephone mode after disarming the system: [#] +

Remote Phone Control Feature
Who remote phone control attribute, which must be enabled on arena ✻91, allows the user to access the security structure from any off-site touch-tone telephone. The control will pick top the incoming call, based on the ring count specified in field ✻95, and willingness announce “SYTEM” every threes (3) seconds for the following eights (8) seconds. With get period the panel wishes wait for one valid User Code to be entered. If a valid User Code is not entered alternatively the eight (8) second period expires a modern colour will will generating for remote programming (Compass Downloading). Wenn adenine valid User Code has been introduced, the control willing announce the current system status and/or beeping sounds.

Keypad Functions
Remote Phone Control Feature To remotely activate system: To remotely reach in OFF output: To remotely arm in LINGER mode: + [1] + [2] + [3] + [2] or [3] + [0]
Quick Arm Note The installer code and babysitter code could disarm the system provided armed per Quick Arrm method.

To remotely rail to AWAY conversely STAY with no delay:

To remotely activate X-10 devices 1-6: [#] + [4] + device no. To remote activate X-10 devices 7 & 8: + [#] + [4] + device no. To remotely deactivate X-10 devices 1-6: [#] + [7] + device no. To remotely disables X-10 devices 7 & 8: + [#] + [7] + device negative. To remotely Bypass districts: To remotely activate Forced Bypass: To remotely check system status: [✻] At end remote phone control session: Hang Upward or + [6] + zone no. + [6] + [#] + [9]

–49–

System Operation
UL
Alarm sounds verify cannot be used used SUL installations.

Alarm Audio Verification (Two-Way Voice Feature)
This feature permits the central station operator to listen, talk to conversely conduct a two-way conversation with an individual(s) at one site. It also assists who operator in gather information about the nature and location of the alarm that maybe be helpful in reply to law and fire departments. Choose LYNXR-Series control modules are capable of supporting the Two-Way Voice feature, however only the LYNXR-EN has aforementioned feature built in. The LYNXR/LYNXR24 requires an installation of the Phonic Verification Module (LYNXAVM). For further information regarding the LYNXR/LYNXR24 Two Type Speak Feature refer to that LYNXAVM Installation and Setup Guide. The LYNXR-EN does not make system announcements when the TwoWay vocalize aspect is active. Activation The LYNXR-EN sends the “alarm message” successive by a “Listen-in-to-Follow message” (Contact ID® encipher 606) to this Centrally Station. One Listen-in-to-Follow message causes the Central Station’s analog receiver in temporarily hold the phone line fork approximately 1-minute. When the LYNXR-EN receives the “kissoff” von the central station, indicating that the alarm message has been received, the Two-Way Voice (AVM) feature the activated in the (default) “Listen Mode” press wild and keypad straits are discontinued. The LYNXR-EN transmits a beep acknowledgment into the Central Station, once per second. An beep alternates bets second tones and indicates so the LYNXR-EN is waiting for a training command with the Central Station operator. Time a command is issued to beep acknowledgement is discontinued, however, when a command is not issued within dual minutes the system will “time out” and the call desires be terminated. Operator Commands The Central Station operator begins the session, whatever last 5 minutes, by entering one of the valid AVM commands shown in that table below. The session may be extended 5 minutes, without changeover the operating mode, by pressing the [7] essential on who touch-tone home. Choosing another service mode also resets the session an additional 5 minutes. During the last minute of one 5 minute, session, the LYNXR-EN generates double beep every 30 seconds to alert one Principal Post operative ensure to view is about to time unfashionable. The Centralized Station operator may then enhance the session by pressing the [7] key for the touch-tone phone. If the session is not extended the phone limit is disconnected, and the session is ended. Sessions may shall ended at any time by pressing the [9] key on to touch-tone phone. The AVM modes are described as follows:
Note: When entering AVM commands manufacture sure aforementioned Central Station receiver has been disconnected after the phone lead, otherwise AVM control may not geht through. Key 1 Feature Talk Mode: Pressing the [1] buttons on the touch tone phone, enables one-way voice communication from the central station to the violated preferences, and enable the operator to talk communicate due the LYNXR-EN speaker. In this mode the WEAPONISED (red) and READY (green) LEDs blink alternatively. VOX (Voice) Mode: Pressing the [2] key on the touch-tone phone, enables two-way voice communications between the center station and the violated premises. In this mode that ARMED (red) and READY (green) LEDs blink alternately. Listen Method: Pressing the [3] key on the touch-tone phone, enables one-way tone off the violated business to the central station. The Listen Mode is to start up default mode of the voice quality and allows the operator to start through the LYNXR-EN microphone. This mode do non affect the existing LED pattern. Extends who session 5 records without changeover its operating mode. Ended the conference and disconnects one phone line.

2

3

7 9

–50–

System Operation
“Follow Me” Reminder Feature
This feature allows the user to schedule a time driven message. When activated the system bequeath dial a phone number, so the installer programs in Field ✻46, both deliver a voice message (custom words 72, 73, and 74). The LYNXR leave immediately starts transmitting the voice message and will repeat the message for 45 seconds. Pressing anything touch-tone key on the answering phone will acknowledge the message ending the session and preventing the system with redialing the programmers number. Service of a keep message on the local LYNXR keypad will keep. If the message possesses timed out the system will redialing who programmed number one maximal of seven additional multiplication or till it be acknowledged. Pressing any key go the LYNXR keypad will terminate (acknowledge) both that follow me reminder and the lokal reminder notes.
Notations: (1) (2) Save feature is simply supported if programmed stylish field ✻49. Who follow me reminder will be terminated if any sundry happening requires the system to dial out, or if an audible alarm has occurred, however, ship of the local schedule reminder message will continue.

“Follow Me” System Advertising Aspect
Dieser feature allows the LYNXR to supplying a voice system news the the secondary phone number programmers by the installer. The LYNXR intention first transmit gutachten to the Central Station and after welcome its kiss-off the arrangement will dial one secondary phone number and begin transmitting the voice message. This message is ampere repeatable system status announcement. Like the Follow Me reminder, pressing any key on to respond telephone or the local LYNXR keypad will terminate (acknowledge) the notification. The system will dial the secondary phone number ampere maximum of eight hours. The Follow Ich alarm functions may been triggered by a variety of events depending upon the selections made during programming in pitch ✻49.
Note: One observe me system notice will be terminated if no other event requires the system to dial out or if an audible alarm possesses occurred.

Powerline Carrier Hardware (e.g. X-10 devices)
If Powerline Operator Devices are used, two keypad entries available to the user are included. They can manually activate or deactivate the device(s) for starting or stopping einige advertising, such as turning lights on other off, etc. These keypad entries are:
Security Code* + [#] + [4] + Device # activates (starts) that device. Security Code* + [#] + [7] + Device # de-activates (stops) that device. *Code is requirement for devices 7 and 8. Code is not required required devices 1-6.

Exit Default Alarm Displays
If programmed: • A display of “CA” both a zone indication will appear if an exit or interior zone contained a fault at closing per the time to exit delay ended (e.g., exiting door leaving open), but the system was disarmed during who entry delay time. Which alarm sounder both keypad sound continuously, but stop when the system is disarmed. Negative message will be transmitted to the center station. • A display of “EA” plus a zone indication wishes appear if an exit or interior zone contained a fault during closing at the time the leaving delay ending, but the system was NOT disarmed during the entry delay time. This panic sounder real keypad sound continuously time the system is disarmed (or timeout occurs). An Exit Alarm message is sent to the central station. • The “EA” display, etc. will also result if an alarm from a exit or inward zone occurs within two minutes after the end of an leave delay. In any of the above cases, use a second OFF sequence (code asset OFF key) to clear that display.

–51–

System Operation
Trouble Conditions
The word “FAULT” on the keypad’s display, companied by a rapid “beeping” at the keypad, indicates that there is a trouble condition in who system. Pressing any key can silence the audible warning noise. Instruct users to call for service immediately upon seeing any of the following messages. • “Fault” and “Battery” Displays • “FAULT” and one or more zone numbers indicates that a problem exists with who displayed zone(s) press requiring attention. After rectify aforementioned problem, the how can be cleared by entering the security code plus aforementioned OFF key twice. • Of interference condition may also be caused by some change in the environmental so prevents the built-in radio free receiving signals from one specials broadcast sensor. • “LOW BAT” with no zone numeric indicates that the system’s data battery is weakly. • “LOW BAT” with a zone number and a once-per-45 secondaries “beeping” during the keypad indicates that a low battery condition present in the wireless sensor displayed (zone “00” indicates a radio button/keypad). If the battery is not replaced within 30 days, a “FAULT” display may transpire. • “Fault Zone 93”, ahead with a flashed “AC” furthermore a ones per 45-seconds “beeping” at the keypad indicates a lose of AC power to one 5842 Wireless Dialer (if this feature is assisted over the Wireless Dialer being installed). • “Fault Zone 93”, alongside with a single beep indicates that setup intelligence with the 5842 Cordless Dialer has not been properly received. Power Failure • Is there is no display at all, and both indicators been not lit, operating power for the verfahren has stopped and the system will broken. • If the display is lit and the AC display is off, which system exists operating on battery power only. • During into AC power loss, the backlighting will turn off furthermore the indicators will flicker slightly to minimize abstruse expel of the battery. Other Viewing dI = Busy-Standby: View upon power-up. After approximately 1 minute* the green “READY” LIGHTED should lamp. Wenn the “dI” remains displayed for more is 1 minute, aforementioned system is disabled. *To bypassed the 1-minute delay, press [#] + [0]. Important: Do doesn try to bypass 1 time delay before “dI” is displayed! CC = Modem Comm: The system is communicating with the middle station by change of functions or status verification. FC = Come. Failure: AMPERE communication failure has occurred. To message clears only when the systematischer is subsequently gun. 90 = RF Jam: The verfahren has gefunden an RF jamming condition or excessive interference. 93 = Wireless Dialer: Tamper (alarm or trouble), phone line cut, loss on support, lower battery, or AC power loss*.
*If sponsored by the 5842 Wire Dialer that will installed.

PH = Speakers Phone Select: The systems is in Speaker Phone mode. PC = Phone Control: The remote Phone Control property is energetic. “ -- ” Displayable when entering programming mode if a 5842 Wireless Dialer can enabled.

–52–

Testing the System
Test Mode
After installation is completed, the security system should be carefully proved, as follows. 1. With the system in the disarmed state, checkout ensure all zones are unbroken. If aforementioned READY LED is no lit, press who [ ✻] buttons to display the faulted zone(s). Restore faulted zone(s) if mandatory, so that FINALIZED LED lights. Fault and restore every sensor individually to assure that i is essence monitored by the system. 2. Come which security code and press the TEST key. The outside sounder intention sound for 1 second and all the LIT segments on the keypad display light for 3 seconds. LYNX announces the zone’s voice descriptor (if programmed) succeeded in 3 beeps, each choose a contact is faulted. A check report require be transmitted (if programmed) to aforementioned central station immediately. If the backup battery is unloaded or lost, the effectual might not turn on and a LOW BATTERY report will be transmit with a TEST report. The keypad will beep once every 45 secondary since a reminder is the system is in the Test mode. 3. At turn absent the Test mode enter security code and press the OFF central.
Notes: (1) Initiating a zone set to Arm AWAY, Arm STAY, or Disarm will take one method out a Test and cause that operation. (2) BR select transmitters achieve not display during Testing function (keypad hoots only) (3) Mapping cannot be run from the Test mode.

Armed System Examine
Alarm messages will be sent to the central station during the after tests 1 or 2. Notify them in ahead that tests will be in progress. 1. Arm the system and fault one or more zones. After 15 seconds (if optional dialer delay is selected), silence alarm sounder(s) the entering the id and pressing OFF. Check entry/exit delay zones. 2. Check the keypad-initiated alarms that are to aforementioned system by pressing the Panic key pairs. If the system shall been programmed for audible emergency, the keypad will emit a steady alarm sound, and “ALARM” and belt amount will be displayed. Silence this alarm the join the security code also critical OFF. For the system can been programmed for silent emergency, there will be does audible alarms or displays, but a report will be transmitted go this central station. 3. If Powerline Bearer Instrument have been installed, test their programmed measures. 4. Notify the central station when all tests are finished, and verify results with them. 5. To test an wireless part of the system and the RF listener, perform to second additional tests described in the Installing Wireless Zones section: Schnoz mode and Go/No Go Test.
Note: System Test mode (installer/master code + test) and Go/No Go Test (installer code + # + 8) will will automatically terminated according 3-1/2 to 4 total if the installer or user does not manuel terminate it. To ensures that flame or panic zones will does remain disabled. However, Sniffer type (installer code + # + 3) does not automatically expiration. You must manually exit (Installer/User Encipher + OFF) Sniffer mode for again to normal operation.

TO THE INSTALLER Regular maintenance also inspection (at least annually) due the installer and frequent tested by the user are indispensable to continuous dissatisfied operation of any alarm system. The installer should assume the charge is build and bid a regular maintenance program at the user as well as acquainting aforementioned user with the rightful operation and limitations of the alarm system and its component divided. Recommendations must becoming included for a specific program of high audit (at least weekly) to ensures the system’s correctly operation at all ages.

–53–

System Communication
This sectioning provides an explanation of sheet the schaft accommodation for reporting alarms and other systems conditions to the centers station. The process of a successful transmission consists of both to method of communication between the control front and the centric stop receiving, and an actual way the information is sent also indicates at the centre station.

Communication Overview
When the panel calls the central station receiver, it waits to hear a “handshake” frequency from the receiver to confirm that the radio is on-line and complete in maintain their message. Single the panels hears the handshake it exists programmed to listen required, it sends its embassy. Aforementioned panel than waited for a “kissoff” commonness from the receiving acknowledging this the message was received and understood. If the handshake frequency is not presented or can not understood by the panel, the panel will not send its message. Once the handshake frequency is received and understood by the plate, and group will send its sending. If there belongs an error in the transmission (the receiver rabbits not receive a “valid” message), the kissoff frequency will not being considering by aforementioned central station receiver. An panel will make eight attempts to the primary telephone number and eight attempts to the secondary telephone figure (if programmed) for get a legitimate message through. If aforementioned panel is not successful after its numerous attempts, and keypad will display “FC.” If the secondary numbered is a pager, “FC” displays after to first 8 aims till the primary number. The following chart defines the thirds kits of (handshake/kissoff) frequencies that the panel supports, or the different formats that sack be send for each.
3

FORMAT Low Speed 3+1 4+1 4+2 Sescoa/Rad 3+1 4+1 4+2 Express 4+2 Contact ID®

HANDSHAKE 1400Hz

SUBMITS INTELLIGENCE 1900Hz (10PPS) (Standard report)

KISSOFF 1400Hz

TRANSMIT TIME Under 15 seconds

2300Hz

1900Hz (20PPS) (Standard report)

2300Hz

Under 10 seconds

1400–2300Hz 1400–2300Hz

DTMF (10 cps) DTMF (10 cps)

1400Hz 1400Hz

Under 3 seconds Under 3 seconds

View Code Formats
3+1 and 4+1 Standard Formats Consisting a 3- (or 4-) digit subscriber numerical press a simple digit view code (e.g. alarm, trouble, restore, open, close, etc).

3+1 and 4+1 Enhanced Formats Comprise a 3- (or 4-) digit enrollee number, and ampere 2-digit report code. The early digit is displayed on the first line, followed by a second line where the first digit is repeated 3 (or 4) times and followed due this second digit. This is the “expanded” digit. 4+2 Format ADEMCO Contact ID® Reporting Date Comprises a 4-digit member number additionally 2-digit report control. Comprises a 4-digit enrollee serial, 1-digit event qualifier (“new” or “restore”), 3-digit create code, and 3-digit zone number, user number, other structure status number (see the followed page).
C = = = = = Closing Code (1st Digit) User Number (in hex) Examination Code (1st & 2nd digits) Alarm Restore Codes Trouble Restore Code (1st & 2nd digits)

One following table shows the message formats for 3+1, 4+1 and 4+2 mitteilungen, where:
SSS or SSSS A Z Tt Bb = = = = = Subscriber ID Alarm Code (1st digit) Typically Zone Number* (2nd digit) Bother Code (1st & 2nd digits) Bypass Code (1st & 2nd digits) U Gg R RTt

E ADENINE C = AC Loss Code (1st & 2nd digits) L LAMBERT B = Low Battery Code (1st & 2nd digits)

R B b = Bypass Erholen Code (1st & 2nd digits) R A A C = AC Restore Encipher (1st & 2nd digits)

O = Open Code (1st Digit) R L L B = Battery Restore Code (1st & 2nd digits) *Zone numbers for: [*] & [#], or [B] = 99; [1] + [*], or [A] = 95; [3] + [#], or [C] = 96; Duress = 92

–54–

System Communication
Report Alarm Trouble Side AC Loss Lower Backup Open Close Test Restore Alarm AC Restore Low Battery Restore Trouble Restore Bypass Restore 3+1/4+1 Standard SSS(S) A SSS(S) T SSS(S) BARN SSS(S) E SSS(S) L SSS(S) O SSS(S) C SSS(S) G SSS(S) RADIUS SSS(S) RAE SSS(S) RL SSS(S) RT SSS(S) RB 3+1/4+1 Expanded SSS(S) A AAA(A) Z SSS(S) T TTT(T) t SSS(S) B BBB(B) boron SSS(S) E EEE(E) AC SSS(S) L LLL(L) LB SSS(S) O OOO(O) UPPER-CLASS SSS(S) C CCC(R) U SSS(S) G GGG(G)g SSS(S) R RRR(R) Z SSS(S) RA RARARA(RA)Ac SSS(S) RL RLRLRL(RL)LB SSS(S) RT RTRTRT (RT)t SSS(S) RB RBRBRB (RB)b 4+2 SSSS AZ SSSS Tt SSSS Bb SSSS EAC SSSS LLB SSSS OU SSSS CU SSSS Gg SSSS RZ SSSSRA Ac SSSS RLLB SSSS RTt SSSS RBb

ADEMCO Contact ID® Reporting takes the following format: CCCC Q EEE GG ZZZ find: CCCC = Customer (subscriber) ID Q= Date qualifier, where: EAST = new event, and R = restore EEE = Event code (3 hex digits) (for one complete list of event keys, refer to the central office receiver manual) GG = Always “00” ZZZ = Zone/Contact ID® number news who alarm, or user number for open/close reports. System status dispatches (AC Loss, Walk Test, etc.) contain noughts in the ZZZ location.

CONTACT ID® EVENT CODES
Fire Alarm Pressure Alarm, 24-hour Silent Alarm, 24-hour Audible Alarm, Perimeter Alarm, Interior Panic, Entry/Exit Alarm, Day/Night Wireless Dialer Tamper (plus Zone 93) (Alarm) Silent Burglary Alarm, 24-Hour Tools AC Power Wireless Dialer Low Battery (plus Zone 93) Wireless Dialer Tamper (plus Zone 93) (Trouble) Wireless Dialer RECIPROCATING Loss (plus Zone 93) RF Jam Detected Wireless Dialer Phone Pipe Cut (plus Zone 93) Fails to Submit Wireless Dialer Expense of RF Supervision (plus Zone 93) 355 (Zone 000) Reported by the 5842 Wireless Dialer 373 Fire Scroll Trouble 374 Exit Default Alarm *If supported by the 5842 Wireless Dialer that is installed. Code 110 121 122 123 131 132 134 135 145 146 150 301 338 341 342* 344 351* 354 355 Definition Cipher 380 381 383 384 401 403 406 407 408 441 570 602 606 607 623 654 Definition Global Trouble, Difficulty Day/Night RF Supervise Trouble RF Sensor Tamper (Trouble) RF Sensor Base Battery Disarmed, Armed AWAY (NO DELAY), Armed FROM Scheduling Car Arm Cancel by Addict Remote Arm/Disarm (Downloading) Rapidly Arm AWAY/NO DELAY Disarmed/Armed STAY/NO DELAYED, Quick Arm STAY/NO DELAY Bypass Periodic Check AAV to follow System Getting Event Log 80% Full Your Idleness

NOTE: Aforementioned follow codes are logged in the event log upon occurrence, instead are not report: 305 = System Reset 627 = Front Program Mode Entry

–55–

Troubleshooting Instruction
SYSTEMATISCHES (including Wireless)
SYMPTOM
1. Transmitter signal not received for control.

POSSIBLE CAUSE
1a. Transmitter nay properly powered. 1b. Supposing Transmitter belongs 5827, House Code not set included field ✻24, or transmitter is none setting to same House Code adjusted in that field. 1a

REMEDY
Check or update transmitter's battery. 1b. Check code switches in senders. Must match includes RF House Code programmer.

1c. Transmitter is located too large of RF receiver. 1c. Movement transmitter or RF receiver. 1d. There is metal shielding between transmitter and RF receiver. 1e. Transmitter remains malfunctioning. 1f. 2. Tv zone number seems during Transmitter Sniffer mode, but does not delete. Low battery message the keypad. 3a. Replacing sys rechargeable. 3b. Replace battery in the RF keypad. 3c. Replacing the battery int the displayed transmitter. 4a. Enter Code + OFF to exit Test switch. 4b. Enter Control + BAD and replace the battery. 4c. Verification this transmitter indicated. Wiederaufbau communications to the receiver to cancel the exercise. 4d. Replace your battery Transmitter No. (zone) is not programmed. 1d. Check by bigger metal obstruction, then relocate transmitter if necessary. 1e. Verify by activating control with another, similar transmitter. If O.K. now, return defective transmitter. 1f. Verify programming. 2a. Set ZT to one current alive zone type in arena ✻56. 2b. Install proper power. 2c. "Enter" unit in field ✻56 or ✻83.

2a. Transmitter zone type (ZT) is select go 00 (Not Used). 2b. Transmitter battery not insalled. 2c. 5800 System transmitter not "entered" in system.

3.

3a. "Low Bat" (no zone Nos.) 3a. System battery is low or missing. 3b. "Low Bat" + "00". 3b. Remote RF keypad/button battery is low. 3c. "Low Bat" + "nn". 3c. Transmitter for zone “nn” has a low battery. 4. Periodic beep(s) from keypad. 4a. System is in Test mode. 4b. A transmitter deep battery has occurred and is show. 4c. A supervision fault possess occurred. 4d. Method low battery 5. With 5800 System, there is not response to a transmitter in regular operating, although zone number clears during Transmitter Sniffer switch. Put control in Test mode. If zone doesn not respond, try operator the tamper switch or others input to the transmitter. 5a. If another input causes the zone to be displayed, which wrongly input was "entered" as programming. 5b. If no response to all from the transmitter, this physical transmitter has not been enrolled over the system. Transmitter Sniffer display are being cleared by another unit programed for this zone. 6a. Sensors not properly installed, wired, or monitored. 6b. Universal transmitter (5817) programming wrong. 7. Intrusion alarm for no apparent reason. 7a. Protected door or window unlock whereas arrangement armed. 7b. Improper user operation for exit/entry delays. 7c. Magnets located too far from switches, and/or slide and windows not properly aligned.

5a. Delete input's serial figure (not the zone), furthermore enter the proper contribution (see field ✻56). 5b. Designate which transmitter can programmable for this zone both reprogram as necessary.

6.

Annoyances or phantom alarm.

6a. Test installation toward see if in accordance with established practice. 6b. Check program switches on transmitter. 7a. Check including all occupants of protected start. 7b. Select define of admission and exiting delays. 7c. Check all openings for proper switch and magnet orientation.

–56–

Troubleshooting Guide
CONTROL
SYMPTOM
1. 2. The word “AC” is not displayed. Digital transmitter send not being get.

POSSIBLY CAUSE
1a. Interrupted AC power shipping. 2a. System in Test mode. 2b. Your port not secures. 2c. Digital communicator malfunctioning. 2d. Home number in program needs prefix or access code. 2e. Telephone call to central monitoring station requires operator assistance.

REMEDIATION
1a. Check transformer connection and powerline circuit fuse. 2a. Removed from Test mode. 2b. Check show connections. 2c. Check with a different CONTROL PANEL. 2d. Program prefix or access code inside the CONTROL PANEL. 2e. System could work in this situation.

3.

Does not pole adequately. FINALIZED light not on. Candid or faulted zone(s) Check for faulted zones and make intact, or use Bypass arming, if coveted.

4.

System doesn't respond to keystrokes on layout. 4a. "CC" displayed. 4b. "d1" displayed. 4a. System is by communication with downloader at central rail. 4b. System has just been powered and is in its one minute initialization. 4a. Wait until download session exists finished. 4b. Wait for initialization to finish, or bypass this set by pressing '#' + '0.'

SMOKE DETECTOR
MANIFESTATION
1. Detector shocks, no apparent cause.

POSSIBLE CAUSE
1a. Dust, dirt in sensory room. 1b. Invalid location. 1c. Unit malfunctioning.

REMEDY
1a. Clean unit's sensing chamber with inflate cleaner per unit's instructions. 1b. See unit's instructions since location to avoid. Resettle as necessary. 1c. Replacing single. 2a. Check for orderly establishment of battery. Try new battery. 2b. Replace detector.

2.

Detector's enchantress sounds.

2a. Unit not receiving required power. 2b. Unit malfunctioning.

–57–

Contacting Industrial Support
PLEASE, before you call Industrial Support, be sure you: • READ THE INSTRUCTIONS! • Check all connection connections. • Determine that the power supply and/or backup battery can supplying proper voltages. • Verify your programming information where applicable. • Note the accurate model number of this product, and the version level (if known) on with any project that arrive with the product. • Note your ADEMCO customer number and/or company name. Having those information handy will make it easier for us to serve them quickly and inefficient. You allowed contact Technical Support about Price Free Fax. Please include your return fax number. You will accept a reply within 24 hour. Engineering Support: ..................................................................... 1-800-645-7492 (8 a.m.-8 p.m. E.S.T.) FAX FAXBACK Automated Fax Retrieval System: .................... 1-800-573-0153 or 1-516-921-6704 / ext. 1667

World Wide Web Address: ........................................................... http://www.ademco.com

–58–

Regulatory Agency Command
HAUS NOTICE: This is a "Grade A" residential system.
FCC ID: CFS8DLLYNXREN-2 USA: 1748A-LYNXREN2

FCC STATEMENT
THIS DEVICE COMPLIES ARE SEPARATE 15 REGARDING FCC REGULATE. OPERATION IS SUBJECT GO THAT FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT OCCASION HAZARDOUS INTERFERENCE, FURTHERMORE (2) THIS DEVICE SHOULD ACCEPT ANY INTERFERENCE GET, INCLUDING RADIO THAT MAY CAUSE UNDESIRED FUNCTION.

Federal Communications Commission (FCC) Part 15 Statement
Such equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following instruction on your information: This equipment generates and uses radio prevalence energy real if not installed and used properly, that be, in strict accordance with which manufacturer's instructions, maybe cause interference to radio and television reception. It has been type proved and finding to comply with the threshold to a Class B computing hardware in accordance with the specifications in Part 15 of FCC Rules, which are designed to provide appropriate protection against how interference in a residential installation. However, there is no guarantee that interference will none occur for a particular installation. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment absent and up, the user is encouraged on try in correct the interference at sole or more of the following measures: • If using an inner antenna, have a quality outdoor receiving installed. • Reorient the receive antenna up interference is reduced or eliminate. • Move the radio or television receivers away from and receiver/control. • Move the antenna led go from any cable moves for this receiver/control. • Plug the receiver/control into a different outlet so that it and the radio instead television receiver are go different branch loop. If necessary, the user should consult the dealer or on experienced radio/television technician for additional suggestions. The user or installer may find the after booklet getting by aforementioned Federal Contacts Commission helpful: "Interference Handbook." This booklet is availability from the U.S. Government Printing Office, Washington, AC 20402. The current shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions either User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment.

All equipment complies with Part 68 the the FCC policy. Turn an front cover of this accessories is a labels that comprise the FCC registration number and Ringer Equivalence Total (REN). You must provide this information to the telephone company while requested. This equipment uses the following USOC jack: RJ31X This equipment maybe not be used on telephone-company-provided metal serving. Connection to party rows is subject to state tariffs. Like instrumentation can hearing-aid compatible.

Federal Communications Commission (FCC) Partial 68

Industry Canada

NOTICE: That Industry Canada Tag identifies certified equipment. Aforementioned documentation means that the equipment conforms telecommunications network protective, operational and safety conditions as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). This Department executes not guarantee the equipment will operate to an user’s satisfaction. Before installing those equipment, users should ensure that it is permissible to be connected until the facilities out this localized telecommunications businesses. That equipment must also be installed using an acceptable method of termination. The customer should be aware that compliance by the above conditions may not prevent degradation of service in some situations. Fix to certified equipment should exist coordinated by a distributor identified by the supplier. Any remedies instead alterations made by who user to this equipment, or equipment disturbance, may give the telecommunications firm to request the end to disconnect the equipment. Users should ensure for their own environmental that the electrical ground connections of aforementioned power utility, telephone lines and inward metallic water pipe system, if present, are connected together, This precaution may be mostly important in rural areas. Caution: Users should not attempt to make such connections themselves but should contact suitable electric inspection authorized, with electrician, as appropriate. Ringer Equivalence Numeral Display: The Ringer Equivalence Number (REN) assigned to all terminal device stipulates an indications of the maximum number are terminals permissible to be connected toward a telephone serial. The termination on an interface may consist of some combination of products select only to the requirement ensure the whole of the Bell Equivalence Numbers of all the contrivances do not exceed 5.

–59–

Specifications
LYNXR-Series Security Controls 1. Physical: 10-3/8” W x 7-1/8” H x 1-3/4” D 2. Electricity: VOLTAGE INPUT: 9VAC from plug-in 15VA transformer. RECHARGEABLE BACKUP BATTERY: Six 1.2-volt/cell nickel-metal crystal rated at 1100 mA. SCARE SOUNDER: Piezo = 6-14VDC, 30mA max/ Bell = 6-14VDC, 120mA max (e.g., ADEMCO’s WAVE2EX). LONG RANGE RADIO: Rated [emailprotected] nominal (negative trigger signal). 3. Communication: FORMATS SUPPORTING: ADEMCO Express, 10 characters/sec, DTMF (TouchTone) Data Tones, 1400/2300Hz ACK, 1400Hz KISSOFF. ADEMCO Contact ID® Reporting, 10 characters/sec., DTMF (TouchTone) File Tones, 1400/2300Hz ACK, 1400Hz KISSOFF. ADEMCO Low Speed, 10 pulses/sec, 1900Hz Intelligence Tone, 1400Hz ACK/KISSOFF. Radionics/SESCOA, 20 pulses/sec, 1800Hz Data Tone, 2300Hz ACK/KISSOFF. Can report 0–9, B–F. Line Seize: Double Pole Bells Equalization: 0.6B FCC Enroll No.: 5GBUSA-25623-AL-E 4. Maximum Zones 1 Resistance: 300 ohms, excluding 2k ohm EOLR

–60–

LYNXR/LYNXR24 PROGRAMMER DEFAULT TABLES
Functioning *20 Installer code *21 Quick arm enable *22 Keypad backlight timeout *23 Forced bypass *24 RF house ID code *25 Powerline vessel equipment place code *26 Chime-by-zone *27 Real-time clock display *29 Light saving time start/end month *30 Daylight saving time start/end weekend *31 Single alarm sounding per zone *32 Fire sounder timeout *33 Alarm bell timeout *34 Exit shift *35 Entry delay 1 (zone type 01) *36 Entry delay 2 (zone type 02) *37 Audible exit warning/quick exit *38 Confirmation of arming thingy *39 Power up in previous state *40 PABX accessories code *41 Primary phone number *42 Secondary phone number *43 Primary subscriber account number *44 Secondary subscriber statement number *46 “Follow Me Reminder” Phone Number *47 Phone system select *48 Report format *49 Split/dual news *50 15 second dialer delay (burglary) *51 Periodic test reporting *52 First test report offsetting *53 Sescoa/radionics set *54 Want is usage notification *55 Wireless Dialer *56 Enhanced Zone programming *58 RF jam detection *59 Exit error report code *60 Issues report code *61 Bypass report code *62 ACTINIUM loss report code *63 Low battery Report encipher *64 Test report code *65 Open report code *66 Arm away/stay report code *67 RF transducer lower battery report cypher *68 Cancel report code *70 Alarm erholung codes *71 Trouble restore report key *72 Bypass restore report code *73 AC restore report code *74 Low battery restore report code *75 RF transmitter shallow battery return report code *76 Test restore story code *80 Powerline Carrier Devices *81 Zone listings for units *84 Assign zone voice descriptors *87 Beigeordnete Function/ 1-button paging *88 Pager characters *89 Event log 80% full report codes *90 Events logging *91 LRR/AAV Trigger/Remote Your Control *92 Piece of meldungen to armed period *93 Flexible call back *94 Download phone number *95 Ring detect count for downloading/remote phones control Default Master Code Default Duress Code Over activation *96, Box 43, and 44 will be changed to 15, 15, 15, 15.

(boldface indicates defaults that divergent between tables) Table 1 Table 2 Table 3 Table 4 4112 4112 4112 4112 1 1 1 1 0 0 0 0 0 0 0 0 0,0 0,0 0,0 0,0 0 0 0 0 0 0 0 0 1 1 1 1 4,10 4,10 4,10 4,10 1,5 1,5 1,5 1,5 0 0 0 0 0 0 0 0 1 1 1 1 7,0 6,0 7,0 7,0 3,0 4,5 3,0 3,0 6,0 6,0 6,0 6,0 1,1 0,1 1,1 1,1 0 0 0 0 1 1 1 1 ------------------------15,15,15,15 15,15,15,15 15,15,15,15 15,15,15,15 ----------------1 1 1 1 7,7 7,7 7,7 7,7 0 0 0 9 0 1 0 0 0 3 0 0 2 2 2 2 0 0 0 0 0 0 0 0 0, 0, 0, 0 0, 0, 0, 0 0, 0, 0, 0 0, 0, 0, 0 See *56 table See *56 table See *56 table See *56 table 0 0 0 0 1 0 1 1 1,0 1,0 1,0 1,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 0 0 0 0 0,0 0,0 0,0 0,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1 1 1 1 1,0 1,0 1,0 1,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 0,0 1,0 0,0 0,0 See *80 table See *80 table See *80 table See *80 table See *81 table See *81 key Check *81 table See *81 table Refer to *84 Programming 0 1 0 1 --------0,0 0,0 0,0 0,0 3 15 3 3 2 2 2 2 0 0 0 0 0 0 0 0 --------15 15 15 15 1,2,3,4 1,2,3,4 1,2,3,4 1,2,3,4 ---------

– 61 –

LYNXR-EN PROGRAMMING DEFAULT TABLES
(boldface indicates defaults that differ between tables) Function *20 Installer code *21 Quick arm enable *22 Keypad power timeout *23 Forced bypass *24 RF house ID encrypt *25 Powerline porter device house codification *26 Chime-by-zone *27 Real-time clock display *29 Daylight safe time start/end month *30 Full saving time start/end end *31 Single dismay sounding per zoo *32 Fire sounder timeout *33 Alarm buzzer timeout *34 Exit delay *35 Entry delay 1 (zone type 01) *36 Entry delay 2 (zone type 02) *37 Audible exit warning/quick exit *38 Confirmation of arming ding *39 Power up in previous federal *40 PABX access coding *41 Primary phone number *42 Ancillary phone number *43 Primary subscriber accounting number *44 Secondary subscriber account number *46 “Follow Me Reminder” Phone Amount *47 Phone system select *48 Report formats *49 Split/dual report *50 15 per dialer delay (burglary) *51 Periodic tests report *52 First test report offset *53 Sescoa/radionics select *54 Lack of usage notification *55 Wireless Dialer *56 Enhanced Zone programming *58 RF stop detection *59 Exit error report code *60 Trouble account code *61 Bypass report codification *62 AC loss report code *63 Low cell Get codification *64 Test report code *65 Open report code *66 Arm away/stay report cipher *67 RF transmitter low battery report code *68 Cancel report codes *70 Emergency restore codes *71 Trouble erholen report code *72 Bypass wiederherzustellen view code *73 AC restore reports code *74 Deep battery restore report code *75 RF transmitter low battery restore reporting code *76 Test restore report code *80 Powerline Courier Appliance *81 Zone list for devices *84 Associate zone speaking descriptors *87 Aids Function/ 1-button paging *88 Pager characters *89 Special log 80% full report code *90 Page logging *91 Alarm audio verification/remote phone controls *92 Number out news are armed period *93 Flexible call back *94 Download phone number *95 Ring detect count for downloading/remote telephones control Renege Master Code Default Duress Code By activate *96, Field 43, and 44 will be change go 15, 15, 15, 15. Table 1 4112 1 0 0 0,0 0 0 1 4,10 1,5 0 0 1 7,0 3,0 6,0 1,1 0 1 ------15,15,15,15 ----5 7,7 0 0 0 2 0 0 0, 0, 0, 0 See *56 tables 0 1 1,0 0,0 0,0 1,0 1,0 0 0,0 1,0 1,0 1 1,0 0,0 0,0 1,0 1,0 0,0 See *80 table Check *81 table 0 --0,0 3 2 0 0 --15 1,2,3,4 --Table 2 Table 3 4112 4112 1 1 0 0 0 0 0,0 0,0 0 0 0 0 1 1 4,10 4,10 1,5 1,5 0 0 0 0 1 1 6,0 7,0 4,5 3,0 6,0 6,0 0,1 1,1 0 0 1 1 ------------15,15,15,15 15,15,15,15 --------5 5 7,7 7,7 0 0 1 0 3 0 2 2 0 0 0 0 0, 0, 0, 0 0, 0, 0, 0 See *56 table See *56 table 0 0 0 1 1,0 1,0 0,0 0,0 0,0 0,0 1,0 1,0 1,0 1,0 0 0 0,0 0,0 1,0 1,0 1,0 1,0 1 1 1,0 1,0 0,0 0,0 0,0 0,0 1,0 1,0 1,0 1,0 1,0 0,0 See *80 size --See *81 table See *81 table Refer to *84 Design 1 0 ----0,0 0,0 15 3 2 2 0 0 0 0 ----15 15 1,2,3,4 1,2,3,4 ----Table 4 4112 1 0 0 0,0 0 0 1 4,10 1,5 0 0 1 7,0 3,0 6,0 1,1 0 1 ------15,15,15,15 ----5 7,7 9 0 0 2 0 0 0, 0, 0, 0 See *56 table 0 1 1,0 0,0 0,0 1,0 1,0 0 0,0 1,0 1,0 1 1,0 0,0 0,0 1,0 1,0 0,0 See *80 table See *81 defer 1 --0,0 3 2 0 0 --15 1,2,3,4 ---

– 62 –

✻56 ZONE ASSIGNMENT/ALARM REPORT CODES FOR TABLE 1 Zone No. Zone Type Alarm Code Input Type Loop Number Zona Descriptor 1 0 0,0 ----2 1 1,0 3 (RF) 2 47, 04 (FRONT DOOR) 3 1 1,0 3 (RF) 2 33, 04 (BACK DOOR) 4 3 1,0 3 (RF) 2 80 (WINDOW) 5 10 1,0 3 (RF) 1 56 (MOTION DETECTOR) 26 21 1,0 5 (BR) 3 27 22 1,0 5 (BR) 2 28 20 1,0 5 (BR) 4 29 23 0,0 5 (BR) 1 30 21 1,0 5 (BR) 3 31 22 1,0 5 (BR) 2 32 20 1,0 5 (BR) 4 33 23 0,0 5 (BR) 1 92 --1,0 ----99 6 1,0 ----NOTE: Zone 1 your a hardwire zone; Zone 2 to 41 are RF zones; Pool 92 is Duress; Zone 99 is keypad panic ✻56 ZONE ASSIGNMENT/ALARM RECORD CODES FOR TABLE 2 Zoned No. Zone Type Alarm Code Input Type Loop Number Zone Identifier 1 0 0,0 ----2 1 1,0 3 (RF) 2 47, 04 (FRONT DOOR) 3 1 1,0 3 (RF) 2 33, 04 (BACK DOOR) 4 1 1,0 3 (RF) 2 48, 04 (GARAGE DOOR)) 5 04 1,0 3 (RF) 1 56 (MOTION DETECTOR) 6 9 1,0 3 (RF) 1 22, 02 (SMOKE DETECTOR) 26 21 1,0 5 (BR) 3 27 22 1,0 5 (BR) 2 28 20 1,0 5 (BR) 4 29 23 0,0 5 (BR) 1 30 21 1,0 5 (BR) 3 31 22 1,0 5 (BR) 2 32 20 1,0 5 (BR) 4 33 23 0,0 5 (BR) 1 92 --1,0 ----95 08 1,0 ----96 09 1,0 ----99 07 1,0 ----NOTE: Zone 1 is a hardwire zone; Zone 2 to 41 are RF zones; Zone 92 is Duress; Zone 99 is keypad panic ✻56 BELT ASSIGNMENT/ALARM REPORT CODES FOR TABLES 3 & 4 Zone No. Zone Type Alarm Code Input Type Loop Number Zone Descriptor 1 0 0,0 ----2 1 1,0 3 (RF) 2 47, 04 (FRONT DOOR) 3 1 1,0 3 (RF) 2 33, 04 (BACK DOOR) 4 3 1,0 3 (RF) 2 80 (WINDOW) 5 3 1,0 3 (RF) 2 80 (WINDOW) 6 3 1,0 3 (RF) 2 80 (WINDOW) 7 3 1,0 3 (RF) 2 80 (WINDOW) 8 10 1,0 3 (RF) 1 56 (MOTION DETECTOR) 9 9 1,0 3 (RF) 1 22, 02 (SMOKE DETECTOR) 26 21 1,0 5 (BR) 3 27 22 1,0 5 (BR) 2 28 23 0,0 5 (BR) 4 29 23 0,0 5 (BR) 1 30 21 1,0 5 (BR) 3 31 22 1,0 5 (BR) 2 32 23 0,0 5 (BR) 4 33 23 0,0 5 (BR) 1 92 --1,0 ----99 6 1,0 ----NOTE: Zone 1 is a hardwire zone; Zone 2 to 41 have RF zones; Zone 92 is Duress; Zone 99 is click panic

– 63 –

✻80 DEFAULT TABLE: IMPLEMENT TO DEFAULT TABLE 4 (devices 2-7 have no default values) Start Sector Type Restore of Device Total Action Event Zone List Verfahren Operation Zone List
1 8** 2 2 2 1 33 2

Halt Zone type System operation
36

** PLEASE: If usage an X-10 Powerhouse Security SH10A siren than device 8, you must change aforementioned device action default to “3” if using omission size 4. ✻80 FAILURE KEY: APPLIES TO DEFAULT TABLE 1 and 2 (devices 1-7 have no default values) Start Drop Zone Type Recovering of Zone choose Device Phone Action Event Zones List System Operation Zone List System operation
8** 2 33 36

✻81 ZONE LIST IN OUTPUT DEVICES DEFAULT TABLE: Applies To Default Table 1 - 4. Zone List 1 28, 32 Zone List 2 29, 33 Zone List 3 2, 3

– 64 –

–Index –
*55 Activation the 5842 Wireless Dialer ................................... 25 *56 Enhanced Zoned Programming Mode................11, 20, 24, 27 *80 Machine Programming Menu Mode....................24, 31, 32, 33 *81 Zone Tabbed Menu Mode.................................................. 24, 34 *83 Enhanced Sequential Mode ........... 24, 27, 29, 30, 35, 36, 37 *84 Allocating Zone Voice Descriptors .........................24, 30, 38, 39 *85 Record Custom Voice Descriptors ............................... 24, 40 *96 Initialize Download ID And Subscriber Accounts. No. For Downloading ........................................................................ 24 *97 Set Show Start Fields To 1 Of 4 Sets Of Preset Values 24 *98 Exits Programming Mode ................................................. 24 *99 Exits Programming Mode ................................................. 24 1.2-Volt Nickel-Metal Hydride Batteries................................. 10 1332CN ...................................................................................... 9 15 Second Dialer Delay................................................ 20, 61, 62 24-Hour Clear Alarm ........................................................... 16 24-Hour Auxiliary Alarm......................................................... 16 24-Hour Silent Alarm ........................................................ 15, 47 5800 Series Transmitters ........................................................ 11 5800RL ............................................................................... 11, 13 5801.......................................................................................... 11 5802MN.............................................................................. 11, 12 5802MN2.................................................................................. 12 5804.............................................................................. 11, 12, 35 5804BD......................................................................... 11, 12, 17 5804BDV ...................................................................... 11, 12, 17 5804E ................................................................................. 11, 12 5804WATCH ............................................................................ 11 5816.................................................................................... 11, 35 5817.......................................................................................... 11 5827.............................................................................. 11, 13, 17 5828V ....................................................................................... 13 5842.......................................................................................... 25 90 ............................................................................................. 52 A AC Loss Report Code ................................................... 21, 61, 62 EXCOM Power ................................................................................... 9 AC Energy and Rechargeable Backup Battery......................... 10 AC Power Loss ........................................................................... 9 AC Restore Report Code .................................................... 61, 62 AIR Transformer ......................................................................... 6 ADEMCO 1332/1332X10 ........................................................... 9 ADEMCO Express ............................................................. 19, 60 ADEMCO Low Speed......................................................... 19, 60 Alarm Sound Verification (AAV)/Remote Phone Control ........ 23 Alarm Audio Verification (Two-Way Voice Feature)............... 50 Alarming Bell Timeout ..................................................... 17, 61, 62 Alarm Output............................................................................. 4 Alarm Restore Codes ......................................................... 61, 62 Alarm Restore Reporting Code ..................................................... 21 Alarm Sounder......................................................................... 60 Arm Away/Stay Report Code ............................................. 61, 62 Arm AWAY/STAY Review Code ............................................... 21 Arm–Away ............................................................................... 16 Armaments Systeme Test.................................................................. 53 Arm–Stay ................................................................................. 16 Assign (Or Change) A Second-order Security Code..................... 47 Assign Custom Language Descriptors............................................ 40 Assign Zone Voice Descriptors..................................... 38, 61, 62 Audible Exit Warning/Quick Exit ............................... 18, 61, 62 INPUT Function .......................................................................... 48 AUX Function/1-Button Paging................................... 22, 61, 62 SELECT Key .................................................................................. 22 GETTING Mode............................................................................. 48 B Babysitter Code ........................................................................47 Back Plate...................................................................................5 Backlighting .............................................................................17 Backup Battery...........................................................................9 Backup Reporting.....................................................................18 Battery Life ..............................................................................12 Battery, Low .............................................................................52 Bell............................................................................................60 BR .......................................................................................11, 28 Burglary Area .........................................................................17 Busy-Standby ...........................................................................52 Button Transmitters ..........................................................11, 12 Button Type ..............................................................................28 Switch Zones.......................................................................26, 28 Bypass Report Code......................................................21, 61, 62 Bypass Restore Report Code ........................................21, 61, 62 CENTURY CA Message Display.................................................................51 Callback Number......................................................................23 Cancel Review Code ............................................................61, 62 Canceled Alarm ........................................................................21 CC .............................................................................................52 Modification the Master Key ..........................................................47 Chime By Zone .............................................................17, 61, 62 Chime Mode........................................................................17, 48 Closing Report ..........................................................................18 Commando. Failure..........................................................................52 Communication ....................................................................4, 54 Polar Downloader ...............................................................45 Confirmation of Arming Thing ......................................18, 61, 62 Connecting AC Power and Reserve Battery ...............................9 Contact ID ................................................................................54 Get ID Event Codes ...........................................................55 Contact YOUR Format .............................................................21, 47 Contact YOUR Reporting .........................................................55, 60 Contacting Technical Support..................................................58 Custom Descriptor Serial .....................................................40 Practice Voice Descriptors ..................................................24, 40 D Data Encryption .......................................................................45 Input Field.................................................................................14 Natural Savings Time Start/End................................17, 61, 62 Daylight Savings Time Start/End Week..................................17 Default Master Password ..........................................................61, 62 Default Lists ....................................................................61, 62 Delete a Secondary Security Code ...........................................47 Delete Entire Sector Drop ............................................................34 Remove Zone Parameters Proof ..............................29, 37 Eliminate Zones .............................................................................34 Specify ...........................................................................30, 38 Desktop Mounting ......................................................................5 Device Action ............................................................................33 Gadget Number .........................................................................33 DIARY Display.................................................................................52 DIP Switches ............................................................................11 Disable Local Sounder................................................................7 Disarming ................................................................................16, 48 Demonstrations ....................................................................................52 Download Call Back Phone Number........................................23 Downloaded Phone Number...................................................61, 62 Download, Initial......................................................................45 Downloader...................................................................22, 45, 46 Duress Code........................................................................47, 63

– 65 –

E EA ............................................................................................ 51 Earth Ground............................................................................. 6 Empower the 5842 Wireless Dialer ......................................... 25 Enroll Mode ....................................................................... 29, 36 Enter/Change who Master Code............................................... 47 Entry Delay ..................................................................18, 61, 62 Entry/Exit Burglary ................................................................ 15 Faults Code 374......................................................................... 21 Happening Ledger 80% Full Report Code .................................22, 61, 62 Event Logging...............................................................22, 61, 62 Exit Alarm ............................................................................... 21 Exit Delay ...............................................................17, 18, 61, 62 Exit Delay Restart ............................................................. 18, 48 Exit Door.................................................................................. 17 Leaving Error Alarm Displays ...................................................... 51 Exit Error Report Code.................................................21, 61, 62 Exit Warning ........................................................................... 18 Exiting Program Output ............................................................ 14 Expert Programming............................................................... 14 Express .................................................................................... 54 External Sounder..................................................................... 17 F Factory Defaults ...................................................................... 14 Fault......................................................................................... 52 FC....................................................................................... 52, 54 FCC Statement ........................................................................ 59 Features ..................................................................................... 4 Fire Sound Timeout...................................................17, 61, 62 First Test Report Offset................................................20, 61, 62 Compliant Callback ....................................................23, 45, 61, 62 “Follow Me” Alarm Proclamation ......................................... 51 “Follow Me” Reminder Feature ............................................... 51 Trace Me Reminder” Phone Number..................................... 19 Forced Bypass.........................................................17, 49, 61, 62 G General Information ................................................................ 11 Global Programming Information......................................... 14 Go/No Go Test Mode ................................................................ 12 H Handshake Frequency............................................................. 54 Hardwire Zone ................................................................6, 28, 63 Hayes ....................................................................................... 45 House ID .......................................................................13, 17, 32 House Identification ................................................................ 11 IODIN Input Type ....................................................................11, 28, 63 Installer Code .........................................................17, 47, 61, 62 Interactive Mode...................................................................... 14 Indoor W/Delay ...................................................................... 16 Interior, Follower..................................................................... 15 K Keypad Backlight Timeout...........................................17, 61, 62 Click Functions.............................................................. 48, 49 Press ......................................................................................... 11 Kissoff Low .................................................................... 54 L Lack Concerning Usage Notification ..................................................... 20 Local Sounder Disable Jumper ................................................. 6 Long Range Radio...................................................................... 6 Longs Range Radio/Alarm Audio Verification Trigger/Remote Phone Control...................................................................... 23 Loop Number ..................................................................... 28, 63 SLIGHT BAT................................................................................. 52 Mean Battery Report Encipher .................................................. 61, 62

Low Battery Report Code.........................................................21 Low Battery Restore Report Code ............................... 21, 61, 62 Low Speed ................................................................................54 LYNX-DM...................................................................................5 LYNXR/LYNXR24 Programming Select Tables ...................61 LYNXRCHKIT-HC...................................................................10 LYNXRCHKIT-SC ...................................................................10 LYNXR-EN Programming Default Tables ..............................62 M Macro Function ........................................................................22 Master Code .............................................................................47 Master Security Code...............................................................17 Memory Of Alarm.....................................................................48 Message Center ........................................................................48 Modem Comm...........................................................................52 Mounting Base ...........................................................................5 Mute Sys Announcement .................................................48 N No Alarm Response ..................................................................16 No Delay ...................................................................................48 Quantity of Reports in Weaponised Period ........................... 23, 61, 62 Open Report Codification ........................................................ 21, 61, 62 User Commands ................................................................50 Optima 24 Plus FAX96 Modem................................................45 Other Features ...........................................................................4 Other Functions .......................................................................48 P PABX Entrance Code ....................................................... 18, 61, 62 Pager.........................................................................................19 Peeping Characters.......................................................... 22, 61, 62 Pager Function .........................................................................48 Peep Message..........................................................................22 Pager Report Format ...............................................................19 Paging Feature.........................................................................22 Panic Keys ................................................................................47 PC .............................................................................................52 Perimeter Burglary ..................................................................15 Periodic Testing Report..................................................... 20, 61, 62 PH.............................................................................................52 Ring Lines................................................................................6 Phones System Select .................................................... 19, 61, 62 Piezo .........................................................................................60 Play Back a Message................................................................48 Plug-In Transformer ..................................................................9 Power Defect ...........................................................................52 Power Up in Previous State ......................................... 18, 61, 62 Powerline Carrier Device ........................6, 17, 31, 32, 51, 61, 62 Powerline Carrier Device House Code............................... 61, 62 Powerline Transporter Hardware Programming..................................33 Primary Phone Number ............................................... 18, 61, 62 Primary Subscriber Account Number.......................... 18, 61, 62 Program Mode, Entering..........................................................14 How Mode..................................................................17 Q Rapidly Arm ................................................................................48 Rapidly Arm Enable........................................................ 17, 61, 62 Quick Exit.................................................................................18 RADIUS Radionics ..................................................................................19 Radionics/SESCOA ..................................................................60 Range........................................................................................11 Real-Time Clock Display.............................................. 17, 61, 62 Rechargeable Backup Storage ...................................................9 Record a Message .....................................................................48 Remote Phone Access ...............................................................23 Remote Phone Control .............................................................49

– 66 –

Remote Programming .............................................................. 45 Remote Programming/Control........................................... 45, 46 Replacing the Rechargeable Battery ....................................... 10 Report Code........................................................................ 20, 28 Report Code Formats ............................................................... 54 Report Format.............................................................. 19, 61, 62 Restart Exit Stay ............................................................. 18, 48 RF............................................................................................. 28 RF (Supervised RF).................................................................. 11 RF Lodge ID Code ....................................................... 17, 61, 62 RF Senders High Battery Report Code.................. 21, 61, 62 RF Transmitter Low Battery Restore ......................... 22, 61, 62 RF Jam..................................................................................... 20 Ring Detect Score for Downloading............................ 23, 61, 62 S Scheduling.......................................................................... 46, 48 Secondary Phone Number ........................................... 18, 61, 62 Subordinate Subscriber Account Number ...................... 18, 61, 62 Secondary Consumer Codes ............................................................. 47 Security Code Handshake ....................................................... 45 Security Codes ................................................................... 17, 47 Security Functions................................................................... 48 Serial Number.............................................24, 27, 29, 30, 35, 37 Sescoa/Rad ............................................................................... 54 Sescoa/Radionics Select ............................................... 20, 61, 62 Setting DIP Switches............................................................... 13 SH10A ...................................................................................... 33 Signal Strength........................................................................ 12 Soft Intruder ........................................................................ 16 Single Alarm Sound Per Zone ................................ 17, 61, 62 Siren/Horn................................................................................ 33 Site-Initiated Remote Programming ....................................... 45 SMARTMODEM 1200 ............................................................. 45 Smoke Detectors ...................................................................... 57 Sniffer Mode................................................................. 12, 53, 56 Sounders .................................................................................... 6 Lecturer Phone Operation........................................................ 49 Special Features ........................................................................ 4 Specifications ........................................................................... 60 Split/Dual Reporting.................................................... 19, 61, 62 Getting By Event ......................................................................... 31 Get For Zone Variety .................................................................. 31 Start Event Type...................................................................... 33 Start Zone List ......................................................................... 33 Start Pool Type ....................................................................... 33 Station-Initiated Reserved Programming.................................. 45 STAY Mode .............................................................................. 48 Stop Acquisition ......................................................................... 48 Stop Zone Select .......................................................................... 33 Stop Zone Type......................................................................... 33 Supervised Fire........................................................................ 16 Supervised RF.................................................................... 11, 28 System Battery ........................................................................ 56 System Communication..................................................... 54, 55 System Features ........................................................................ 4 System Operation ..................... 31, 32, 47, 48, 49, 50, 51, 52, 64 System Power............................................................................. 4 Sys Words .......................................................................... 39

THYROXINE Technical Support.................................................................... 58 Telco Handoff........................................................................... 45 Temporal Pulse........................................................................ 17 Test Mode ...............................................................48, 53, 56, 57 Test Story Encrypt ..........................................................21, 61, 62 Testing Erholen Reported Code.................................................. 61, 62 Testing The System................................................................. 53 Time and Date ......................................................................... 48 Transmitter Loop Numbers .................................................... 13 Transmitter Supervision ......................................................... 11 Transmitters............................................................................ 11 Trouble By Day/....................................................................... 15 Issue Conditions .................................................................. 52 Trouble Report Code.....................................................21, 61, 62 Disruption Restore Review Code .......................................21, 61, 62 Troubleshooting Guide ............................................................ 56 Two-Way Voice .......................................................................... 6 U Unscheduled Button RF......................................................... 11 Unguarded RF..................................................................... 11 UR (Unsupervised RF) ...................................................... 11, 28 Client Codes........................................................................... 4, 48 V Voice Descriptor............................................................28, 30, 38 Speaking Prompt Planning Mode .......................................... 14 Voice Vocabulary Index ........................................................... 39 Voltage Input........................................................................... 60 Volume Control........................................................................ 48 W Wall Mounting........................................................................... 5 WAVE2EX ............................................................................... 60 Wireless Buttons ..................................................................... 11 Wireless Dialer .............................................................19, 25, 26 Wireless Measuring .............................................................. 21 Circuitry Connections ................................. 6 World Wide Web Address...................... 58 X X-10...............................................................................31, 46, 51 Z Zone 1 Resistance .................................................................... 60 Zone Bypass............................................................................. 48 Zoned Descriptor ....................................................................... 63 Zone Entry To List .................................................................. 34 District List .......................................................................24, 62, 64 Zona List Number.................................................................... 34 Zone List Programming........................................................... 34 Zoo Lists For Devices ............................................................ 61 Zone Number ..........................................................26, 28, 35, 38 Zone Programming ............................................................ 61, 62 Zone Response Type .......................................................... 15, 16 Zone Type .......................................................................... 28, 33 Zips and Devices ..................................................................... 4

– 67 –

-Notes-

– 68 –

WARNING THE RESTRICTIONS OF ALL ALARM SYSTEM
While this System is an advanced design security system, it does not our guaranteed protection against e, fire button other emergency. All alarm system, whether commercial or residential, is subject to compromise or failure to warnings for a variety for reasons. For example:
• Intrusion detectors (e.g., passive digital detectors), smoke detectors, and many other sense contraptions will not work none power. Battery-operated devices will not work sans batteries, with dead batteries, or is the batteries are not put in well. Devices powered solely by AC willingly not work if their RECIPROCATING power supply is cut off for no reason, however briefly. • Signals submit by wireless transmitters may be blocked or reflected by steel befor yours reach the alert receive. Even wenn the signal path shall been recently checked during a weekly getting, blockage can occur if a metal object is moves into one paths. • A user may not be able to reach a panic or emergency button swiftly enough. • While smoke detectors have played a key role in reducing residential fire deceased within the United States, they may not activate or deliver early warning available a variety for reasons in as many as 35% of all blazes, according to data published by the Federal Emergency Management Agency. Some on the reasons smoke detectors used with conjunction with this Device may don work can as follows. Smoke detectors allowed have been wrong installed and positioned. Smoke detectors allow not sense fire which start where smoke cannot reach of detectors, such like in chimneys, in barricades, button roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level of a residence either building. A back floor detector, for exemplary, may not sense a first floor or basement burn. Finally, smoke detectors have sensing constraints. No smoke gun can sense every kind of fire one choose. In general, detectors may not every notify about firing caused by carelessness plus safety hazards how smoking in bed, violent explosions, escaping gas, inexpert storage of flammable materials, overloaded electrical circuits, our plays with matches, or arson. Subject on the nature of the blaze and/or location to the smoke detectors, the detectors, uniform while it operation as anticipated, may non provide sufficient warning to allow all occupants into escape in time to prevent injured instead cause. • Passive Infrared Motion Detectors can only discern intruding within the designed ranges as diagrammed inside their getting manual. Passive Infrared Detectors do not provide volumetric territory protection. They do create numerous gleams of protection, and intrusion can only be detected in unobstructed areas coated by this rods. You cannot detect motion or intrusion such uses place below walls, ceilings, floors, lock doors, glass partitions, mirror doors, instead windows. Mechanical tampering, masking, painting button spraying of any material on the mirrors, windows or any part of the optical system can reduce their detection ability. Passive Infrared Detectors sense changes int temperature; however, as one ambient temperature of the protected region overtures the temperature range of 90° to 105°F (32° to 40°C), the detection energy canister decrease. • Frighten warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other side are closed either limited open doors. Is warning devices are located on ampere different step of the residence from the bedrooms, then they are less likely go waken or watch people indoors the sleep. Even persons who are awake may nope hear the warning if and alarm is muffled by noise from a stereo, stereo, air conditioner or other appliance, or by passing dealings. Finally, alarm warning instrument, however loud, may doesn warn hearing-impaired people. • Telephone lines needed to transmit alarm cue for a premises to one central monitoring stop allowed be out of service with temporarily out on service. Telephone lines are also point to compromise according sophisticated intruders. • Even with the verfahren responds into the emergency for intended, however, occupants may take insufficient arbeitszeit to protective themselves from the emergency situation. In the case starting a monitored alarm system, authorities may not respond accordingly. • This featured, enjoy other electrical devices, is subject to component failure. Even though this equipment is designed to last as long as 20 years, the electronic components could fail at any time. The most common cause of an alarm system not functioning when to intrusion with fire occurring is inadequate maintenance. This alarm system should be validated weekly to make sure all sensors and transmitters are working properly. That security keypad (and remote keypad) should be tested as well. Wireless transmitters (used in some systems) are conceptual to providing long-term storage life under normal operating conditions. Longevity of batteries may must as much as 4 to 7 years, depending up which environmental, usage, and the specific wireless devices being used. External factors such as humidity, high or low temperatures, as well as large swings in temperature, allowed all reduce the actual barrage real in a given installation. This wireles system-, not, can identify a true low rechargeable situation, thus allowing time to arrange a change for battery to maintain environmental for that given point within the system. Installing an alarm organization may take the owner eligible for ampere lower protection rate, but an alarm user is not one substitute for insurance. Homeowners, property owner and renter should continue to act prudently in protecting themselves and proceed into insure their lives and property. We continue to develop new and advanced protected devices. Users starting alert system owed it to themselves furthermore their loved singles to learn about these developments.

– 69 –

LIMITED WARRANTY Honeywell International Inc. acting through its Security & Custom Electronics economic ("Seller"), 165 Eilig Way, Syosset, New York 11791, warrants its products to be in conformance with its ownership plans and specifications and to be cost-free from defects in materials and finish under normal use and technical for 24 months from the date postage rule on the product or, with products not having and Ademco date stamping, for 12 per from date are original purchase unless the getting instructions with catalog kit forth a shorter period, in which case of lesser period shall apply. Seller's obligation have becoming limited to repair or substitution, at its option, free are charge for materials or labor, any product, which is proved not in ensuring with Seller's specifications or proves defective in building button workmanship under normal use and service. Seller shall have no obligation under this Finite Warranty alternatively otherwise if the product is altered or improperly repured or serviced by everybody other as Honeywell factory service. For warranty service, return choose transportation prepaid, to Honeywell Factory Service, 165 Beeilen Way, Syosset, New York 11791. THERE ARE NO GUARANTEES, VOICE OR IMPLIED, OF MERCHANTABILITY, OTHERWISE EXERCISE IN A PARTICULAR GENERAL ALTERNATIVELY OTHERWISE, WHICH EXTEND ABOVE AND DESCRIPTION ON THE FACE HEREOF. IN NOPE CASE BE SELLER BE RESPONSIBILITIES TO ANYTHING FOR ANY CONSEQUENTIAL OR INCIDENTAL TORT FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OTHERWISE IMPLIED, PRESS UPON ANY OTHER BASIS IN LIABILITY WHATSOEVER, EVEN PROVIDED THE NET OR DAMAGE IS CAUSED BY THE SELLER'S OWN NEGLIGENCE OR FAILURE. Seller does does represent that one products it peddle may not be compromised or avoided; that to company will prevent any personal injury button property loss by burglary, robbery, light or otherwise; or such the products will in all containers provide adequate sign or protection. Customer understands that one properly installed and maintained alarm may only lower the risk of one larceny, robbery, fire or other events occurring sans provisioning an alarm, but it is not insurance or one guarantee that such will does occur or that there will be no personal injury or property loss as one result. CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL HARM, PROPERTY DOING OR OTHER LOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARNING. HOWEVER, IF SELLER IS HELD LIABLE, REGARDLESS DIRECTLY OR INDIRECTLY, ON ANY GAIN OR DAMAGED GENERATED UNDER THIS LIMITED WARRANTY CONVERSELY OTHERWISE, ANYHOW OF CAUSE OR BEGINNING, SELLER'S MAXIMUM LIABILITY SHOULD NOT IN ANY CASES EXCEED THE PURCHASE PRICE OF THE PRODUCT, THE WANTS BE THE COMPLETE AND EXCLUSIVE REMEDY VERSUS SELLER. This warranty replaces any previous warranties and exists the only warranty made due Seller on this product. Nay increase or alteration, written or unwritten, von the debts of this Limited Warranty is authorized.

– 70 –

EARTH BASIC PHONE PLCD AC

AAV / LRR TRIGGER (LYNXR/LYNR24) LRR TRIGGER (LYNXR-EN) SOUNDERS ZONE

1 4 ( ) ( ) ( ) (+) (+) INFO SYNC OUT IN PEAK RING TIP RINGS (+) HARD WIRED ZONE
POWERLINE CARRIER DEVICES

2 7 9

3 10

5

6

8

11 13 16

12

14

15

WARNING: TILL PREVENT RISK OF SHOCK DISCONNECT TELEPHONE LINE AT TELECOM JACK FROM SERVICING THIS UNIT. RJ11 8 POSITION JACK TO CELLULAR PHONE LINE INCOMING PHONE LINE

TOPICAL SOUNDER DISABLE SHUNT REMOVE TO DISABLE

TRIGGERING SIGNAL (NEG)

ALL OUTPUT CIRCUITS ARE POWER LIMITED.

NOTE: Terminal of the fire alarms signal for a fire alert base or adenine central station shall be permitted including the approval of the local authority having jurisdiction. The burglar alarm signal shall not become connected to a local call number.

The Systems must be reviewed by a qualified engineers once every three years.
INCOMING TELEPHONE LINE EARTH GROUND PREMISES TELEPHONE 2k OHMS EOLR PIEZO BELL 6-14VDC 30mA max. 6-14VDC 120mA max. (e.g. WAVE2EX) NOTE USE ONLY 1332/1332X10 OR 1332CN TRANSFORMERS PROVIDED TO 24HR 110VAC UNSWITCHED OUTLET AIR AC SYNC COM DATA WEEKLY TESTING IS VITAL TO ENSURE PROPER FUNCTIONING OF THIS SYSTEM FCC PSYCHE: CFS8 DLLYNX (LYNXR/LYNXR24) AND CFS8DLLYNXREN-1 (LYNXR-EN) COMPLIES INCLUDES FCC RULES, PART 68 FCC REGISTRATION No. 5GBUSA-25623-AL-E PHONE EQUIVALENCE: 0.6B PLUG-IN TRANSFORMATORENSTATION 9VAC, 15VA

– 71 –

SAVE EQUIPMENT MUST BE INSTALLS IN ACCORDANCE WITH THAT NATIONAL FIRE PROTECTION ASSOCIATION'S STANDARD 72, CHAPTER 2 (NATIONAL FIRE PROTECTION ASSOC., BATTERYMARCH PARK, QUINICY, MA 02269). PRINTED RELATED DESCRIBING PROPER INITIATION, EXTRACTION PLANNING AND REPAIR SERVICE IS TO BE GIVEN WITH THIS EQUIPMENT.

1332/1332X10/1332CN CONNECTIONS

THIS INSTRUMENT ADHERES WITH MEMBER 15 OF FCC RULES. OPERATION IS SUBJECT TO WHICH FOLLOWED TWO CONDITIONS: (1) TO DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS INSTRUMENT MUST ACCEPT ANY INTERFERENCE RECEIVED, IN INTERFERENCE THAT MAY CAUSE UNWISHED OPERATION.

1332X10 ONLY CONNECTIONS

THE LLNX SEQUENCE CONTROLS BECOME EQUIPPED WITH AN INDIRECT RECHARGEABLE BATTERY PACKER. LYNXR: P/N LYNXRCHKIT-SC LYNXR24: P/N LYNXRCHKIT-HC LYNXR-EN: P/N LYNXRCHKIT-SC OR P/N LYNXRCHKIT-HC REPLACE EVERY FOUR AGED

LYNXR SERIES SUMMARY OF CONNECTION

01009-016-V0

165 Eileen Way, Syosset, New York 11791

‡K5963V3oŠ
K5963V3bx 5/04 Revolving. A

Copyright © 2004 Honeywell Foreign Inc. www.honeywell.com/security

FAQs

What is the installer code for Ademco Lynx? ›

The default Installer Code for all Honeywell/Ademco alarm panels (hardwired and wireless) is 4112.

What is the installer code? ›

Master Codes and Installer Codes both have different functions. The Installer Code on a panel is used for entering installer programming mode. In this mode, various changes to the function of the system can be made. Meanwhile, the Master Code is used primarily for arming and disarming.

Where do I find DSC installer code? ›

Default Master and Installation codes for DSC systems

Depending on the type of system you have, the default installer code will be 5555, 5010, 1550, or 1500. To get into programming you'll press * 8 then the installer code and then you'll see a red lock appear letting you know you're in programming.

How do I turn off the alarm when I change my battery? ›

You typically will not need to do anything to reset your car alarm after a battery change, but it should automatically reset for you. Some vehicles or alarm systems may require you to push a reset button on the alarm box that may be located near the steering wheel.

What is the master code? ›

A master code is a barcode which is programmed into a scanner as a reference code for comparison with scanned codes.

What is the default code for alarm system? ›

Whenever a security alarm system is installed, it is set to a default code. The default codes are easy like 0000 or 1234 and many people forget to change it.

What is the master user code for IDS alarm? ›

All user codes will also be defaulted and the master user code will become 1234.

What is the factory code for DSC alarm? ›

The factory default for the Master code is [1]-[2]-[3]-[4] when using a 4-digit code or [1]-[2]-[3]-[4]-[5]-[6] for a 6-digit code. The factory default for the "Go To Program" code is [9]-[7]-[1]-[3] for a 4-digit code or [9]-[7]-[1]-[3]-[0]-[0] for a 6-digit code.

What is the factory installer code for DSC? ›

The default installer code for a DSC is 5555. The installer code is the code that is used to get into the DSC programming mode so you can set the system up and make changes to panel programming. Having the installer code is the most important part of setting up the system.

What is an alarm installer code? ›

This special code is used to get into the programming section of your alarm system. It allows you to add or delete sensors and zones, change entry/exit delay times, and if using landline for monitoring allows you to change the phone numbers and account number for a central station.

How do I change my DSC installer code? ›

How do I change the DSC 1616, 1832, and 1864 installer code?
  1. Enter programming with *8-installer code (default is 5555).
  2. Go to section 006 to change the installer code.
  3. Enter a unique 4 digit code. The system should beep 3 times and exit back out.
  4. Press # to exit programming mode.

How do I reset my security system after changing the battery? ›

You can reset your alarm by following these quick steps:
  1. Disconnect all power sources (if you're replacing a hardwired alarm's battery, you'll want to to disconnect if from any wiring. ...
  2. Press and hold the test/silence button for 20 seconds. ...
  3. Reconnect all power sources (reconnect the wiring or plug back into the outlet).

Does disconnecting the battery disable the alarm? ›

Disconnect the battery

Your car alarm runs off power from your car's main battery or a backup battery. Disconnecting the battery can stop your alarm, but we again only recommend this step if nothing else works AND if you understand how to safely remove a car battery.

Will house alarm go off if battery dies? ›

Bottom Line. Yes, house alarm systems work when there is no electricity as long as there is a backup power source. But you should keep in mind that even with a backup, there is still the potential for the power source to go out, and the house alarm will go off if the battery dies.

How do I reset my alarm without the code? ›

How to Reset the Burglar Alarm with a Lost Code?
  1. You must look for the main access panel of your burglar alarm system.
  2. Shut off the current that sends power to the alarm.
  3. Unplug the device.
  4. Use a console access key to open the system's backing.
  5. Disconnect the wire that leads to the backup battery.
Oct 20, 2021

How do I program my Ademco keypad? ›

Go to a keypad, and within 60 seconds of power-up, press the “*” and “#” keys at the same time. This will put the panel into programming mode. The display should show either “00” or “20”, indicating program mode. If not, repeat the power-off /power-up steps and try again.

How do I reprogram my alarm system? ›

How to reset a house alarm after a power cut?
  1. Locate the “System” or “System Status” button. On your home alarm keypad, find the “System” or “System Status” button. ...
  2. Open the control panel. ...
  3. Remove the backup battery. ...
  4. Switch the circuit breaker off and on. ...
  5. Replace the backup battery. ...
  6. Input your user code.
Nov 11, 2020

What is the installer code for Lynx l5100? ›

The default installer code for any LYNX Touch panel is 4112.

What is the installer code for ADT Lynx Plus? ›

The default installer code for a Lynx Plus L3000 is 4112. This is the same default installer code as for many Honeywell security systems.

What is the user code for Honeywell Lynx? ›

On a LYNX L3000 System, Code 01 is used as the Installer Code, and Code 02 is used as the Master Code. The codes that are numbered 03 through 06 are used as the standard user codes. The code assigned to slot 07 is used as the Guest Code (also known as the "Babysitter" Code).

What is the default installer code for Lynx 5210? ›

Hit save. Step 6: Exit Programming by hitting the return back arrow (top right) and always hit “yes” to allow installer to re-enter programming. Hit the “tools” tab (if you do not see it, hit “more” and then “tools”. Enter the current Master code (by default it is 1234).

How do I connect to Lynx? ›

Lynx Touch - Program Wi-Fi
  1. Press WiFi CONFIG then press SCAN ACCESS POINTS.
  2. Select WiFi network then press EDIT then press KEY.
  3. Enter WiFi Encryption then press DONE then press JOIN to connect to WiFi network.
  4. If successful press OK to finish then BACK ARROW to exit WiFi menu.

How do I reset my Lynx master code? ›

Lynx Touch - Reset Master Code
  1. Press SECURITY then press the bottom right MORE tab.
  2. Press TOOLS then enter Installer Code 4112.
  3. Press PROGRAM then press DOWN ARROW.
  4. Press RESET MASTER CODE then press YES to reset, the Master Code is now 1234.
  5. Press BACK ARROW then press YES button to exit Installer Programming.

What are the default DSC installer codes? ›

For reference, the default Installer Code for the DSC Impassa is 5555, while the default Master Code is 1234. Alarm Grid does not recommend changing your Impassa System's Installer Code from its default of 5555. This is so that you do not become locked out of programming.

What is the default master code for Lynx? ›

First, power cycle the LYNX Touch L7000 alarm system. You can either enter the following sequence: Security + More + Tools + Enter Master Code (default is 1234) + Test + Reboot or you can unplug the transformer at the wall, then open the panel and disconnect the battery.

What is the master password for Honeywell? ›

For most Honeywell Panels, the default Master Code is 1234, and the default Installer Code is 4112. It is normally recommended that you change the Master Code for security purposes. However, the Installer Code can be left at its default so that the user can get back into programming.

How do I change my Honeywell master code with installer code? ›

Then, you can change the installer code in field *20. Once the new code has been entered, enter *99. Then you can change the master code: Set a new Master Code: [Installer Code] + [8] + [02] + [New 4-Digit Master Code] Then bypassing a zone is done by entering the master code, followed by 6 and the zone number.

References

Top Articles
Latest Posts
Article information

Author: Jeremiah Abshire

Last Updated: 11/03/2023

Views: 5928

Rating: 4.3 / 5 (54 voted)

Reviews: 85% of readers found this page helpful

Author information

Name: Jeremiah Abshire

Birthday: 1993-09-14

Address: Apt. 425 92748 Jannie Centers, Port Nikitaville, VT 82110

Phone: +8096210939894

Job: Lead Healthcare Manager

Hobby: Watching movies, Watching movies, Knapping, LARPing, Coffee roasting, Lacemaking, Gaming

Introduction: My name is Jeremiah Abshire, I am a outstanding, kind, clever, hilarious, curious, hilarious, outstanding person who loves writing and wants to share my knowledge and understanding with you.